Radar Vectors
FAA Order Cancelled Issued Mar 1, 1975 AGL-464 3 pages Copy saved Nov 24, 2026

Order 6980.19 Replacement of Selenium Rectifiers in the Engine- Generator Transfer Circuitry

This document is cancelled. It may have been replaced. Check the official source before relying on it.

Official source ↗ Open PDF

Text read by OCR from a scanned file. Check the original, as some words may be misread.

ORDER DEPARTMENT OF TRANSPORTATION FEDERAL AVIATION ADMINISTRATION GL 6980.19

ORDER DEPARTMENT OF TRANSPORTATION FEDERAL AVIATION ADMINISTRATION GL 6980.19

GREAT LAKES REGION

3/3/75

Replacement of Selenium Rectifiers in the Engine-Generator SUBJ: Transfer Circuitry

1. PURPOSE. This Order authorizes the replacement of selenium rectifiers with silicon rectifiers in the engine-generator cirpuitry for better reliability.

GREAT LAKES REGION

2. DISTRIBUTION. This Order is distributed. to Section level and. above in the Airway Facilities Division and. to.all Airway Facilities Fietd Offices.

3. REFERENCES. Instruction Manual issued. for each respective enginegenerator.

4. BACKGROUND. Deterioration of selenium rectifiers has caused numerous engine-generator transfer malfunctions and in several instances fires have been directly attributed. to this cause. As the selenium rectifier ages, its forward resistance increases, redpcing the voltage across the TR relay, causing it to operate sluggishly with ultimate failure.

5. APPLICATION. This modification applies to all .engine generators having selenium diodes installed. in their TR circuit.

6. MATERIAL REQUIRED. On most engine-generators only one silicon diodes IN 3487, NSN 5961-00953-4538, is required. With certain engine-generator plants, however, a higher rated. capacitor rated. at 15-16 mfd 450 WVDC and an additional 1000 ohm 3-5 watt varliable type resistor also will be required. DO NOT USE A CAPACITOR WHOSE CASE IS CONNECTED TO A LEAD SINCE IT WILL BE INSTALLED ACROSS AN UNGROUNDED 208 VOLT SOURCE.

7. SOURCE OF MATERIAL. Obtain diode from facility stock or the FAA Deppt. When necessary obtain capacitor and. resistor from station stokk or procure locally.

Distribution: Initiated By: AGI-445

FAA Form 1320-1 (7–71) supersedes previous edition U.S. GOVERNMENT PRINTING -0-439-727

auon numner on top line. Type date on line below. Type"'Appendix" and number on kext line. GL 6980.19 3/3/75

8. SPECIAL TOOLS AND TEST EQUIPMENT REQUIRED. None.

9. SCHEDULE To be performed by field maintenance personnel as soon as practicable, but not to exceed 60 days from date of this Order.

10. ESTIMATED TIME REQUIRED. 4 manhours.

11. DISPOSITION OF SURPLUS PARTS. None.

12. INSTALLATION PROCEDURES

12. INSTALLATION PROCEDURES

a. Lock out the engine-generator.

b. Rempve a lead. from the battery supply.

C. Isolate the engine-generator panelboard. by the use of the bypass switch.

d. Replace the existing selenium diode with the silicon diode.

Return the engine-generator to its normal operating position andmeasure the voltage across the capacitor and. relay coil in the TR circuit.

f. If the measured. voltage is below the voltage rating of the capacitor and. coil, modification is complete.

g. If the measured. voltage is above their ratings, isolate the plant, remove the battery lead, and replace the capacitor with one having a higher voltage rating, and/or install the variable resistor in series with the relay coil. Adjust the resistor so that the voltage drop across the coil does not exceed. its rating.

h. Replace the battery lead. and return the engine to normal standby status.

13. TEST AFTER INSTALLATION. Test the engine-generator to determine that its transfer operation is satisfactory.

14. RESULTS AFTER INSTALLATION. Replacing the selenium diode with a silicon diode will provide better reliability to engine-generator plants. Five Typing l ines Left

Type "Page", and the page Type "Chap" and the chapter number on top line. number on line below. Type "Par" and paragraph number on next line. Page 2

FAA FORM 1320-11(2-70) SUPERSEDES PREVIOUS EDITION DIRECTIVE TYPING GUIDE - EVEN PAGE

FAA FORM 1320-11(2-70) SUPERSEDES PREVIOUS EDITION DIRECTIVE TYPING GUIDE - EVEN PAGE

3/3/75 GL 6980.19

15. CORRECTIONS TO INSTRUCTION MANUAL. Correct wiring diagram and. parts list as required.

16. CORRECTIONS TO INSTALLATION DRAWINGS. None.

OGERRY L. FASIG Acting Chief, (Airway Facilities Division, AGL-400