Order 6110.7E Maintenance of the Oceanic Display and Planning System (ODAPS)
This document is cancelled. It may have been replaced. Check the official source before relying on it.
Text read by OCR from a scanned file (1 of 102 pages). Check the original, as some words may be misread.
ORDER 6110.7E
ORDER 6110.7E
MAINTENANCE OF THE OCEANIC DISPLAY AND PLANNING SYSTEM
(ODAPS)
September 17, 2003
U.S. DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
Distribution:Selected Airway Facilities Field and Regional Offices; ZAF −600 Initiated By:AOS −300
RECORD OF CHANGES DIRECTIVE NO. 6110.7E
CHANGE SUPPLEMENTS CHANGE SUPPLEMENTS TO BASIC
CHANGE SUPPLEMENTS CHANGE SUPPLEMENTS TO BASIC
OPTIONAL TO BASIC
OPTIONAL
FAA FORM 1320-5 (6-80) USE PREVIOUS EDITION
Page i
FOREWORD
1.PURPOSE.
This handbook provides guidance and prescribes technical standards and tolerances, and procedures applicable to the maintenance and inspection of the Oceanic Display And Planning System (ODAPS) au− tomation. It also provides information on special methods and techniques which will enable mainte− nance personnel to achieve optimum performance from the equipment. This information augments in− formation available in instruction books and other handbooks, and complements the latest edition of Or− der 6000.15, General Maintenance Handbook for Air− way Facilities.
FAA FORM 1320-5 (6-80) USE PREVIOUS EDITION
2.DISTRIBUTION.
This directive is distributed to selected offices and services within Washington headquarters, the Wil− liam J. Hughes Technical Center, the Mike Monroney Aeronautical Center, regional Airway Facilities divi− sions, and Airway Facilities field offices having the following facilities/equipment: ODAPS.
3.CANCELLATION.
This order cancels Order 6110.7D, Maintenance of the Oceanic Display and Planning System (ODAPS) dated 1/22/02.
4.EXPLANATION OF CHANGES.
a. Configuration Control Decision (CCD) N22771 authorizes the addition of the ODAPS equipment and channel interface cables for the Host and Oceanic Computer System Replacement (HOCSR) Phase 3 program. The Symmetrix 5630 and Service Processor (SP), and the Monitor and Control (M&C) subsystem will be added to the ODAPS. Additional Enterprise Systems Connection (ESCON) channel interface cables will be connected to Channel Path Identifiers (CHPID) 82, 83, DA, and DB.
b. CCD N23617 uses the IBM 6400 −050 printer as a coaxial−attached replacement for the existing 3268 Keyboard Video Display Terminal (KVDT) Printer Replacements (KPR). This is part of the HOCSR Phase 4 program.
c. CCD N23980 uses the IBM 6400 −015 printer as a coaxial−attached replacement for the existing IBM 4245 −012 High Speed Printer (HSP). This is part of the HOCSR Phase 4 program.
5.MAINTENANCE AND MODIFICATION PROCEDURE.
a. The Order 6000.15, this handbook, the applica− ble equipment instruction book and other applicable handbooks shall be consulted and used together by the maintenance technician in all duties and activities for the maintenance of the ODAPS automation. These documents shall be considered collectively as the single official source of maintenance policy and direc− tion authorized by the Operational Support (AOS) Program. References located in the appropriate para− graphs of this handbook entitled Chapter 3, Standards and Tolerances, Chapter 4, Periodic Maintenance, and Chapter 5, Maintenance Procedures shall indi− cate to the user whether this handbook and/or the equipment instruction book shall be consulted for a particular standard, key inspection element or per− formance parameter, performance check, mainte− nance task, or maintenance procedure.
b. The latest edition of Order 6032.1, Modifica− tion to Ground Facilities, Systems, and Equipment in the National Airspace System, contains compre− hensive direction concerning the development, autho− rization, implementation, and recording of modifications to facilities, systems, and equipment in commissioned status. It supersedes all instructions published in earlier editions of maintenance technical handbooks and related directives.
c. Modifications to equipment that are listed in NAS −MD −001, National Airspace System (NAS) Configuration Management Document, as baselined under configuration management shall be in accor− dance with the latest edition of Order 1800.66, Config− uration Management Policy.
6.FORMS LISTING.
In addition to the forms required by Order 6000.15, FAA Forms 6110 −6 and 6110 −7, Technical Perfor− mance Records, will be maintained for each ODAPS facility. These forms are available from the FAA Logis− tics Center (FAALC) under National Stock Numbers
6110.7E
(NSN) 0052-00-905-8002 and 0052-00-905-9000 respectively in units of pads, 50 sheets per pad.
7. RECOMMENDATIONS FOR IMPROVEMENT.
This handbook is under configuration management control as defined in Order 1800.66 and NAS-MD-001. Any changes to the baseline document or requests for deviation from national stan-
Page ii
9/17/03
dards shall be processed through the NAS Change Proposal (NCP) process. Copies of FAA Form 1800 -2, NCP, are provided in the back of this handbook for the convenience of handbook users.
Richard A. Thoma Program Director for Operational Support, AOS–1
Page iii
TABLE OF CONTENTS
TABLE OF CONTENTS
Paragraph Page
Chapter 1. GENERAL INFORMATION AND REQUIREMENTS
100. Objective 1 … 101. Safety 1 … 102. Coordination 1 … 103. Certification 1 … 104. Aircraft Accident 1 … 105. Flight Inspection 2 … 106. Technical Inspection 2 … 107. Periodic Maintenance 2 … 108. Test Equipment and Tools for Periodic Maintenance 2 … 109. References 2 … 110.-199. Reserved 4 …
Chapter 2. TECHNICAL CHARACTERISTICS
Chapter 2. TECHNICAL CHARACTERISTICS
200. System Introduction 5 … 201. System Functional Overview 5 … 202. System Description 5 … 203. System Theory of Operation 17 … 204. Symmetrix 5630 DASD M&C Subsystem 20 … 205.-299. Reserved 22 …
Chapter 3. STANDARD AND TOLERANCES
300. General 23 … 301. ODAPS 24 … 302. FDPS 25 … 303. DASD Subsystem 26 … 304. MTS 27 … 305. S1RPAM Subsystem 28 … 306. ISD Subsystem 28 … 307. TP Subsystem 29 … 308. AIDCS Subsystem 29 … 309. ODL Subsystem 30 … 310. Symmetrix 5630 DASD M&C Subsystem 31 … 311.-399. Reserved 32 …
Chapter 4. PERIODIC MAINTENANCE
Chapter 4. PERIODIC MAINTENANCE
400. General 33 …
Page iv
TABLE OF CONTENTS (Continued)
Paragraph Page
Section 1. PERFORMANCE CHECKS
401. Daily 34 … 402. Weekly 34 … 403. Monthly 36 … 404. Quarterly 37 … 405. Semiannually 42 … 406. Annually 43 … 407. As Required 46 … 408.-449. Reserved 46 …
Section 2. OTHER MAINTENANCE TASKS
Section 2. OTHER MAINTENANCE TASKS
450. Reserved 47 … 451. Weekly 47 … 452. Reserved 48 … 453. Monthly 48 … 454. Quarterly 51 … 455. Semiannually 52 … 456. Annually 55 … 457. Every 3 Years 56 … 458. Every 4 Years 57 … 459. As Required 57 … 460.-499. Reserved 57 …
Chapter 5. MAINTENANCE PROCEDURES
Chapter 5. MAINTENANCE PROCEDURES
500. General 59 … 501. Remote Support Facility Operations for the 9672-RA4 Processor 59 … 502. Remote Support Operations for the ODAPS 5630 DASD Subsystem 60 …
Section 1. PERFORMANCE CHECK PROCEDURES
503. FAA Form Entries 61 … 504. Check T-Bar Variswitch Operation and Battery Backup 61 … 505. Check Power Cords, Cables, and Connectors 61 … 506. Service Level Certification 64 … 507. Check S1RPAM Processor Interface Cards 64 … 508. Check G3 Switchover Operation 65 … 509. Check TP or ISD Server Switchover Operation 65 … 510. Check TP or ISD LAN Switchover Operation 66 … 511. Check TP SC Switchover Operation 66 … 512. Check IBM RISC/6000 770 or 771 Processor 66 … 513. Check Disk Array/6000 67 …
Section 1. PERFORMANCE CHECK PROCEDURES
Page v
TABLE OF CONTENTS (Continued)
Paragraph Page
514. Check IBM 4226 or 4232 Line Printer 68 … 515. Check S1RPAM Processor Replacement Operation 68 … 516. Check S1RPAM Processor External Interfaces 68 … 517. Check IBM 7026-H50 Processor 69 … 518. Check ME800A Short Haul Modems 70 … 519. Check Lamps and Audible Tone of the HMC Alarm Box 70 … 520. Check Universal Power Supply 600 or 1000 71 … 521. Check ODAPS-AIDCS-FIR Interfaces (New York ARTCC) 71 … 522. Check ODAPS-AIDCS-FIR Interfaces (Oakland ARTCC) 72 … 523. ODL Unit Level Certification 73 … 524. ODL System Level Certification 73 … 525. ODL Service Level Certification 73 … 526. Check ODL Server Switchover Operation 74 … 527. Check ODL LAN Switchover Operation 74 … 528. Symmetrix 5630 M&C Maintenance Procedures 74 … 529. EMC 5630 Disk Drive/Power Supply Replacement Validation 75 … 530.-549. Reserved 76 …
Section 2. OTHER MAINTENANCE TASKS PROCEDURES
Section 2. OTHER MAINTENANCE TASKS PROCEDURES
550. Clean Printer 82 … 551. Clean Tape Drive 82 … 552. Clean and Inspect Cabinet 82 … 553. Clean Air Filter 82 … 554. Fan Operational Check 82 … 555. Clean and Inspect Equipment 83 … 556.-574. Reserved 83 …
Section 3. SPECIAL MAINTENANCE PROCEDURES
Section 3. SPECIAL MAINTENANCE PROCEDURES
575. Online Certification Data Requirements 84 … 576.-599. Reserved 84 …
Chapter 6. FLIGHT INSPECTION
600.-699. Reserved 85 …
Chapter 7. MISCELLANEOUS
700. Abbreviations and Acronyms 87 … 701.-799. Reserved 90 …
Appendix 1. CERTIFICATION REQUIREMENTS
Table 1. En Route Surveillance Automated Flight Plan (ESAFP) Service 2 … Table 2. Surveillance Flight Plan System (SFS) 3 … Table 3. Surveillance Processing System (SPS) 4 …
Appendix 1. CERTIFICATION REQUIREMENTS
Page vi
LIST OF ILLUSTRATIONS
Figure Page
2-1. ODAPS Subsystem Diagram 6 … 2-2. ODAPS IBM 9672 Channel Interconnects 8 … 2-3. ODAPS IBM 3274 Terminal Interconnects 9 … 2-4. ODAPS S1RPAM Configuration Diagram 12 … 2-5. Oakland ODAPS Cable Configuration Diagram (TP) 13 … 2-6. New York ODAPS Cable Configuration Diagram (TP) 14 … 2-7. ISD System Architecture Diagram 15 … 2-8. ODAPS AIDCS Cable Configuration Diagram 16 … 2-9. Oakland ODAPS Cable Configuration Diagram (ODL) 18 … 2-10. New York ODAPS Cable Configuration Diagram (ODL) 19 … 2-11. Symmetrix DASD Monitor and Control 21 … 5-1. Technical Performance Record (2 Sheets) 62 … 5-2. Success Criteria for Disk Drive Replacement (logall.log) 77 … 5-3. Indication for Disk Drive Resynchronization in Progress (logall.log) 78 … 5-4. Success Criteria for Disk Drive Resynchronization Complete (logall.log) 79 … 5-5. Environmental Log File with No Errors Present (env.log) 80 … 5-6. Environmental Log File with Example Error Present (env.log) 81 …
CHAPTER 1. GENERAL INFORMATION AND REQUIREMENTS
CHAPTER 1. GENERAL INFORMATION AND REQUIREMENTS
100.OBJECTIVE.
This handbook provides the necessary guidance, to be used in conjunction with information available in instruction books and other handbooks, for the proper maintenance of the Oceanic Display And Plan− ning System (ODAPS) automation. It does not cover associated plant, communications, or alternating cur− rent (ac) power equipment maintenance.
101.SAFETY.
Personnel shall observe all pertinent safety pre− cautions when performing duties on the equipment. Refer to Order 6000.15, General Maintenance Hand− book for Airway Facilities, for guidance.
102.COORDINATION.
a. Maximum availability is of prime importance to the users of Airway Facilities (AF) systems, ser− vices, and equipment. Maintenance should therefore be accomplished, to the extent practicable, on the of− fline operating equipment. When it is necessary to perform maintenance on the online operating equip− ment, it shall be coordinated with the appropriate personnel to preclude unanticipated shutdowns.
b. AF personnel shall be familiar with the role of the ODAPS in the National Airspace System (NAS) so that facility shutdowns can be coordinated with the proper agency and non−agency personnel. Partic− ularly, AF personnel shall thoroughly coordinate with Air Traffic Operations (ATO) personnel, in advance, any maintenance activity that may adversely effect the use of a commissioned facility. Furthermore, AF personnel must be familiar enough with ATO proce− dures to ensure that notification is made sufficiently early to allow ATO personnel to take appropriate action. It is expected that ATO personnel will recog− nize the need for releasing equipment at the time scheduled for maintenance and will cooperate in the furtherance of practices that assure continuous and reliable operation. See Order 6000.15 for additional guidance.
c. AF personnel are also responsible for keeping ATO personnel advised of the operational status of all system, subsystem, facilities and equipment. When
unscheduled interruptions occur, prompt notification shall be made to cognizant ATO personnel. They shall be advised immediately when equipment fails, service is restored, the established tolerances are exceeded, or the established tolerances are expected to be ex− ceeded so that ATO can issue the NOtice To AirMen (NOTAM), re−route air traffic, and/or take other nec− essary action. This is especially important where standby or spare equipment is not immediately avail− able.
103.CERTIFICATION.
Refer to Order 6000.15 for general guidance on the certification of systems, subsystems, and equip− ment. Refer to appendix 1 of this handbook for the specific certification requirements of the ODAPS. The NAS Operations Manager/NAS Area Specialist (NOM/NAS) shall initiate daily certification of Enroute Surveillance Automated Flight plan (ESAFP) Service and weekly certification of Surveil− lance Flight plan System (SFS). The Airway Trans− portation System Specialist (ATSS) shall initiate quarterly certification of Surveillance Processing Sys− tem (SPS).
104.AIRCRAFT ACCIDENT.
After receiving information that an aircraft acci− dent has occurred within the service area of the facility for which they are responsible, the following mini− mum actions are required of cognizant AF personnel. See the latest edition of Order 8020.11, Aircraft Acci− dent and Incident Notification, Investigation, and Re− porting.
a. Check the Facility Maintenance Log (FAA Form 6030 −1 and/or applicable Maintenance Man− agement System (MMS) entries) to determine the sta− tus of the system at the time of the accident.
b. Record all Technical Performance Record (TPR) data as found and any other system parameters considered necessary to establish the operational ca− pability of the system.
c. Review the Facility Maintenance Log and the TPR and compile all data pertinent to the accident.
d. Certify entries of FAA Form 6030 −1 or MMS and the TPR. In all cases have another electronics
technician or the supervisor certify the entry, includ− ing the date and time of the entry.
e. AF Accident Investigation. Once ATO re− leases the accident notification message, the AF sector manager will initiate a technical facility evaluation. In addition, the Regional AF Division will designate a Regional AF Accident Representative as a coordina− tor of the AF contribution to the accident investiga− tion and as a liaison with the FAA investigator−in−charge. See Order 8020.11, for the de− tails of and the procedures for the investigation and reporting of an ODAPS related aircraft accident or incident.
f. Records. All station records such as logs, meter reading forms, etc., are official documents and, as such, may be required in case of an investigation re− garding a local aircraft accident and should be safe− guarded.
g. It is imperative that all records be kept current, concise, and accurate. These checks shall be made carefully and completed rapidly. All station records, such as facility logs, meter readings forms, etc., are official documents. They will be needed during an investigation of a local aircraft accident. Additionally, these records will be used for investigating other situ− ations when the operation of the facility is questioned.
105.FLIGHT INSPECTION.
Since ODAPS receives no sensor inputs directly, no ODAPS flight inspection is required. All ODAPS sensor inputs undergo required flight inspection un− der other system procedures.
106.TECHNICAL INSPECTION.
Facility inspections are among the more effective management controls for ensuring the required quali− ty level of maintenance work and equipment and sys− tem performance. See Order 6000.15 for general guidance on inspections and the latest edition of Or− der 6040.6, Airway Facilities NAS Technical Evalua− tion Program (RIS:AF 6040 −8) for details on the intervals and requirements for formal inspections.
107.PERIODIC MAINTENANCE.
Chapter 4 of this order establishes the tasks and schedules that are required for the periodic mainte− nance of the ODAPS automation. These tasks, as scheduled, are the minimum required for the ODAPS automation to meet minimum performance stan− dards.
108.TEST EQUIPMENT AND TOOLS FOR PERIODIC MAINTENANCE.
The test equipment required for performing rou− tine maintenance of the ODAPS automation are man− aged by the latest edition of Order 6200.4, Test Equipment Management Handbook. Tools and sup− plies are specified and managed by the latest edition of Order 4630.2, Standard Allowance of Supplies and Working Equipment for National Airspace System Facilities.
109.REFERENCES.
a. The instruction books and orders which apply to the ODAPS equipment are listed below.
(1)6NASP −5462, Interim Situation Display (ISD), Computer System Operator’s Manual
(2)6NASP −5263, Interim Situation Display (ISD), Software User’s Manual
(3)6NASP −5162, Interim Situation Display, Hardware Design Document
(4)6IBM 3268 Printer Models 1, 2 and 2c Maintenance Information, SY27 −0201 −4
(5)6IBM Maintenance Diagnostic Program Local 3274 Model 1B/1D Display System On−Line Tests, D99 −3274A −01
(6)6IBM 3380 Online Test (OLT) User’s Guide, D99 −3380A −02
(7)6IBM 3480 Online Tests (OLTs), D99 −3480A −00
(8)6IBM Maintenance Diagnostic Program 3880 Storage Director Online Test, DCL −3880A −02 (D99 −3880A −01)
(9)6IBM 4245 Printer Models 12 and 20 Maintenance Information Manual, Volume 1
(10)6IBM 4245 Printer Models 12 and 20 Maintenance Information Manual, Volume 2
(11)6TI 6110.11, Diagnostic User’s Guide for the Series/1 Replacement (S1R) and Series/1 Replace− ment Peripheral Adapter Module (S1RPAM) Volume II
(12)6TI 6110.10, Hardware Installation and Maintenance Manual for the Series/1 Replacement (S1R) and Series/1 Replacement Peripheral Adapter Module (S1RPAM) Volume I
(13)6TI 6110.9, Series/1 Replacement (S1R) and Series/1 Replacement Peripheral Adapter Module (S1RPAM) Handbook
(14)6IBM RS/6000 Enterprise Server Model H50 User’s Guide SA38 −0546 −00
(15)6IBM RS/6000 Diagnostic Information for Multiple Bus Systems SA38 −0509 −06
(16)6Order 6000.15, General Maintenance Handbook for Airway Facilities
(17)6Order 6032.1, Modification to Ground Facilities, Systems, and Equipment in the National Airspace System
(18)6NAS −MD −001, National Airspace System (NAS) Configuration Management Document
(19)6Order 1800.66, Configuration Manage− ment Policy
(20)6Order 8020.11, Aircraft Accident and Incident−Notification, Investigation, and Reporting
(21)6Order 6040.6, Airway Facilities NAS Tech− nical Evaluation Program
(22)6Order 6200.4, Test Equipment Manage− ment Handbook
(23)6Order 4630.2, Standard Allowance of Supplies and Working Equipment for National Airspace System Facilities
(24)6AIX Version 3.2 System Management Guide: Operating System and Devices, IBM, Order Number GC −2486 −00
(25)6AIX Version 4.3 System Management Guide: Operating System and Devices, IBM, Order Number SC23 −4126 −00
(26)6AIX Version 3.2 Problem Solving Guide and Reference, IBM, Order Number SC23 −2204 −04
(27)6Maintenance Information for the IBM 6091 Color Display (Model 19i), IBM, Order Number SY66 −0117 −00
(28)6Setup and Operation for the 6091 Color Displays, IBM, Order Number GA23 −2114 −03
(29)6IBM 4226 Printer User’s Reference, IBM, Order Number GA18 −7182 −00
(30)64226 Printer Operator Reference, IBM, Order Number GA18 −7183 −00
(31)67018 POWER Server Models 770 and 771 Operator Guide, IBM, Order Number SA23 −2698 −00
(32)6Certainty ARRAY/6000 Model 505/510 Deskside Series, Installation Guide, Cambex Corpora− tion, Order Number 081 −448 −003 Rev. C
(33)6IBM 3151 ASCII Display Station Models 11, 31, and 41 Guide to Operations, IBM, Order Num− ber GA18 −2633 −02
(34)6User’s Manual Power Line Filter & Distribution Unit Model 2 −1000/6FA1, CYBEREX Inc., UM −2 −1000/6FA1:1, September 1991
(35)6User’s Manual Power Line Filter & Distribution Unit Model 600/6FA1, CYBEREX Inc., UM −600/6FA1
(36)6RS232 Fallback Switch User’s Manual, Black Box Corporation
(37)6TI 6130.6 Hardware Design Data (HDD) Instruction Book Flight Data Input/Output (FDIO) System, Volume 1, Sections 1 −10 (FDIO −51B)
(38)6POWERstation and POWERserver Common Diagnostic and Service Guide, IBM, Order Number SA23 −2687
(39)6NASP −9102, Equipment Instruction Book, Oceanic Display and Planning System (ODAPS), Hardware Design Document for the Tele− communications Processor
(40)6NASP −9557, Instruction Book, Oceanic Display and Planning System (ODAPS), Operator’s Manual for the Telecommunications Processor
(41)6NASP −9257, Software Instruction Book, Oceanic Display and Planning System (ODAPS), User’s Manual for the Telecommunications Processor
(42)6TI 6110.2, Equipment Instruction Book, Oceanic Display and Planning System (ODAPS) Op− erations and Maintenance Manual for the Telecom− munications Processor
(43)64232 Printer User’s Guide, IBM, SA24 −4386 −01
(44)64232 Printer Operator Panel Instruc− tions, IBM, SA24 −4387 −01
(45)6IBM Info Window II 3153 ASCII Display User’s Guide, IBM, Order Number GA27 −4083 −01
(46)6TI 6110.4, Interim Situation Display In− struction Book
(47)6TI 6110.5, Interim Situation Display (ISD) NDI/COTS Equipment Documentation
(48)6IBM S/390 Support Element Operations Guide, GC38 −3108 −03
(49)6IBM S/390 Installation Manual, SY24 −6156 −04
(50)6IBM S/390 Service Guide, SY24 −6158 −04
(51)6IBM S/390 Hardware Management Con− sole Operations Guide, GC38 −0459 −00
(52)6IBM S/390 Parts Catalog, S123 −1151 −04
(53)6NASP −7211, Computer System Opera− tors Manual (CSOM) for the Air Traffic Services (ATS) Interfacility Data Communications System (AIDCS)
(54)6NASP −7201, Software User Manual (SUM) for the Air Traffic Services (ATS) Interfacility Data Communications System (AIDCS)
(55)6TI 6110.6, Operation and Maintenance Technical Instruction Manual (OMTIM) for the Air Traffic Services (ATS) Interfacility Data Communica− tions System (AIDCS)
(56)6HP NetServer LC II User Guide, HP Part Number 5965 −2497
(57)6ViewSonic E655 User’s Guide
(58)6Epson Printer User’s Guide LQ −570+/1070+
(59)6Motorola Codex 3600 Series User’s Manual
(60)6Channel−to−Channel Adapter or 3088 MCCU Exerciser On−Line Test User Guide, D99 −3150A −05
(61)6NASP −7214, Oceanic Data Link (ODL), Computer System Operation Manual (CSOM)
(62)6TI 6110.15, Technical Instruction Manual for the Oceanic Data Link
(63)6Order 6110.9, Electronic Equipment Mod− ification Handbook Oceanic Display and Planning System
(64)6RS/6000 Enterprise Server Model H80 Series Service Guide
(65)6CDRL D038, System Problem Determina− tion and Maintenance Manual
(66)6RS/6000 Enterprise Server Model H80 Series User’s Guide
(67)6Catalyst 2900 Series XL Installation Guide, Cisco Systems
(68)6CDRL D038, Storage Subsystem Certifica− tion Manual
(69)6NCD NCBridge Software Reference Manual
(70)6Ethercom Model EFTT1003 User’s Manual
(71)6Symmetrix Model 3630/5630 Product Manual
(72)6Device Support Facilities User’s Guide
(73)6IBM 6400 Line Matrix Printers Mainte− nance Information Manual Cabinet and Pedestal Models, S246 −0117 −06
(74)6IBM 6400 Line Matrix Printers Setup Guide, S246 −0116 −02
b. System specifications are available in the fol− lowing document:
(1)6FAA −E −2713, ODAPS Specifications
(2)6FAA −ER −2889, Telecommunication Pro− cessor Specification
(3)6FAA −ER −2896, Interim Situation Display Specification
(4)6CDRL D0027, Host and Oceanic Computer Replacement System, Oceanic Computer Subsystem Functional Specification Baseline
c. The ODAPS utilizes equipment whose mainte− nance is not covered in this handbook. See the latest edition of Order 6170.9, Maintenance of Communica− tion Multiplex (MUX) Equipment, and the latest edi− tion of Order 6170.10, Maintenance of Data Multiplexing Network Equipment, for the mainte− nance of the Bell Dataphone 1600 modem, the Nippon Electronics Co. (NEC) 2400 MR Data Modem, the General Datacomm 201C and 202 modems, and the Codex 6250 Statistical Multiplexers.
110.−199.RESERVED.
CHAPTER 2. TECHNICAL CHARACTERISTICS
CHAPTER 2. TECHNICAL CHARACTERISTICS
200.SYSTEM INTRODUCTION.
The ODAPS improves Air Traffic Control (ATC) for oceanic areas serviced by the FAA. Seven existing ocean− ic control centers have been consolidated into two, lo− cated in the New York and Oakland Air Route Traffic Control Centers (ARTCC). ODAPS will provide each site with automated functions and capabilities which are almost identical to those existing in ARTCCs. It will also support controllers by providing the data needed to grant safe and efficient clearances to aircraft passing through oceanic airspaces.
201.SYSTEM FUNCTIONAL OVERVIEW.
a. The ODAPS exchanges flight plan data and general flight information with the NAS host comput− er. The ISD is responsible for displaying data from ODAPS and relaying controller inputs back to ODAPS. National Airspace Data Interchange Net− work (NADIN) 1A supports the ODAPS interface with Service A, the Aeronautical Fixed Telecommunica− tions Network (AFTN), and Aeronautical Radio, Inc. This interface supports the exchange of weather−re− lated data, flight movements, and various other sup− port data. The AIDCS transfers operational flight information between ODAPS and non−US Flight In− formation Regions (FIR) for flights that are expected to cross the boundary between US airspace and for− eign airspace. The AIDCS translates the flight infor− mation between the NAS format required by ODAPS and the International Civil Aviation Organization (ICAO) format required by the FIRs.
b. The ODAPS transmits to North American Air Defense Command Regional Operations Control Cen− ters the flight plans of aircraft heading toward the United States and penetrating the outer Air Defense Identification Zone, the Canadian Air Defense Identifi− cation Zone, or the Distant Early Warning Identification Zone. The Telecommunications Processor (TP) Servers support the ODAPS interface with TP workstations and Thermal Flight Strip Printers (TFSP) using an Insti− tute of Electrical and Electronic Engineers (IEEE) 802.5 token ring fiber optic Local Area Network (LAN). The TP workstation monitor provides an operator with a visual display of flight strips, general information, and weather messages. TP workstation monitors also pro− vide a visual display for editing messages and for scrol−
ling through a historical recording of messages received. The TP System Console provides an interface to TP for identification of problems and for providing correc− tive action. TFSPs are used to print flight progress and coordination strips. The ODAPS also exchanges flight data with the Enhanced Traffic Management System (ETMS).
c. The ODL servers support the ODAPS interface with ODL workstations and TFSP using an IEEE 802.5 token ring fiber optic LAN. The ODL worksta− tion monitor provides an operator with all the TP functionality. The ODL workstation also provides a visual display for Controller/Pilot Data Link Commu− nications (CPDLC) message processing, outgoing data communications with Radio Operators (RO) for message processing with High Frequency (HF) equipped aircraft, and NADIN II interface for CPDLC position reports to ODAPS. The ODL System Console provides an interface for identification of problems and for providing corrective action. TFSPs are used to print flight progress and coordination strips.
202.SYSTEM DESCRIPTION.
a. The ODAPS is composed of eight subsystems, each of which is discussed in the paragraphs that fol− low. These subsystems are shown in Figure 2 −1, ODAPS Subsystem Diagram.
(1)6Flight Data Processing Subsystem (FDPS).
(a)6Processor 9672 −RA4 −G3.
16S/390 Parallel Enterprise Server. Each S/390 Parallel Enterprise Server 9672 Model RA4, Generation 3 (G3), can be divided into four func− tional subsystems: processor, storage, channel, and power.
26Processor Subsystem. The 9672 −RA4 is a Complimentary Metal Oxide Semicon− ductor (CMOS) processor running at approximately 32 Million Instructions Per Second (MIPS), expandable to 45 MIPS within the same processor family. Each proces− sor subsystem consists of four Processing Units (PU). A PU is the hardware computing element of the comput− er.
6110.7E 9/17/03
Page 6 Chap 2 Par 202
Symmetrix 5630 DASD
ODAPS
Flight Data
Processing
Subsystem
Direct Access
Storage Device
Subsystem
Magnetic
Tape
Subsystem
Series/1
Subsystem
Software
Subsystem
Telecommunications
Processor
Subsystem
3380 Model AD4
3380 Model AE4
3380 Model BD4
3880 Model 3
3380 Model BE4
3480 Model A22
3480 Model B22
7026 Model H50
Gateway Laptop
2391 Plus Printer
Modem Splitter Power
Modem Splitters
Ethernet Hub
A/B Switch
NADIN Modem
7018 Model 770
7018 Model 771
4226 or 4232
SONY Display (20x20)
3151 or 3153
NAS Monitor
FDP
Conflict Probe
Communications
Display
7018 Model 771
4226 Model 302
6091 Model 19i
3151
Tape Drive Model 7208
RS422/RS232 Converter
RS485/RS232 Converter
Workstation Rack
Server Rack
QWERTY 101 Keyboard
Trackball
Modem Splitter
Expansion Chassis
TFSP
7018 Model 770
IBM Mouse
Interim Situation
Display
Transceiver
Server Rack
Space Saver Keyboard
Trackball
NORAD Modem
Short Haul Modem
Air Traffic Services
HP NetServer LC II
HP 101-key Keyboard
HP Mouse
Epson LQ-570 Printer
Interfacility Data
Communications
System
Codex 3600 Modems
UPS 600 or 1000
Distribution Panel
9672 Model RA4
6562 H/W Mgt Console
P200 Monitor
Support Element Console
Modem
Lexmark Optra E Plus Printer
3268 Model 2C
4245 Model 12
3274 Model 41D
3180 Model 1
Power Distribution Unit
PCCA Cards & Tailgates
Communication Cards
Philips 19 inch Monitor
Certainty ARRAY/ 6000 Model 505
Common Console Keyboard
Tape Drive Model 7208
208V PDUs Model 163A445 -1
110V PDUs Model 600/6FA1
Display Controller for X-Windows
Multiple-Station Access Unit
2970 Token Ring Adapter Cards
Common Console Frame
Certainty ARRAY/ 6000 Model 505
Fallback Switch Model 5K-SW901A
Common Console Keyboard
208V Dual PDU Model 163A445-1 110V Dual PDU Model 600/6FA1
110V Single PDU Model 600/6FA1
Multiple-Station Access Unit
2970 Token Ring Adapter Cards
ViewSonic 15-inch Monitor
ME800A Short Haul Modems
Eicon X25 Interface Adapter
7018 Model 770
7018 Model 771
3151
Server Rack
Trackball
Cambex ARRAY/ 6000 Model 505
Common Console Keyboard
Tape Drive Model 7208
Multiple-Station Access Unit
2970 Token Ring Adapter Cards
Oceanic Data Link Subsystem
4226 Model 302
6091 Model 19I
Fallback Switch Model 5K-SW901A
208V Dual PDU Model 163A445-1
110V Single PDU Model 600/6FA1
Workstation Rack
QWERTY 101 Keyboard
TFSP
IBM Mouse
Decision Data IS-482G Terminal
T-Bar Variswitch A/B Switches
Replacement Peripheral Adapter
Module Subsystem
Series 5000
External Modem
Cisco 2924M XL-EN
NCD NC900 Thin Client Lexmark Optra M410 Printer Ethercom EFTT 1003_A
RS/6000 H80 Server
P260 Monitor
Sony DDS-4mm Tape Drive
Keyboard and Pointing Device
Service Processor 6400 Model 050
6400 Model 015
FIGURE 2 −1.ODAPS SUBSYSTEM DIAGRAM
The three possible functions of the PU are determined by the Licensed Internal Code (LIC) which are loaded on it.
FIGURE 2 −1.ODAPS SUBSYSTEM DIAGRAM
a6Central Processor (CP) LIC, which gives the PU the S/390 functionality.
b6System Assist Processor (SAP) LIC, which gives the PU internal system and Input/Output (I/O) control functions.
c6Spare, in this state, the PU per− forms an idle loop program LIC. The 9672 −RA4 uses the CP and SAP functions and maintains one spare for each. The SAP spare if needed will be switched in automatically, where the CP spare requires a Power On Reset (POR) to activate.
36Storage Subsystem. The storage subsystem is distributed across the Multiple Chip Module (MCM) and four memory cards of 128 Mega− bytes (MB) each. The 9672 −RA4 can be configured from a minimum of 512 MB up to 8 Gigabytes (GB).
46Channel Subsystem. The channel subsystem consists of six parallel channel cards, each controlling three channels (12 currently used); and two Enterprise System CONnection (ESCON) fiber optic channel cards, each controlling four channels (two currently used). The parallel channels connect to the existing I/O interfaces. The ESCON channel is used as a Channel−To−Channel (CTC) device allow− ing the two 9672 processors to perform health check− ing operations. The 9672 −RA4 is expandable to 96 parallel channels (in increments of three), and 256 ESCON channels (in increments of four).
56Power Subsystem. The power sub− system is designed with the use of redundant hard− ware, whereby a single power failure will not result in an outage. This also allows for replacement of a failed part without affecting system operation. The 9672 −RA4 frame accepts dual power feeds, allowing separate critical bus input voltage sources.
669672 −RA4 Frame. The 9672 −RA4 frame also contains an IBM Thinkpad Personal Com− puter (PC) which is the Support Element (SE). Its purpose during normal operations is to maintain the Central Processing Complex (CPC), collecting and sending CPC status, hardware messages and operat− ing system messages to the Hardware Management Console (HMC). The SE will be used during periods
of 9672 −RA4 problem determination, service or re− pair maintenance, and also for running diagnostic tests for certification. The SE connects via the Think− pad parallel port to the CPC’s Universal Processor Controller (UPC) card.
76HMC Workstation. The HMC workstation is an IBM PC using Operating System/2 (OS/2) LIC, and is designed to be the main operator console, in order to activate, operate, monitor, and perform recovery tasks of the 9672 −RA4. The ap− plication software is an object oriented design, using a Graphical User’s Interface (GUI) platform. The HMC contains a 21−inch color display monitor; a 3.5−inch Read/Write Optical Cartridge (ROC) drive for backups and microcode patch updates; a Compact Disc−Read Only Memory (CD −ROM) drive for system software and microcode driver loading; and a modem for the reporting of service calls if necessary. The HMC and SE communicate via a Token−Ring LAN. The HMC modem features allow for either a manual or automatic callout to the IBM service center from the HMC, and an optional call in from the IBM service center to the HMC for downloading new patches to the microcode. The use of these features will be strictly controlled. Only the manual call out function will be utilized to report a service call. This leaves control of the system to local ODAPS operational personnel. Refer to Chapter 5, Maintenance Procedures, para− graph 501 of this document for further information and FAA policy concerning this feature.
(b)6Other FDPS Components. The other components of the FDPS consists of the following; IBM 3268 Model 2C and IBM 6400 Model 050 console printers, IBM 6400 Model 015 and IBM 4245 Model 12 high speed printers, IBM 3274 Model 41D terminal control units (System Network Architecture version), IBM 3180 Model 1 display stations, commonly called Keyboard Video Display Terminal (KVDT), Decision Data IS −482G terminals, and T −Bar Variswitch A/B switches. See Figure 2 −2, IBM 9672 Channel Inter− connects and Figure 2 −3, IBM 3274 Terminal Inter− connects. The FDPS processes flight−plan and stored adaption data to prepare flight progress strips and other data that will be output to controller positions. It also processes flight data messages, updates the flight−plan data base, and monitors the health and status of the ODAPS. When critical flight−plan data changes or is requested by the controller, the FDPS starts the conflict probe function at predetermined intervals.
390
388
389
387
326
A
5
0
8
9
B
6
1
2
3
4
9 6 7 2
R A 4
P r o c e s s o r
# 2 3880
3880
3480
Support Element
MAU
9 6 7 2
R A 4
P r o c e s s o r
# 1
Hardware Management
Console
RSF Modem
3274 TCU
4245 HSP
S1RPAM
ISD
Tape
DASD
Lexmark
Printer
7
4245 HSP
ISD
3274 TCU
3480
3480
3480
3380
3380
Tape
DASD
A
5
0
9
B
6
1
2
3
4
8
7
Support Element
MAU
RSF Modem
Hardware Management
Console
Lexmark
Printer
340
341
3151 or 3153 4226 or 4232
3151 or 3153 4226 or 4232
313
314
329
330
329
330
333
334
335
336
356
357
358
359
360
361
362
363
327
328
354
355
350
351
352
353
323
324
325
316 317
315
318
320
321
319
322
347
348
349
345
346
343
344
342
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
T
B
BD
95
90
96
A2
E8
A1
91
94
A0
BC
92
D8
80
BD
95
90
96
A2
E8
A1
91
94
A0
BC
92
ESCON CTC
ESCON CTC
ESCON CTC
CHPID
CHANNEL
CHANNEL
CHPID
S1RPAM
DA
E S C O N
E S C O N
82
DB
83
80
D8
DA
82
DB
83
EMC 5630 DASD #1
EMC 5630 DASD #2
NOTE:CThree digit numbers indicate cable identification numbers
FIGURE 2 −2.ODAPS IBM 9672 CHANNEL INTERCONNECTS
3180-1 SEIOT-A
3180-1 KCNF-A
3180-1 SEIOT-A
3268 or 6400 KPR-1
3180-1 KCNF
A B
3268 or 6400-050 KPR2
A B
3180-1 SEIOT
B
3180-1 SEIOT-B
3180-1 KCNF-B
3268 or 6400 KPR-1
6400-015 HSP
A B
3268 or 6400-050 USER PRINTER
A B
3180-1 TERMINALS
A B
3180-1 SUPIOT
A B
3268 or 6400-050 KPR3
A B
7 B T
9672-RA4 (1)
328
327
3274 (1)
3274 (2)
3180-1 SUPIOT
7
9672-RA4 (2)
354
355
OPERATOR STATION
MCC AREA
SUPERVISOR STATION
USER STATIONS
A
IS-482G VM Terminal
IS-482G VM Terminal
B T
EQUIPMENT ROOM
NOTE:CThree digit numbers indicate cable identification numbers
FIGURE 2 −3.ODAPS IBM 3274 TERMINAL INTERCONNECTS
(2)6Direct Access Storage Device (DASD).
FIGURE 2 −3.ODAPS IBM 3274 TERMINAL INTERCONNECTS
(a)63880/3380 Subsystem. The DASD sub− system consists of IBM 3380 Models AD4, AE4, BD4, and BE4 DASDs and IBM 3880 Model 3 Storage Con− trol Units (SCU). The IBM 3380 is a large capacity, high−performance disk storage unit. The IBM 3380 Models AE4 and BE4 have a capacity of 5 GB, an average seek time of 17 milliseconds (ms), and a data transfer rate of 3 MB per second. The IBM 3380 Mod− els AD4 and BD4 have a capacity of 2.5 GB, an average seek time of 15 ms, and a data transfer rate of 3 MB per second. This subsystem satisfies the ODAPS disk storage requirements.
(b)6Symmetrix 5630 DASD Subsystem.
16The EMC Symmetrix 5630 DASD sub− system is the replacement for the IBM 3880 Disk Stor− age Director/3380 DASD elements. It is comprised of two identical units: Disk Subsystem 1 and Disk Subsystem 2, each containing the functions of the Director and DASD in one cabinet.
26The 5630 DASD configurations for ARTCCs contain two ESCON channel cards to con− nect to the ODAPS 9672 central processors with data transfer rates up to 17 MB per second; two Fibre chan− nel cards to connect to the DASD Monitor and Control (M&C) subsystem, which provides equipment and software for monitoring the DASD as well as other devices within its own subsystem; four disk directors on two board assemblies control the eight 36 GB disk device arrays. The physical disk device arrays are partitioned by defining logical 3380 Count Key Data (CKD) type disk volumes, or Fixed−Block Architecture (FBA) open systems format volumes. Some open sys− tems FBA volumes will be defined on each Symmetrix, but such volumes are reserved for future use. Two 512 MB Cache memory boards provide the hardware necessary to interface between the Host processor, disk directors, and disk arrays. This feature of the Symmetrix is known as Integrated Cached Disk Array (ICDA) technology, and allows for faster data transfer. Each Symmetrix implements Redundant Array of In− dependent Disks (RAID) technology. As a result, all data stored in Symmetrix will be mirrored using RAID −1 (mirroring).
36Each Symmetrix 5630 presents the ap− pearance of an IBM 3990 Storage Director and multi− ple 3380 −D/E−disk devices to the channel/Host processor. It provides the necessary low−level trans− formation of the requested functions from Channel Command Word (CCW) program directives to the ac−
tual directives known by Symmetrix. The emulation process within each Symmetrix insulates the channel/ Host processor from the actual physical implementa− tion semantics of the DASD.
46The 5630 battery subsystem maintains power for approximately 3 minutes to the entire sub− system if ac power fails. The main power subsystem operates on 208 Volt (V) ac single−phase input power at frequencies of 50 or 60 Hertz (Hz). Two power supplies provide +5 V, +12 V, and +24 V power to the Symmetrix components.
56The Service Processor is a laptop com− puter in each Symmetrix 5630, which provides the ability to manage various aspects, including the down− loading of configuration data to the directors and pro− viding diagnostic and maintenance utilities for the Symmetrix. The Service Processor will primarily be used by EMC customer engineers. It is located on the inside of the front door of each Symmetrix 5630. The Service Processor interfaces with Symmetrix components via an RS −232 interface and/or an Ethernet Hub and has an attached 33.6 Kilobytes per second (Kbps) external modem for communicating with the EMC Customer Support Center when Sym− metrix detects an error condition. The external mo− dem is generally placed in the space on the lower left inside the front of the cabinet and uses a separate 110 Vac single−phase power feed. This modem will be used with a dial out only configuration, and only when required by EMC to render a repair to the 5630.
(c)65630 DASD M&C. The 5630 DASD M&C provides an external interface to monitor and control the storage device’s functionality without in− terfering with the operational mission of the storage device and/or degrading its performance. The M&C is responsible for acquiring storage device configura− tion parameters, monitoring all state and status changes, and reporting all monitored data. The M&C also provides monitor and control for the M&C server workstations and other M&C devices on the network. For a more detailed description of the M&C, refer to paragraph 204.
(3)6Magnetic Tape Subsystem (MTS). The MTS consists of IBM 3480 Model A22 Magnetic Tape Control Units (MTCU) and IBM 3480 Model B22 Magnetic Tape Units (MTU). This subsystem satisfies the online data storage requirements of ODAPS.
(4)6S1RPAM Subsystem. The S1RPAM sub− system consists of two sets of the following equipment: IBM 7026 Model H50 processor, Gateway 5100 or 5150 notebook system console, Bay Networks Ether−
net Hub, eight powered B&B Electronics modem split− ters, modem splitter power distribution panel, Cyberex Power Distribution Unit (PDU), an Auto− matic Switching System Series 5000 A/B Switch and a Lexmark matrix printer. All components except the printer are housed in a Crenlo rack. In addition, the S1RPAM subsystem also contains NEC 2400M mo− dem (Oakland), General DataComm 201C modem (New York), ME801A/ME801B Sync Short Haul mo− dems, Bell 1600 modem (Oakland), Codex 6250 multi− plexor, and ME800A Asynch−Short Haul modems. See Figure 2 −4, S1RPAM Configuration Diagram. This subsystem interfaces the FDPS to a variety of commu− nication lines from other facilities. These lines sup− port the exchange of flight data and related support information. The S1RPAM subsystem also interfaces the FDPS to local devices.
(5)6TP Subsystem. The TP subsystem con− sists of IBM 7018 Model 770 or Model 771 RISC/6000 processor, IBM 4226 Model 302 printer, IBM 6091 Model 19−inch color display, Certainty ARRAY/6000 disk, IBM 3151 ASCII display, IBM 7208 tape drive, Cyberex Model 163A445 −1 208 V power distribution unit, Cyberex Model 600/6FA1 110 V power distribu− tion unit, Black Box powered Multi−station Access Unit (MAU) with Ring In/Ring Out (RIRO) fiber in− terface, Black Box Model SK −SW901A RS232 fall− back switches, Loral Initial Sector Suite Rack, Black Box 3−port modem splitter, a RM060 converter rack (expansion chassis) which holds a power supply, a Black Box RS232/RS485 converter to interface with the CCK, an TFSP, an IBM QWERTY 101 keyboard, Measurement Systems Trackball or IBM mouse, and 19−inch (width) Rack. An example of the ARTCC TP in Oakland is shown in Figure 2 −5, Oakland ODAPS Cable Configuration Diagram (TP), and New York ARTCC is shown in Figure 2 −6, New York ODAPS Cable Configuration Diagram (TP). This subsystem provides a visual display of update, general informa− tion, weather, and flight strip messages. It also pro− vides an input interface for controller entered messages.
(6)6ISD Subsystem. The ISD subsystem con− sist of IBM 7018 Model 770 or Model 771 Reduced Instruction Set Computer (RISC)/6000 processors (site dependent), IBM 4226 or 4232 line printer, SONY 20x20 color display, a 19−inch Philips auxiliary dis−
play, ARRAY/6000 disk, IBM 3151 or 3153 American Standard Code for Information Interchange (ASCII) display, IBM 7208 tape drive, Cyberex Model 163A445 −1 208 V PDU, Cyberex Model 600/6FA1 110 V PDU, a Display Controller for X −Windows (DCX), a transceiver, a Black Box powered MAU with RIRO fiber interface, Server Rack, a Common Console Keyboard (CCK), a Space Saver Keyboard, Measure− ment Systems Trackball, and a Common Console Frame. See Figure 2 −7, ISD System Architecture Dia− gram. The subsystem interfaces the Flight Data Proc− essing Subsystem (FDPS) to ISD Servers, which are connected to ISD Oceanic Consoles (OC).
(7)6ODAPS Software Subsystem. The ODAPS software subsystem consists of the following software modules: the NAS monitor, the FDPS pro− gram, the conflict probe subsystem program, the S1RPAM program, and the ISD program.
(8)6AIDCS Subsystem. The AIDCS consists of one Hewlett Packard (HP) NetServer LC II system computer, one HP D4950B ABA 101−key enhanced keyboard, one HP mouse, one ViewSonic E655 15−inch Super Video Graphics Adapter (SVGA) moni− tor, one Epson LQ−570 Plus printer, two Motorola Codex 3600 modems, two Black Box ME800A asyn− chronous short haul modems, one Eicon X.25 inter− face adapter, and one American Power Conversion (APC) Smart Universal Power Supply (UPS) 600 or 1000. The HP NetServer LC II system computer con− sists of an Intel Pentium II 266 −MHz processor, 32 −MB of Random Access Memory (RAM), a 2 −GB removable hard drive, a 1.44 −MB floppy disk drive, a 24X CD −ROM, two serial communication port adapters, a parallel printer port, and an Eicon High Speed Interface (HSI/PC) 1 −MB X.25 interface card. The ODAPS AIDCS Cable ConfigurationDia− gramis shown in figure 2 −8. This subsystem inter− faces to the S1RPAM via a pair of Black Box ME800A asynchronous short haul modems and to NADIN II via a pair of Codex modems. These interfaces are used by this subsystem to exchange flight information mes− sages with ODAPS via the S1RPAM and with non−US FIRs via NADIN. This subsystem provides a visual display of flight information, the status of the connec− tions to ODAPS and the FIRs, and error information. It also provides an interface for controller input.
6110.7E 9/17/03
Page 12 Chap 2 Par 202
S1RPAM Rack A
A/B Gang Switch
ENE
T
SCS
Tailgate Assembly
Ethernet
Hub
Printer
0 15
S1RPAM Rack B
A/B Gang Switch
11
T
I
H50 Processor
Tailgate Assembly
Ethernet
Hub
Printer
PCCA Cards
COMM
Cards
PCCA
Cards
COMM Cards
To IBM 9672
To External interfaces (including CTS)
S1RPAM System
Console
To External
Splitter
Modem
Panel
To IBM 9672 To IBM 9672 To IBM 9672
S1RPAM System
Console
H50 Processor
PDU PDU S1RPAM SC
PDU PDU S1RPAM SC
(unfiltered
output)
AB Switch
H50 Relay Box
Eth. Hub (Filtered Outputs)
S1RPAM SC
(unfiltered
output)
Modem Eliminator
Modem Eliminator
I
ENE SCS
Splitter
Modem
Panel
14 13 12 11 10 9 8 7 6 5 4 3 2 1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
ENE SCS
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
B U S
I N
B U S
I N
T A G
I N
T A G
I N
B U S
O U T
B U S
O U T
T A G
O U T
T A G
O U T
B U S
I N
T A G
I N
B U S
O U T
T A G
O U T
B U S
I N
T A G
I N
B U S
O U T
T A G
O U T
1 P
2 P
3 P
4 P
5 P
6 P
7 P
8 P
9 P
1 P
2 P
3 P
4 P
5 P
6 P
7 P
8 P
9 P
P 1 S 1 S 3 6 2
P 1 S 1 S 3 6 2
8 8
8 8
Power Distribution Panel A Power Distribution Panel B Primary Power
Secondary Power
Primary Power
Secondary Power
Power Interconnection
18 Gauge Plenum Rated Wire
18 Gauge Plenum Rated Wire
interfaces (including CTS)
I
FIGURE 2 −4.ODAPS S1RPAM CONFIGURATION DIAGRAM
TP Server
1
TP Server
2
TP SYSTEM CONSOLE 2
RO RI P1 P2 P6
RO
P1 P2 P3
RI
(TPM0001)
MAU PA Mounted In TP Server 1
MAU SD Mounted In TP Server 2
(TPM0003)
(TPM0004) (TPM0006)
HOST ODAPS Computer Room
(TPM0004) (TPM0006)
P1 P2 P3
MAU SG Mounted In M1 Console #727
MAU SH Mounted In M1 Console #519 (TPM0005)
RI RO P2 P4 P6
MAU PD Mounted In M1 Console #727
P1 P6
MAU PE Mounted In M1 Console #519
(TPM0002)
RI RO RI RO
(TP0029)
(TP0026)
(TPM0019)
(TPM0008)
(TPM0012)
(TPM0018)
1) PRIMARY CABLE 2) - - - - - - - SECONDARY CABLE 3) FIBER OPTIC, TYPE 1, PLENUM CABLES CONNECTED TO MAU RO AND RI 4) COPPER, TYPE 1, PLENUM RATED CABLES CONNECTED TO MAU PORTS 5) (TPMXXXX) IS THE CABLE NUMBER CONFIGURED
RI RO RI RO
NOTES:
MEZZANINE
(TPM0020)
(TPM0021)
(TPM0022)
(TPM0023)
(TPM0024)
(TPM0025)
P4 P5 P6 P7
(TP0027)
(TP0028)
(TP0030)
P1 P2 P3 P5 P6
(TPM0007)
(TPM0009)
(TPM0010)
(TPM0011)
(TPM0013)
(TPM0015)
(TPM0014)
(TPM0016)
(TPM0017)
OC7 M1 #733
OC2 M1 #725 OC1 M1 #723
AO1 M1 #715
OC3 M1 #623
OC2 M1 #725 OC1 M1 #723
System Console 1
OC4 M1 #621
OC9 M1 #523
OC5 M1 #521 AO5 M1 #513
OC6 M1 #507
AO4 M1 #613
RTS2-1
SOPA and SMMC
P1 P3 P5 P7
RI RO
RTS2-0
To S1RPAM/RCU-1
To S1RPAM/RCU-2
P2 P3 P5
FIGURE 2 −5.OAKLAND ODAPS CABLE CONFIGURATION DIAGRAM (TP)
Server
1 Server
2
TP SYSTEM CONSOLE 2
(TP0004)
TP SYSTEM CONSOLE 2
(TP0015)
(TP0006)
(TP0016)
RO RI P1 P2 P3
RO
P1 P2 P3
RI
(TP0001)
MAU PA Mounted In Server 1
MAU SD Mounted In Server 2
(TP0003)
(TP0012) (TP0014)
HOST ODAPS Computer Room
SOPA and SMMC
P1 P2 P3 P1 P2
MAU SE Mounted In Workstation M1, 505
MAU SF Mounted In Workstation M1, 605 (TP0013)
RI RO P1 P2 P3
RI RO P1 P2 P3
MAU PB Mounted In Workstation M1, 504
RI RO P1 P2
MAU PC Mounted In Workstation M1, 612
(TP0002)
RI RO RI RO
(TP0020)
(TP0019)
(TP0018)
(TP0021)
(TP0017)
(TP0022)
(TP0006)
(TP0010)
(TP0007)
(TP0006)
(TP0009)
1) PRIMARY CABLE 2) - - - - - - - SECONDARY CABLE 3) FIBER OPTIC, TYPE 1, PLENUM CABLES CONNECTED TO MAU RO AND RI 4) COPPER, TYPE 1, PLENUM RATED CABLES CONNECTED TO MAU PORTS 5) (TPXXXX) IS THE CABLE NUMBER CONFIGURED
RI RO RI RO
NOTES:
(TP0011)
M-1 504,
AMIS
M-1 505 SECT 70
M-1 605, SECT 71
M-1 612, SECT 72 System Console 1
SMMC
RTS2-1
RTS2-0
To S1RPAM/RCU-1
To S1RPAM/RCU-2
FIGURE 2 −6.NEW YORK ODAPS CABLE CONFIGURATION DIAGRAM (TP)
6110.7E 9/17/03
Page 15 Chap 2 Par 202
PHILIPS
19” DISPLAY
SONY 20 X 20
19” DISPLAY
DISPLAY
MAU
MAU
MAU
MAU
MAU
FIBER OPTIC TOKEN RINGS
DCX 2000
CPU
LINE PTR
SC
TRACKBALL
PHILIPS
19” DISPLAY
SONY 20 X 20
DISPLAY
DCX 2000
CPU
ISD OCEANIC CONSOLE (OC) TRACKBALL
MAU
PHILIPS
19” DISPLAY
SONY 20 X 20
DISPLAY DCX 2000
CPU
ISD OC TRACKBALL
SONY 20 X 20
DISPLAY
DCX 2000
ISD OC TRACKBALL
CPU
ISD OC TRACKBALL
PHILIPS
19” DISPLAY
SONY 20 X 20
DISPLAY DCX 2000
SYSTEM CONSOLE (SC) TRACKBALL
CPU
LINE PTR
LINE PTR
IBM EAGLE SERVER 1
Cambex ARRAY Subsystem IBM EAGLE SERVER 2 LINE PTR
IBM 9672 (SECONDARY) IBM 9672 (PRIMARY)
ODAPS
ISD
OPERATIONAL
REDUNDANT
ISD SYSTEM ARCHITECTURE
ISD SYSTEM ARCHITECTURE
PHILIPS
19” DISPLAY
FIGURE 2 −7.ISD SYSTEM ARCHITECTURE DIAGRAM
To S1RPAM
ME800A Asynchronous
Short Haul Modem 1
PG
To FAC Power
To FAC UPS
ODAPS Computer Room
Area F (New York) or MEZZANINE (Oakland)
ViewSonic 15-inch Monitor
HP 101-Key Keyboard
HP Mouse
Epson LQ-570 Plus Printer
FIGURE 2 −7.ISD SYSTEM ARCHITECTURE DIAGRAM
PH
ME800A Asynchronous
Short Haul Modem 2
HP NetServer LC II
Eicon X.25 Interface
Adapter Card
To FAC UPS
To FAC UPS
PK
Codex 3600 Modem 1
PL
NADIN II Node (GFE)
Codex 3600 Modem 2
PM
ÊÊ
ÊÊ
ÊÊ
ÈÈ
ÈÈ
To FAC Power
DMN Area
DMN Area
COMM Room (New York) or RDP Area (Oakland)
1) 25 Wire Shielded 2) DB9 to DB25 Cable 3) 2 Pair Twisted Wire 4) 8 Wire Low Loss 5) Cable number is specified by the letter P followed by another letter The cable numbers match those in the AIDCS OMTIM, CDRL No. A053-002D
ËËËË ÈÈÈÈ
ËËËË ÈÈÈÈ
ÈÈÈÈ
Area F (New York) or MEZZANINE (Oakland)
FIGURE 2 −8.ODAPS AIDCS CABLE CONFIGURATION DIAGRAM
(9)6ODL Subsystem. The ODL subsystem consists of IBM 7018 Model 770 or Model 771 RISC/6000 processor, IBM 4226 Model 302 printer, IBM 6091 Model 19−inch color display, Certainty ARRAY/6000 disk, IBM 3151 ASCII display, IBM 7208 tape drive, Cyberex Model 163A445 −1 208 V power distribution unit, Cyberex Model 600/6FA1 110 V power distribution unit, Black Box powered MAU with RIRO fiber interface, Black Box Model SK − SW901A RS232 fallback switches, Loral Initial Sector Suite Rack, RS422 interface for a TFSP and CCK, an IBM QWERTY 101 keyboard, Measurement Sys− tems Trackball or IBM mouse, and 19−inch (width) rack. An example of the ARTCC ODL in Oakland is shown in Figure 2 −9, Oakland ODAPS Cable Con− figuration Diagram (ODL), and New York ARTCC is shown in Figure 2 −10, New York ODAPS Cable Configuration (ODL). This subsystem provides a visu− al display of update, general information, weather, and flight strip messages. It also provides an input interface for controller entered messages.
FIGURE 2 −8.ODAPS AIDCS CABLE CONFIGURATION DIAGRAM
b. A full set of this equipment is located in each of the Ronkonkoma, New York and Oakland, Califor− nia ARTCCs.
203.SYSTEM THEORY OF OPERATION.
a. FDPS Functions. The FDPS has the follow− ing functions:
(1)6System supervision,
(2)6Flight data message processing,
(3)6Route conversion,
(4)6Posting determination,
(5)6Upper winds message processing,
(6)6Health/status monitoring,
(7)6Flight data and conflict probe display order formatting,
(8)6Level flight and altitude transition conflict detection,
(9)6Message acceptance, and
(10)6Response processing.
b. IBM 3380 Disk Drive. The IBM 3380 disk drive in the DASD Subsystem provides the logical capabilities to operate and control the DASDs. The
IBM 3880 SCU contains two storage directors that operate independently and provide basic functions for disk storage control.
c. IBM 3480 Model A22. The IBM 3480 Model A22 is a microprocessor−driven control unit that con− trols the IBM 3480 Model B22 MTUs.
d. S1RPAM Subsystem Functions. The S1RPAM subsystem has the following functions:
(1)6External message receipt,
(2)6External message transmission,
(3)6Protocol conversion,
(4)6Link−level data checking,
(5)6Message size checking, and
(6)6S1RPAM subsystem processor health/ status reporting to FDPS.
e. ISD Subsystem Functions. The ISD subsys− tem performs the following functions:
(1)6Provides health/status reporting to FDPS;
(a)6Displays aircraft traffic situations,
(b)6Routes,
(c)6Map data,
(d)6Aircraft information lists,
(e)6Messages, and
(f)6Status indicators.
(2)6Processes input from the controller via key− board, trackball, and function keys.
f. TP Subsystem Functions. The TP subsystem performs the following functions:
(1)6Display update,
(2)6General information and weather mes− sages,
(3)6Prints flight strip information,
(4)6Processes controller entered messages, and
(5)6Stores received messages for historical re− view.
ÏÏÏ
Ï
Ï
Ï
Ï
ÏÏ
ÏÏ
Ï
Server
2
P1
P2
SYSTEM CONSOLE 2
SYSTEM CONSOLE 2
P2
Ï
P3
Mounted in Server 1
P3
P1
P1
P2 P1
HOST/ODAPS
Computer Room
Control Room
P6 P5 P1 P2 P3 P5
P2 P3 P5 P6 P1 P2 P3 P5
P3
RO RI MAU LAN A
RO RI
RI
RI RO RI RO
RO RI RO
MAU LAN B
Mounted in Server 2
MAU LAN B
Common Console #727
MAU LAN B
Common Console #518
MAU LAN A
MAU LAN A
Common Console #727
MAU LAN A
Common Console #518
SYSTEM CONSOLE 1
SECT 7 RACK #750
SECT 2 RACK #725
SECT 3 RACK #823
SECT 1 RACK #723
SECT 5 RACK #521
SECT 9 RACK #523
SECT A09 RACK #513
SECT 6 RACK #507
RTS2-0
RTS2-1
Server
1
To S1RPAM/RCU-3 To S1RPAM/RCU-4
To NADIN
ODL FALLBACK SWITCHES
ODL FALLBACK SWITCHES
NOTES
1) PRIMARY CABLE 2) SECONDARY CABLE 3) FIBER OPTIC TYPE 1 PLENUM RATED CABLES CONNECTED TO MAU RO AND RI 4) COPPER TYPE 1 PLENUM RATED CABLES CONNECTED TO MAU PORTS
RTS2-2
P6
P6
SECT A04 RACK #613
P7
P7
SECT 4 RACK #821
FIGURE 2 −9.OAKLAND ODAPS CABLE CONFIGURATION DIAGRAM (ODL)
FIGURE 2 −9.OAKLAND ODAPS CABLE CONFIGURATION DIAGRAM (ODL)
Ï
Ï
ÏÏ
ÏÏ
Ï
Ï
Ï
Ï
Ï
Ï
Ï
Server
2
Ï Ï
Ï
P1
Ï
P2
SYSTEM CONSOLE 2
P2
Ï
ÏÏ
P3
Mounted in Server 1
P3
P1
Ï Ï
P1
P2 P1
Ï
Ï
HOST/ODAPS Computer Room
New Control Room/AMCC
P5 P4 P4 P1 P2 P3
P2 P3 P4 P5 P1 P2 P3 P4
P3
RO RI MAU LAN A
RO RI
RI
RI RO RI RO
RO RI RO
MAU LAN B
Mounted in Server 2
MAU LAN B
MAU LAN B Common Console #237
MAU LAN B Common Console #102
MAU LAN A
Common Console #237
MAU LAN A
Common Console #102
SYSTEM CONSOLE 1
SECT 72
RACK #137
SECT 87
RACK #233
SECT 84
RACK #238
SECT 88
RACK #226
SECT 70
RACK #108
SECT 89
RACK #212
SECT 71
RACK #111
SECT 90
RACK #204
SYSTEM CONSOLE 1
RTS2-0
RTS2-1
Server
1
To S1RPAM/RCU3 To S1RPAM/RCU4
To NADIN
ODL FALLBACK SWITCHES
NOTES
1) PRIMARY CABLE
2) SECONDARY CABLE
3) FIBER OPTIC TYPE 1 PLENUM RATED CABLES CONNECTED TO MAU RO AND RI
4) COPPER TYPE 1 PLENUM RATED CABLES CONNECTED TO MAU PORTS
RTS2-2
FIGURE 2 −10.NEW YORK ODAPS CABLE CONFIGURATION DIAGRAM (ODL)
FIGURE 2 −10.NEW YORK ODAPS CABLE CONFIGURATION DIAGRAM (ODL)
g. ODAPS Software Subsystem Functions. The ODAPS software subsystem performs the follow− ing functions:
(1)6Receives plan messages,
(2)6Departure messages,
(3)6Amendment messages,
(4)6Creates a data base for all aircraft that are operating within a oceanic sector, and
(5)6Gives the controller early notification of potential conflicts between aircraft in oceanic air− space.
h. AIDCS Subsystem Functions. The AIDCS Subsystem performs the following functions:
(1)6External message receipt,
(2)6External message transmission,
(3)6Message field validation,
(4)6Message format conversion,
(5)6Message delivery assurance,
(6)6Response message processing,
(7)6Flight data base creation and maintenance,
(8)6External interface status monitoring,
(9)6Controller input processing,
(10)6Message logging,
(11)6Message printing, and
(12)6Display updating.
i. ODL Subsystem Functions. The ODL Sub− system performs the following functions:
(1)6Existing TP functionality,
(2)6CPDLC message processing (air/ground communications processing),
(3)6Outgoing data communications with ROs for message processing with HF−equipped aircraft,
(4)6NADIN II interface for CPDLC Position Report transmittal to the ODAPS,
(5)6Message composition automation at opera− tional positions,
(6)6Message archival for historical and legal purposes,
(7)6Multi−sector processing support,
(8)6Controller−to−Controller communications (E −Mail capability),
(9)6Data Reduction and Analysis (DR&A) func− tionality,
(10)6Controller−to−RO messages, and
(11)6CPDLC message processing redundancy.
204.SYMMETRIX 5630 DASD M&C SUB− SYSTEM.
a. The Symmetrix 5630 DASD M&C subsystem provides an external interface to monitor and control the DASD’s functionality without interference to NAS. The M&C acquires DASD configuration param− eters, monitors all state and status changes, and re− ports all monitored data. The M&C also provides monitor and control of the M&C server workstations and other M&C devices on the network.
The Symmetrix 5630 M&C subsystem, as shown in figure 2 −11, consists of the following major compo− nents:
(1)6M&C Server N Quantity 2
(2)6Ethernet Switch N Quantity 2
(3)6Transceiver N Quantity 8, 4 at M&C user positions (2 wired but not used); 2 at the printers; 2 at the M&C control positions
(4)6M&C User Position N Quantity 2
(5)6M&C Printer N Quantity 2
ÌÌÌ
ÌÌÌ
ÌÌÌ
Remote Support
Modem
ÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑ
Primary Processor
(NAS)
ÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓ
Support Processor
(VM/ESA)
Emulated
3380
Open Systems
Device Manager S/W
ESCON
Fibre Channel
Open Systems
Device Manager S/W
M&C Server 1 M&C Server 2
Network Manager
& M&C Applications
Network Manager
& M&C Applications
Time Server Time Server
CTS
Display, Keyboard, Integrated Pointing Dev
Terminal Server Terminal Server
Computer Specialist M&C User Positions
Dual ESCON
Paths
Each
to Each
X C R
Disk Subsystem 1 Disk Subsystem 2
ÑÑÑ
ÑÑÑ
= Existing GFE
Device Manager S/W Device Manager S/W
Service Processor Service Processor
High Speed Interconnect
Trunks
Thin Client
XCR
Thin Client
XCR
Printer
XCR
AMCC M&C User Positions = Equipment shipped, wired
for but not installed in Phase 3
Remote Support
Modem Emulated
3380
ESCON
Fibre Channel
X C R
Thin Client
XCR
Thin Client
XCR
Printer
XCR
Display, Keyboard, Integrated Pointing Dev
Ethernet
Switch
Ethernet
Switch
FIGURE 2 −11.SYMMETRIX DASD MONITOR AND CONTROL
b. Two redundant M&C servers, which are con− nected via direct fibre channels to the various compo− nents of the 5630 DASD subsystem, continuously display and report the status of the subsystem. Each server is rack−mounted and includes a local keyboard with integrated pointing device and LCD display. The workstations are used to command and control the M&C servers. The M&C servers are IBM RS/6000 Model H80 processors running the AIX Operating System. The M&C servers run a copy of the Tivoli NetView network manager application. The servers also run the EMC Control Center application, which is used to monitor, configure, control, and tune the EMC Symmetrix. The Symmetrix is connected to the M&C server via Fibre Channel. The Control Center is accessible from both the M&C user and control positions. The Control Center forwards Symmetrix status data to the M&C application programs, which allows Symmetrix events and system information to be displayed on the M&C views. The M&C servers also run Coded Time Source (CTS) software, and Network Computing Device (NCD) Thin Client server software. The M&C servers receives date and time synchronization information from the Central Computer Complex Host (CCCH) CTS interface that is connected to a serial port on each M&C server. After being read, the synchronization information is used to update the date and time of each M&C server.
FIGURE 2 −11.SYMMETRIX DASD MONITOR AND CONTROL
c. Two fast Ethernet switches and eight transceiv− ers provide the network infrastructure for the M&C and are used as the interface media between the two M&C servers and the M&C User Positions. The trans− ceivers provide paths to the redundant switches for fault tolerance. The Transceiver acts as a simple A/B switch to arbitrate connectivity of the M&C to one of the two Ethernet switches at a time (depending on which of the two is designated primary at the time).The Ethernet switches are Cisco Catalyst 2900 Series XL Enterprise Edition.
d. Two M&C user positions will be installed at the ARTCC Maintenance Control Center (AMCC) and Computer Operation areas. The user positions consist of a monitor, keyboard, and pointing device. They attach to the Ethernet network via transceivers which provide paths to the redundant switches. The M&C user positions provide a remote user interface to the
M&C servers. They also offer centralized configura− tion management and administration to applications and resources on the M&C server. The M&C user posi− tions are NCD NC900 series Thin Client workstation− s. Four Thin Client workstation position are wired but only two are populated. Four Thin Client units are shipped and two installed, the other two are not installed at the ARTCC. They are used to provide oper− ator interfaces to the M&C Server application. The Thin Clients can boot from either of the M&C servers. They support X11 for access to X −Windows applica− tions. The X −Window system is a graphics system used on UNIX, MS −Windows systems, etc., and pro− vides an inherently client/server oriented base for dis− playing windowed graphics. From the Thin Clients, users can run the Tivoli NetView. Tivoli NetView is a network manager application that displays network topologies, correlates and manages events and Simple Network Management Protocol (SNMP) traps, moni− tors network health, and gathers performance data.
Tivoli NetView provides the scalability and flexibility to manage mission−critical environments. Tivoli Net− View allows network administrators to centralize the management of network hardware devices and ser− vices. The majority of the M&C functions are available at the M&C user positions, each of which has the same set of capabilities. Authority levels are used to deter− mine the capabilities permitted for each individual user. Authority levels are login identifiers that allow users to access a defined set of capabilities, based on job responsibilities. The authority levels are defined as Operations Manager (for NOMs), HOST Opera− tions (for Computer Operators (CO)), Maintenance (for ATSSs), and Administrator (for System Special− ists (SS)). When a user logs on with an authorized User ID and password, only the authorized monitor and control capabilities will be available for active use.
e. Two printers will be installed at the AMCC and Computer Operation areas. The printers are pro− vided to print event logs and configuration reports. The M&C printers are Lexmark Optra Model 410 printers that provide print access to all M&C applica− tions on the server. The printers are attached via Ethernet.
205. −299.RESERVED.
CHAPTER 3. STANDARD AND TOLERANCES
CHAPTER 3. STANDARD AND TOLERANCES
300.GENERAL.
a. This chapter prescribes the standards and tol− erances for the ODAPS automation, as described in Order 6000.15. All key performance parameters and/
or key inspection elements are identified by an arrow () placed to the left of the applicable item.
b. The equipment is grouped by subsystem, rather than by facility, since all subsystems are duplicated at each facility.
STANDARDS AND TOLERANCES
STANDARDS AND TOLERANCES
Parameter Reference Standard
Tolerance/Limit Parameter Reference Paragraph Standard
Initial Operating
301.ODAPS.
a. Flight Data Processing . . .
and Display.
506 Satisfactory overall flight data proces− sing and system display as verified using the OnLine Certification (OLC) programs or manu− al entry checking techniques
Same as standard
Same as initial
b. KVDT Terminal …
Message Input and Display.
506 Satisfactory mes− sage input and dis− play as verified us− ing the OLC pro− grams or General Information (GI) and Test Device (TD) manual mes− sages
Same as standard
Same as initial
c. TP Workstation …
Message Input and Display.
506 Satisfactory mes− sage input, scrol− ling, and display as verified using the OLC programs or TD manual mes− sages
Same as standard
Same as initial
d. TFSP Flight Strip …
Printing.
506 Satisfactory print− out of flight strips with correct device response registra− tion and print quality as verified using the OLC pro− grams or TD manual message
Same as standard
Same as initial
e. Interfacility Data …
Transfer.
506 Satisfactory trans− fer of data as veri− fied using the OLC programs or Test Message (TR) manual message
Same as standard
Same as initial
f. Switchover Operation . . . . 508 Successful switch− overs as verified using manual re− quests
Same as standard
Same as initial
STANDARDS AND TOLERANCES (Continued)
Tolerance/Limit Standard Reference Paragraph Parameter
Operating Initial Standard Reference Paragraph Parameter
302.FDPS.
a. IBM 9672 Model RA4
Processor.
(1) 9672 Frame … IBM S/390 Support Element Operations Guide, GC38 −3108 −03. IBM S/390 Installation Manual, SY24 −6156 −04. IBM S/390 Service Guide, SY24 −6158 −04
Successful comple− tion of Power On Self Test (POST) and the Checkout Tests
Same as standard
Same as initial
(2) 9672 SE … IBM S/390 Support Element Operations Guide, GC38 −3108 −03. IBM S/390 Installation Manual, SY24 −6156 −04
Successful comple− tion of POST
Same as standard
Same as initial
(3) HMC … IBM S/390 Support Element Operations Guide, GC38 −3108 −03. IBM S/390 Installation Manual, SY24 −6156 −04
Successful comple− tion of POST
Same as standard
Same as initial
(4) Multi−System …
Channel Communications Unit (MCCU).
IBM Channel−to− Channel Adapter or 3088 MCCU Exerciser On−Line Test User Guide, D99 −3150A −05
Error free comple− tion
Same as standard
Same as initial
b. IBM 3268 Model 2C Con−
sole Printer.
(1) Operation … IBM 3268 Printer Models 1, 2, and 2c Maintenance Informa− tion, SY27 −0201 −4, sections 716, 725, 743, 746, and 749
Error free comple− tion and no excess accumulation of er− rors
Same as standard
Same as initial
STANDARDS AND TOLERANCES (Continued)
Tolerance/Limit Standard Reference Paragraph Parameter
Operating Initial Standard Reference Paragraph Parameter
(2) Print Quality … IBM 3268 Printer Models 1, 2, and 2c Maintenance Informa− tion, SY27 −0201 −4, sections 731, 736, and 737
Satisfactory print Same as standard
Same as initial
c. IBM 4245 Model 12 Line
Printer.
Operation … IBM 4245 Printer Models 12 and 20 Maintenance Informa− tion Manual, Volume 1, pages DIA −040, DIA −050, and DIA −200
Error free completion
Same as standard
Same as initial
d. IBM 3274 Model 41D Ter−
minal Control Unit.
OLTs … IBM Maintenance Diagnostic Program Local 3274 Model 1B/1D Display System Online Tests, D99 −3274A −01, pages 1 through 19
Error free completion
Same as standard
Same as initial
303.DASD SUBSYSTEM.
a. IBM 3380 Models AD4,
AE4, BD4 and BE4 DASDs.
OLTs … IBM 3380 Online Test (OLT) User’s Guide, D99 −3380A −02, pages 1 through 4, 7 through 13, 18, 19, 21, and 22, and 32 through 44
Error free completion
Same as standard
Same as initial
b. IBM 3880 Model 3 SCU.
OLTs … IBM Maintenance Diagnostic Program 3880 Storage Director Online Test, DCL −3880A −02 (D99 −3880A −01), pages 1 through 8
Error free completion
Same as standard
Same as initial
STANDARDS AND TOLERANCES (Continued)
Tolerance/Limit Standard Reference Paragraph Parameter
Operating Initial Standard Reference Paragraph Parameter
c. Symmetrix 5630 DASD
Subsystem.
(1) Entire unit or any …
component except disk device or power supply.
CDRL D038, System Problem Determina− tion and Maintenance Manual Section 3, or Symmetrix Model 3630/5630 Product Manual Appendix C
Successful comple− tion of IML POST
None None
AND:
Device Support Facili− ties User’s Guide, GC35 −0033, Chapter 11
Error free comple− tion running ICKDSF using Analyze command with SCAN and DRIVE TEST options on any logical volume
None None
(2) Disk Device … 529 Successful comple− tion of replacement drive diagnostics, and resynchroniza− tion of logical volumes
None None
(3) Power Supply … 529 No environmental power faults or alarms
None Temporary change state alarm
304.MTS.
a. IBM 3480 Model A22
MTCU.
OLTs … IBM 3480 Online Test (OLT), D99 −3480A −00, pages 1 through 33
Error free completion
Same as standard
Same as initial
b. IBM 3480 Model B22 MTU.
OLTs … IBM 3480 Online Test (OLT), D99 −3480A −00, pages 1 through 19 and 48 through 56
Error free completion
Same as standard
Same as initial
STANDARDS AND TOLERANCES (Continued)
Tolerance/Limit Standard Reference Paragraph Parameter
Operating Initial Standard Reference Paragraph Parameter
305.S1RPAM SUBSYSTEM.
a. IBM 7026 Model H50
RISC/6000 Processor.
(1) H50 Diagnostics … 517; IBM RISC/6000 Enterprise Server Model H50 User’s Guide, SA38 −0546 −00, Chap− ter 8, Steps 1 −5
Error free completion
Same as standard
Same as initial
(2) S1RPAM …
Diagnostics.
507; TI 6110.11 Error free completion
Same as standard
Same as initial
(3) S1RPAM Wrap …
Diagnostics.
516; TI 6110.11 Error free completion
Same as standard
Same as initial
b. Lexmark 2391 Plus …
Matrix Printer.
TI 6110.10 Error free completion
Same as standard
Same as initial
c. S1RPAM Replacement . . . .
Operation.
515 Successful replacement as verified using manual requests
Same as standard
Same as initial
306.ISD SUBSYSTEM.
a. IBM RISC/6000 Model . . . .
770 or 771. Error free completion
Same as standard
Same as initial
b. IBM 4226 or 4232 … Line Printer Operation.
514; IBM 4226 Printer User’s Reference, GA18 −7182 −0, pages 5 −3 through 5 −4. IBM 4232 Printer User’s Guide, SA24 −43506 −01, Chapter 4
Error free completion
Same as standard
Same as initial
c. Sony 20x20 Color …
Display.
TI 6110.4 Error free completion
Same as standard
Same as initial
d. Server Switchover … 509 Successful switchovers as verified using manual requests
Same as standard
Same as initial
STANDARDS AND TOLERANCES (Continued)
Tolerance/Limit Standard Reference Paragraph Parameter
Operating Initial Standard Reference Paragraph Parameter
e. LAN Switchover … 510 Successful switchov− ers as verified using manual requests
Same as standard
Same as initial
f. Disk ARRAY/6000 … 513 The disk ARRAY is functioning proper− ly under normal conditions
Same as standard
Same as initial
307.TP SUBSYSTEM.
a. IBM RISC/6000 Model . . . .
770 or 771. 512; POWERstation and POWERserver Common Diagnostics and Service Guide, Chapter 5, pages 5 −1 through 5 −3
Error free completion
Same as standard
Same as initial
b. IBM 4226 Model 302 …
Line Printer Operation.
514; IBM 4226 Printer User’s Reference, GA18 −7182 −0, pages 5 −3 through 5 −4.
Error free completion
Same as standard
Same as initial
c. Server Switchover … 509 Successful switchover as verified using manual requests
Same as standard
Same as initial
d. LAN Switchover … 510 Successful switchover as verified using manual requests
Same as standard
Same as initial
e. System Console …
Switchover.
511 Successful switchover as verified using manual requests
Same as standard
Same as initial
f. Disk ARRAY/6000 … 513 The disk ARRAY is functioning proper− ly under normal conditions
Same as standard
Same as initial
308.AIDCS SUBSYSTEM.
a. HP NetServer LC II …
System Computer.
TI 6110.6, Section6.1.1
Error free completion
Same as standard
Same as initial
STANDARDS AND TOLERANCES (Continued)
Tolerance/Limit Standard Reference Paragraph Parameter
Operating Initial Standard Reference Paragraph Parameter
b. Epson LQ −570 Printer. . . . TI 6110.6, Section6.1.2
Ink level is ade− quate and printing operation causes paper advance and displays correct character height and width
Same as standard
Same as initial
c. ME800A Short Haul …
Modems.
518 Green front panel Transmit Data (TD) or Receive Data (RD) light flashes approxi− mately twice per second
Same as standard
Same as initial
d. Eicon X.25 Interface …
Adapter.
TI 6110.6, Section6.1.4
Color of all FIR names in AIDCS address list are yel− low or green
Same as standard
Same as initial
e. UPS 600 or 1000 … 520 The LED labeled OOn Line" is lit
Same as standard
Same as initial
f. ODAPS −AIDCS −FIR … Interfaces (New York ARTCC).
521 A TR message is sent from ODAPS through AIDCS to a FIR. ODAPS re− ceives a DT re− sponse within 30 seconds.
Same as standard
Same as initial
g. ODAPS −AIDCS −FIR …
Interfaces (Oakland ARTCC).
522 A TR message is sent from ODAPS to AIDCS. ODAPS receives a DT re− sponse within 5 to 10 seconds. A MIS message is sent from AIDCS to a FIR (if necessary). AIDCS receives a LAM response within 30 seconds.
g. ODAPS −AIDCS −FIR …
Same as standard
Same as initial
309.ODL SUBSYSTEM.
a. IBM RISC/6000 Model . . . .
770 or 771. 512 Error free completion
Same as standard
Same as initial
b. IBM 4226 or 4232 …
Line Printer.
514 Error free completion
Same as standard
Same as initial
STANDARDS AND TOLERANCES (Continued)
Tolerance/Limit Standard Reference Paragraph Parameter
Operating Initial Standard Reference Paragraph Parameter
c. ODL Service Level …
Certification.
525 Error free completion
Same as standard
Same as initial
d. ODL Server …
Switchover.
526 Successful switchover as verified using manual requests
Same as standard
Same as initial
e. ODL LAN Switchover … 527 Successful switchover as verified using manual requests
Same as standard
Same as initial
f. ODL Disk ARRAY/6000. . . . 513 The disk ARRAY is functioning proper− ly under normal conditions
Same as standard
Same as initial
g. ODL System Level …
Certification.
524 Error free completion
Same as standard
Same as initial
h. ODL Unit Level …
Certification.
523 Error free completion
Same as standard
Same as initial
310.SYMMETRIX 5630 DASD M&C SUBSYSTEM.
a. M&C Server, IBM RS/6000
Model H80.
(1) POST … RS/6000 Enterprise Server Model H80 Se− ries Service Guide, Chapter 1, or CDRL D038, System Problem Determination and Maintenance Manual, Section 6.1.2.2.4
Error free completion
Same as standard
Same as initial
(2) Online …
Diagnostics.
RS/6000 Enterprise Server Model H80 Se− ries User’s Guide, Chapter 5
Error free completion
Same as standard
Same as initial
(a) Service Mode.
(b)Maintenance Mode.
(c) Concurrent Mode.
STANDARDS AND TOLERANCES (Continued)
Tolerance/Limit Standard Reference Paragraph Parameter
Operating Initial Standard Reference Paragraph Parameter
(3) Standalone …
Diagnostics.
RS/6000 Enterprise Server Model H80 Se− ries User’s Guide, Chapter 5
Error free completion
Same as standard
Same as initial
b. Ethernet Switch, Cisco
2924M XL −EN.
POST … . . . Catalyst 2900 Series XL Installation Guide, Cisco Systems, Chap− ter 3, or CDRL D038, Storage Subsystem Certification Manual, Section 3.4.1.2
Error free completion
Same as standard
Same as initial
c. M&C User Position, …
NCD NC900 Thin Client.
CDRL D038, System Problem Determina− tion and Maintenance Manual
POST … . . . Section 6.1.2.5, and the NCD NCBridge Software Reference Manual, Chapter 5
Error free completion
Same as standard
Same as initial
d. Printer, Lexmark …
Optra M410..
CDRL D038, System Problem Determina− tion and Maintenance Manual
POST … . . . Section 6.1.2.6 Error free completion
Same as standard
Same as initial
e. Transceiver LAN …
Data Paths, Ethercom EFTT1003 −A.
CDRL D038, System Problem Determina− tion and Maintenance Manual
Observe Light Emitting … Diodes(LED) ON switch.
Sections 6.1.2.7 and 3.1.4, and Ethercom Model EFTT1003 User’s Manual, page 6
Error free completion
None None
f. Fibre Channel Connec− tivity.
Execute Oinq" … command from AIX command line.
528b Oinq" command responds with list of SCSI devices
None None
311. −399.RESERVED.
CHAPTER 4. PERIODIC MAINTENANCE
CHAPTER 4. PERIODIC MAINTENANCE
400.GENERAL.
a. This chapter establishes all the maintenance activities which are required for the ODAPS automa− tion on a periodic, recurring basis, and the schedules for their accomplishment. The chapter is divided into two sections. The first section identifies the perfor− mance checks (i.e., test, measurements, and observa− tions) of normal operating controls and functions, which are necessary to determine whether operation is within established tolerances/limits. The second section identifies other tasks which are necessary to prevent deterioration and ensure reliable operation. Refer to Order 6000.15 for additional general guid− ance.
b. In addition to the periodic, recurring activities specified in this chapter, Order 6000.15 establishes requirements for routine maintenance and other spe−
cific maintenance activities which are to be performed for all AF equipment
c. All reference paragraphs pertaining to stan− dards and tolerance/limits are found in chapter 3 of this order, unless otherwise stated.
d. The performance checks and maintenance tasks are not to be taken as the minimum work re− quired for proper maintenance, rather as the maxi− mum interval permitted between tasks. This chapter will reference specific paragraphs for the mainte− nance activities listed in the individual equipment instruction books and their frequency of accomplish− ment.
e. Additional maintenance activities, not listed in the instruction books, will refer the user to chapter 5 of this handbook for the appropriate maintenance procedures.
Section 1.CCCPERFORMANCE CHECKS
Section 1.CCCPERFORMANCE CHECKS
Reference Paragraph
Performance Checks Standards &
Tolerances
Maintenance
Procedures
401.DAILY.
a. ODAPS.
(1) Input at least five flight plans to demonstrate …
that the Full Data Blocks (FDB) thereby generated are correctly displayed upon the ISD OCs. One FDB shall be generated at the point of tangency, and the next four FDBs at the four points farthest from the point of tangency. The flight plans should be input from KVDTs or TP Workstations and their combined routes shall penetrate all adapted sectors that have airspace. The flight shall represent overflights or traffic originating or landing within a sectors airspace. The simulated flight plans shall be such that strip printing is initiated.
301a 506
(2) Test all KVDTs using the GI and TD messages …
addressed to each KVDT. The GI messages shall include the position identification (C1, E1, etc.), Logical Device Number (LDN) (200, 204, etc.), and device address (8D, 3F, etc.).
301b 506
(3) Use TD messages to cause display of the …
workstation monitor test pattern at all sector positions. Invalid messages shall be included that cause the sector number, LDN, and FDIO address to be written on the workstation monitor.
301c 506
(4) Exercise all ODAPS TFSPs using the TD message … 301d 506
(5) Use TR or MIS messages to elicit response …
from all adjacent NAS facilities or FIRs.
301e, 308f, 308g 506, 521, 522
b. AIDCS.
Check for satisfactory operation of … interface to FIRs.
308d TI 6110.6, Section6.1.4
c. ODL.
Execute the Olinktest" script … 309c 525
402.WEEKLY.
a. ODAPS.
Check for satisfactory system operation following a … manually initiated switchover.
301f 508
Section 1.CCCPERFORMANCE CHECKS (Continued)
Section 1.CCCPERFORMANCE CHECKS (Continued)
Performance Checks
Reference Paragraph
Performance Checks Maintenance
Procedures Standards &
Tolerances
b. TP.
(1) Servers.
Check for satisfactory system operation following … a manually initiated switchover.
307c 509
(2) LAN.
Check for satisfactory system operation following … a manually initiated switchover.
307d 510
(3) SCs.
Check for satisfactory system operation following … a manually initiated switchover.
307e 511
(4) Disk ARRAY/6000.
Check that the disk ARRAY is operating correctly … 307f 513
c. ISD.
(1) Servers.
Check for satisfactory system operation following … a manually initiated switchover.
306d 509
(2) LAN.
Check for satisfactory system operation following … a manually initiated switchover.
306e 510
(3) Disk ARRAY/6000.
Check that the disk ARRAY is operating correctly … 306f 513
d. S1RPAM.
Check for satisfactory system operation following … a manually initiated replacement.
305c 515
e. AIDCS.
UPS 600 or 1000.
Check for satisfactory operation of UPS … 308e 520
Section 1.CCCPERFORMANCE CHECKS (Continued)
Performance Checks
Reference Paragraph
Performance Checks Maintenance
Procedures Standards &
Tolerances
f. ODL.
(1) Servers.
Check for satisfactory system operation following . . . . a manually initiated switchover.
309d 526
(2) LAN.
Check for satisfactory system operation following a . . . . manually initiated switchover.
309e 527
(3) Disk ARRAY/6000.
(a) Check that the disk ARRAY is operating …
correctly.
309f 513
(b)Run Checkarray diagnostic command … TI 6110.15, paragraph 7.7.1.12.5 TI 6110.15, paragraph 7.3.2.5.8
g. Symmetrix 5630 M&C Subsystem.
M&C Server, IBM RS/6000 Model H80.
Archive Event Log file on CD, and … swap active and standby servers.
Successful archive/ backup and successful swap to other server
528a
403.MONTHLY.
a. FDPS.
(1) IBM 3268 Model 2C Console Printer.
(a) Print quality tests, run print all characters …
test (test number 01) and print ripple pattern test (test number 76).
302b(2) IBM 3268 Printer Models 1, 2, and 2C Maintenance Informa− tion, SY27 −0201 −4, sections 731 and 736.
(b)Run Basic Acceptance Test (BAT), internal …
wrap test (test number 62), and print error log.
302b(1) BM 3268 Printer Mod− els 1, 2, and 2C Main− tenance Information, SY27 −0201 −4, sec− tions 716, 725, 743, 746, and 749
(2) HMC Alarm Box.
Check lamp illumination and audible tone … Successful completion 519
Section 1.CCCPERFORMANCE CHECKS (Continued)
Performance Checks
Reference Paragraph
Performance Checks Maintenance
Procedures Standards &
Tolerances
b. S1RPAM.
(1) Modem Splitter Power Distribution Panel.
Verify the green and yellow LEDs are lit … TI 6110.10 TI 6110.10
(2) Gateway 5100 or 5150 Notebook System Console.
Verify the green LED on the LAN cable … connector is lit.
TI 6110.10 TI 6110.10
c. AICDS.
ME800A Short Haul Modems.
Check for satisfactory operation of interface to … ODAPS Communications Subsystem (OCS).
308c 518
404.QUARTERLY.
a. FDPS.
(1) IBM 3274 Model 301D Terminal Control Unit.
Run OLTs T3274A … (FAA Form 6110 −6 entry).
302d IBM Maintenance Diagnostic Program Local 3274 Model 1B/1D Display System On−Line Tests, D99 −3274A −01, pages 1 through 19
(2) IBM 4245 Model 12 Line Printer.
Run BAT (Routine group C0) … 302c IBM 4245 Printer Models 12 and 20 Maintenance Informa− tion Manual, Volume 1, pages DIA −040, DIA −050, and DIA −200
Section 1.CCCPERFORMANCE CHECKS (Continued)
Performance Checks
Reference Paragraph
Performance Checks Maintenance
Procedures Standards &
Tolerances
(3) IBM 9672 Model RA4 Processor.
(a) 9672 Frame.
Run POST and the Checkout Tests … (FAA Form 6110 −6 entry.)
302a(1) IBM S/390 Support Element Operations Guide, GC38 −3108 −03. IBM S/390 Installation Manual, SY24 −6156 −04. IBM S/390 Service Guide, SY24 −6158 −04
(b)9672 SE.
Run POST Test … (FAA Form 6110 −6 entry.)
302a(2) IBM S/390 Support Element Operations Guide, GC38 −3108 −03. IBM S/390 Installation Manual, SY24 −6156 −04
(c) HMC.
Run POST Test … (FAA Form 6110 −6 entry.)
302a(3) IBM S/390 Support Element Operations Guide, GC38 −3108 −03. IBM S/390 Installation Manual, SY24 −6156 −04
b. DASD.
(1) IBM 3380 Models AD4, AE4, BD4, and BE4 DASDs.
(a) Run OLT’s T3380PSA (Pack Scan−A) …
(FAA Form 6110 −6 entry.)
303a IBM 3380 Online Test (OLT) User’s Guide, D99 −3380A −02, pages 1 through 4, 7 through 12, 18, 19, and 32 through 34
(b)Run OLT’s T3380PSB (Pack Scan−B) …
(FAA Form 6110 −6 entry.)
303a IBM 3380 Online Test (OLT) User’s Guide, D99 −3380A −02, pages 1 through 4, 7 through 11, 13, 21, 22, and 32 through 44
Section 1.CCCPERFORMANCE CHECKS (Continued)
Performance Checks
Reference Paragraph
Performance Checks Maintenance
Procedures Standards &
Tolerances
(2) IBM 3880 Model 3 SCU.
Run OLT’s T3880A (Routines 1, 2, and 3 only) … (FAA Form 6110 −6 entry.)
303b IBM Maintenance Diagnostic Program 3880 Storage Director Online Test, DCL −3880A −02 (D99 −3880A −01), pages 1 through 8
(3) Symmetrix 5630 DASD Subsystem.
(a) Run POST diagnostic … 303c(1) CDRL D038, System Problem Determination and Maintenance Manual Section 6.1.2.11, or Symmetrix Model 3630/5630 Product Manual Appendix C
(b)Run ICKDSF diagnostic using Analyze …
command with SCAN and DRIVE TEST options on any logical volume.
303c(1) Device Support Facili− ties User’s Guide, GC35 −0033, Chapter 11
c. MTS.
(1) IBM 33080 Model A22 MTCU.
Run OLT’s T33080A … (FAA Form 6110 −6 entry.)
304a IBM 3480 Online Tests (OLT’s), D99 −3480A −00, pages 1 through 33
(2) IBM 3480 Model B22 MTU.
Run OLT’s T33080C … (FAA Form 6110 −6 entry.)
304b IBM 3480 Online Tests (OLT’s), D99 −3480A −00, pages 1 through 19, and 48 through 56
d. S1RPAM.
(1) Lexmark 2391 Plus Matrix Printer.
Print internal demonstration page … 305b TI 6110.10
Section 1.CCCPERFORMANCE CHECKS (Continued)
Performance Checks
Reference Paragraph
Performance Checks Maintenance
Procedures Standards &
Tolerances
(2) IBM 7026 Model H50 RISC/6000 Processor.
Run Diagnostics … (FAA Form 6110 −6 entry.)
305a(1) 517; IBM RISC/6000 Enterprise Server Model H50 User’s Guide, SA38 −0546 −00, Chap− ter 8, Steps 1 −5
(3) System.
(a) Run S1RPAM Diagnostics except selected Offline . . .
Diagnostics. (FAA Form 6110 −6 entry.)
305a(2) 507; TI 6110.11
(b)Run S1RPAM Wrap Diagnostics …
(FAA Form 6110 −6 entry.)
305a(3) 516; TI 6110.11
e. ISD.
(1) Server.
Run Central Processing Unit (CPU) Diagnostics … (FAA Form 6110 −6 entry.)
306a 512
(2) OC.
Run CPU Diagnostics … (FAA Form 6110 −6 entry.)
306a 512
(3) SC.
Run CPU Diagnostics … (FAA Form 6110 −6 entry.)
306a 512
(4) IBM 4226 or 4232 Line Printer.
Run Printer Self Test … 306b 514
f. TP.
IBM RISC 6000/770 or 771 CPU.
(1) Server.
Run CPU Diagnostics … (FAA Form 6110 −6 entry.)
307a 512
(2) Workstation.
Run CPU Diagnostics … (FAA Form 6110 −6 entry.)
307a 512
Section 1.CCCPERFORMANCE CHECKS (Continued)
Performance Checks
Reference Paragraph
Performance Checks Maintenance
Procedures Standards &
Tolerances
(3) SC.
Run CPU Diagnostics … (FAA Form 6110 −6 entry.)
307a 512
(4) IBM 4226 Model 302 Line Printer.
Run Printer Self Test … 307b 514
g. AIDCS.
(1) HP NetServer LC II System Computer.
Verify AIDCS system computer is operating … normally. (FAA Form 6110 −6 entry.)
308a TI 6110.6, Section6.1.1
(2) Epson LQ −570 Printer.
Check for satisfactory operation of printer … 308b TI 6110.6, Section6.1.2
h. ODL.
(1) Total System.
Run ODL System Level Certification … (FAA Form 6110 −6 entry.)
309g 524
(2) IBM 4226 or 4232 Line Printer.
Run Printer Self−Test … 309b 514
i. Symmetrix 5630 M&C Subsystem.
(1) M&C Server, IBM RS/6000 Model H80.
Run OService Mode" diagnostic suite … 310a RS/6000 Enterprise Server Model H80 Series Service and User’s Guide
(2) Ethernet Switch, Cisco 2924M XL −EN.
Run POST … 310b Catalyst 2900 Series XL Installation Guide, Cisco Systems, Chapter 3, or CDRL D038, System Problem Determination and Maintenance Manual, Section6.1.2.3.1
Section 1.CCCPERFORMANCE CHECKS (Continued)
Performance Checks
Reference Paragraph
Performance Checks Maintenance
Procedures Standards &
Tolerances
(3) M&C User Position, NCD NC900 Thin Client.
Run POST … 310c CDRL D038, System Problem Determina− tion and Maintenance Manual, Section 6.1.2.5, and the NCD NCBridge Software Reference Manual, Chapter 5
(4) Printer, Lexmark Optra M410.
Run POST … 310d CDRL D038, System Problem Determina− tion and Maintenance Manual, Section 6.1.2.6
(5) Transceiver LAN Data Paths, Ethercom EFTT1003 −A.
Observe LED’s ON switch … 310e CDRL D038, System Problem Determina− tion and Maintenance Manual, Sections 6.1.2.7 and 3.1.4, and Ethercom Model EFTT1003 User’s Manual, page 6
(6) Fibre Channel Connectivity.
Execute Oinq" command from AIX command line … 310f 528b
405.SEMIANNUALLY.
ISD.
Sony 20x20 Color Display.
a. OC.
Run Touch−up Alignment Procedure … (FAA Form 6110 −7 entry.)
306c TI 6110.4
b. SC.
Run Touch−up Alignment Procedure … (FAA Form 6110 −7 entry.)
306c TI 6110.4
Section 1.CCCPERFORMANCE CHECKS (Continued)
Performance Checks
Reference Paragraph
Performance Checks Maintenance
Procedures Standards &
Tolerances
406.ANNUALLY.
a. S1RPAM.
(1) Automatic Switching System Series 5000 A/B Switch.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
(2) Modem Splitters.
Check all I/O cables and connectors … Connectors secure and cables undamaged
505
(3) Modem Splitter Power Distribution Panels.
Check all power cords and cables … Connectors secure and cables undamaged
505
(4) Gateway 5100 or 5150 Notebook System Console.
Check all cables and connectors … Connectors secure and cables undamaged
505
(5) IBM 7026 Model H50 RISC/6000 Processor.
Check all cables and connectors … Connectors secure and cables undamaged
505
(6) Lexmark 2391 plus Matrix Printer.
Check all cables and connectors … Connectors secure and cables undamaged
505
b. ISD.
(1) Servers.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
(2) LAN.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
(3) OCs.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
Section 1.CCCPERFORMANCE CHECKS (Continued)
Performance Checks
Reference Paragraph
Performance Checks Maintenance
Procedures Standards &
Tolerances
(4) SCs.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
c. TP.
(1) Servers.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
(2) LAN.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
(3) Workstations.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
(4) SCs.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
d. FDPS.
T −Bar Variswitch A/B Switches.
(1) Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
(2) Check operation and battery backup … Successful completion 504
e. AIDCS.
(1) HP NetServer LC II System Computer.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
TI 6110.6, Section6.2.4
(2) Epson LQ −570 Printer.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
TI 6110.6, Section6.2.4
Section 1.CCCPERFORMANCE CHECKS (Continued)
Performance Checks
Reference Paragraph
Performance Checks Maintenance
Procedures Standards &
Tolerances
(3) ME800A Short Haul Modems.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
TI 6110.6, Section6.2.4
(4) Eicon X.25 Interface Adapter.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
TI 6110.6, Section6.2.4
(5) UPS 600 or 1000.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
TI 6110.6, Section6.2.4
f. ODL.
(1) Servers.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
(2) LAN.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
(3) Workstations.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
(4) System Consoles.
Check all power cords, cables, and connectors … Connectors secure and cables undamaged
505
g. Symmetrix 5630 M&C Subsystem.
M&C Server, IBM RS/6000 Model H80.
Check tape drive operation … Error free operation CDRL D038, System Problem Determina− tion and Maintenance Manual, Section 6.1.2.4, and the SONY SDT −10000 Digital Data Storage (DDS) Drive Unit Operator’s Guide
Section 1.CCCPERFORMANCE CHECKS (Continued)
Performance Checks
Reference Paragraph
Performance Checks Maintenance
Procedures Standards &
Tolerances
407.AS REQUIRED.
a. FDPS.
MCCU.
Run OLTs T3150A and T3150STS … 302a(4) IBM Channel−to− Channel Adapter or 3088 MCCU Exerciser On−Line Test User Guide, D99 −3150A −05
b. ODL.
(1) Servers, System Consoles, and Sector Workstations.
This test is intended to be run after repair to either of the mentioned units.
Run Ounit cert" script … 309h 523
(2) IBM RISC 6000 770/771.
Run CPU Diagnostics to assist in diagnosis of … problems on Servers, System Consoles, and Sector Worksta− tions.
309a 512
c. Symmetrix 5630 M&C Subsystem.
(1) Disk Drive.
Validate disk drive replacement action … 303c(2) 529
(2) Power Supply.
Validate power supply replacement action … 303c(3) 529
408. −449.RESERVED.
Section 2.CCCOTHER MAINTENANCE TASKS
Section 2.CCCOTHER MAINTENANCE TASKS
Reference Paragraph
Maintenance Tasks Standards &
Tolerances
Maintenance
Procedures
450.RESERVED.
451.WEEKLY.
a. FDPS.
(1) IBM 4245 Model 12 Line Printer.
(a) Clean and vacuum print chain, clean gate, …
and front area of the printer.
Visibly clean IBM 4245 Printer Models 12 and 20 Maintenance Informa− tion Manual, Volume 1, page TTE −050
(b)Check for correct ribbon skew … Correctly skewed IBM 4245 Printer Models 12 and 20 Maintenance Informa− tion Manual, Volume 2, pages FRO −140 through FRO −200
(c) Run test pattern routine (routine 61), …
print/skip/space exerciser (routine 63), character set arrangement test (routine 66), and print quality pat− tern (routine number 67).
Characters easily dis− cernible
IBM 4245 Printer Models 12 and 20 Maintenance Informa− tion Manual, Volume 1, pages DIA −040, DIA −050, DIA −110, DIA −130, DIA −210 through DIA −270, and DIA −290
(d)Print error low … No excessive accu− mulation of errors
IBM 4245 Printer Models 12 and 20 Maintenance Informa− tion Manual, Volume 1, pages LSE −020 and LSE −030
(2) Reserved.
b. ISD.
(1) OCs.
(a) Inspect console for cleanliness … Visibly clean 555
(b)Inspect console for damage … Console undamaged TI 6110.4
(c) Inspect console for proper display presentation … Clear and precise dis− play images
TI 6110.4
Section 2.CCCOTHER MAINTENANCE TASKS (Continued)
Section 2.CCCOTHER MAINTENANCE TASKS (Continued)
Maintenance Tasks
Reference Paragraph
Maintenance Tasks Maintenance
Procedures Standards &
Tolerances
(2) System Consoles.
(a) Inspect console for cleanliness … Visibly clean 555
(b)Inspect console for damage … Console undamaged TI 6110.4
(c) Inspect console for proper display presentation … Clear and precise dis− play images
TI 6110.4
c. AIDCS.
HP NetServer LC II System Computer.
(1) Inspect monitor for cleanliness … Visibly clean 555
(2) Extract log files from system … Log files are extracted from the computer system
NASP −7211, Section3.2.3.1
d. ODL.
IBM 7208 Tape Drive.
Clean and inspect tape drive … Error free completion 551
452.RESERVED.
453.MONTHLY.
a. ISD.
(1) Server.
(a) Clean Cathode Ray Tube (CRT) and keyboard … Visibly clean 555
(b)Vacuum interiors and check for obstructions … Visibly clean 552
(c) Check CPU cooling fans for proper operation … Visibly operating 554
(2) OC.
(a) Clean CRT and keyboard … Visibly clean 555
(b)Vacuum interiors and check for obstructions … Visibly clean 552
(c) Check CPU cooling fans for proper operation … Visibly operating 554
Continue reading ↓ 120 of 223 passages shown