Order 6980.24A Battery Theory and Selection Guidelines
This document is cancelled. It may have been replaced. Check the official source before relying on it.
ORDER I 6980.24A I
ORDER I 6980.24A I
July 12, 1988
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
Distribution: A-W(PS/~)-3;A-X(AF)-3;A-Y(FA/AY)-3 Initiated By: ~~~-130
RECORD OF CHANGES OfllECtl~E NO.
I 6980.24A I
J CHANGE SUPPIDEMENTS CHANGE suPPLEMEMS TO
I OPTIONAL USE TO ’ OPiiONAl USE BASIC BASIC
I OPTIONAL USE TO ’ OPiiONAl USE BASIC BASIC
I .
I
I I
1 T
1
1
.
-_- -. FAA Form 1320-S (S-68) SUPERSEDES PREVIOUS EDITION C FM AC 7s-8744
July 12, 1988 6980.24A
This order contains the information necessary to properly select and size batteries for either existing or proposed Federal Aviation Administration (FAA) equipment or facilities which are or will be dependent on battery systems for backup electrical power.
The rechargeable batteries which have been determined to be most suitable for application to the present and future FAA requirements are discussed herein. In each instance where a battery type is concerned, theory and chemistry in addition to operating parameters are covered in detail.
' Acting Director, Program
Engineering Service
Page i(and ii)
July 12, 1988 - 6980.24s
TABLE OF CONTENTS
TABLE OF CONTENTS
CHAPTER 1. GENERAL
1 0 Purpose 2 0 Distribution 3 0 Cancmllatlon 4 a Action 5 0 Background 6 l Definitions 7 0 Objaotive 8 0 S0ope
CHAPTER 2. BATTERY THEORY
9 0 Basic Theory 5 10 0 Primary Ce118 8 11 l Secondary cells 8 12 l Applloability 9 13 0 Lead-Aoid 16 14 a Nickel-Cadmium-Alkaline 22
CHAPTER 3. BATTERY SBLBCTIOR
CHAPTER 3. BATTERY SBLBCTIOR
15 0 Chapter Overview
SECTION 1. NEW (ORIGINAL) BALTTRIBS
16 0 Sp8t8IB Approach 17 0 Initial Prooe88 18 0 Data Sheet 19 l New (Original) Battery 20 0 Daterrlna Battery Parameter8 21 l Plow Chart Seleation Of New (Original) Batterlea
SECTION 2. REPLACEMBBT BATTERIES
SECTION 2. REPLACEMBBT BATTERIES
22 0 Replaaenent Batteries
CHAPTER 4. BATTERY FACILITY DESIGl!
23 0 Battery Facilities 24 0 Rooms, Compartmsnt8, Platform8
29
29
29
29 29 30 36 48
51
54
54
57
57 57
Page iii
6g80,24A July 12, 1988
TABLE OF CONTEHTS
. 25 0 Battery Facility Ventilation 57 26 0 TempsratUr8 EnViPOnIl8nt 60 27 0 Weight Support 60 28 60 0 s8iBaPiCB Comidarationa 29 0 S a f e t y 61
TABLE OF CONTEHTS
Page Iv
July 12, 1988 l
6980.248
LIST OF FIGURES
FIGURE 3-1 Battery Facility Data Sheet 31 FIGURE 3-2 Battery S8180tiOn Flow Chart 53 FIGURE 4-i s818mi0 ZODe8 61 FIGURE 4-2 united State8 Seiamia Zones 62
TABLE 2-l
TABLE 2-2
TABLE 2-3 TABLE 2-4
TABLE 2-5
TABLE 2-6
TABLE 3-l TABLE 3-2
TABLE 3-l TABLE 3-2
TABLE 3-3
TABLE 3-4
LIST OF TABLES
Lead-Aaid Battery Capaofty VS Temper-
ature Example Of Lead-Acid Low Rate Stationary Battery Capaalty Versus Rat8 Lead-Aaid Battery Charge Voltage Niakel-Cadmium-Alkaline Battery Capaalty VS Terperature Example Of Niakel-Cadmium-Alkaline Pocket Plate Cell Capacity Veraua Rate Float Voltage Effects On Nickel-Cadmium-Alkaline Batterlea Halntananae Interval Example Of Lead-Acid Low Rate Stationary Battery Capacity Veraua Rate Example Of Nickel-Cadmium-Alkaline Pocked Plate Cell Capacity Veraua Rate Replaaement Battery Data For Stationary Engine Generator8
LIST OF TABLES
APPENDIX 1,
Determining Battery Capaalty For Complex Load (6 pages) APPERDIX 2.
. T8mp8rature Conversion Table (3 pages) APPENDIX 3m
Battery Seleation And Sizing Example (5 pages)
18
19 20
24
24
26 39
45
46
54
Page v(and vi)
July 12, 1988 6980.244
CHAPTER 1. GENERAL
1 PURPOSE* This order provides battery theory and selection procedures for new and replacement secondary (rechargeable) batteries for application in FAA equipment and facilities. Battery facility design considerations are included as chapter 4. This order be should be used in conjunction with FAA Order 6980.26, Battery Backup Power Systems - Theory And Selection Guidelines, when developing requirements for a complete direct-current (dc) battery operating standby power distribution
CHAPTER 1. GENERAL
system.
2 DISTRIBUTION. This order is distributed to branch level in the Program Engineering Service and Systems Maintenance Service in Washington headquarters; to branch level in the regional Airway Facilities divisions; and to branch level in the Facility Support Division and the FAA Academy at the Mike Monroney Aeronautical Center.
3 CANCELLATION. This order cancels Order 6980.24, Battery Theory and Selection Guidelines, dated February 7, 1983.
4 ACTION. The battery theory and selection procedures given in this order shall be used to select and size new and replacement batteries for FAA equipment and facilities.
5 BACKGROUND. In the past, the FAA has depended primarily on engine generators to provide stand-by power to its facilities. Advances in solid-state technology and increased use of directcurrent-powered electronic equipment has prompted the agency to investigate other sources of stand-by power. In employing these systems, the selection of the optimum battery is critical. This order has been revised to provide more detailed information and guidance in the selection of the most cost effective battery system. In addition, the battery facility design chapter has been expanded to include more considerations to improve battery performance, battery life and human safety.
6 DEFINITIONS. The definitions of selected words used in the text of this order are provided in this paragraph. These selected words are either not of wide and ordinary use, or the meaning of the word as used herein is different from ordinary or normal usage.
a. Ampere-Houra The product of direct current in amperes, multiplied by'the time in hours that the current exists.
b l Batterv. An electrochemical energy storage device, consisting of one or more cells.
c . C-Rate. Discharge or charge current rate in amperes; numerically equal to rated capacity of a cell in ampere-hours.
Chap 1 Par 1 Page 1
6980.24A July 12, 1988
d fmJb. A single electrochemical couple. consists of a container,
A cell a positive plate or group of plates connected to the positive cell terminal, a negative plate or group of plates connected to the negative cell terminal, and electrolyte.
e. 11 Reversal Electrochemical reversal of polarity of the plates of a secondary battery cell due to forced discharging
(reversed polarity charging) after the cell voltage has decreased to zero volts.
f terminils.
Cell Voltage. The voltage measured at the battery cell
g Charge. State of Condition of a cell in terms of the discharge capacity remaining in the cell relative to the discharge capacity of a fully charged cell.
h Charm Rate. battery is charged.
The current at which a secondary cell or It may be expressed in amperes or as a fraction or multiple of the battery's capacity (capacity considered as if delivered in 1 hour). For example, the lO-hour charge rate of a 4-ampere-hour cell is C/10 = h/10 = 0.4A = 4OOmA.
1 battery.
Charge. Process of supplying electrical energy to a
3 0 CYcle, One sequence of battery discharge and recharge.
k cycl8s'del
vcle Life The total number of discharge-recharge vered by i battery until the battery is unable to perform satisfactorily.
1 DeeDa Withdrawal of at least 80 percent of the raied capacity of a cell or battery.
m. Denth of DischargQ The percentage of rated capacity to which a cell or battery ii discharged.
n. Discharge. Withdrawal of electrical energy from a battery.
0 . ischarge Rate. The current at which a battery is discharged. (See Charge Rate.)
P Pry CharQed A battery that contains cell plates in the chirged condition'but does not contain electrolyte.
9 Electrolvte. The material that conducts the ions between the positive and negative plates of a battery cell.
July 12, 1988 6980.24A
Yo E n e r g y D e n s i t y . R a t i o o f c e l l e n e r g y t o w e i g h t o r v o l u m e ( w a t t - h o u r s p e r p o u n d o r w a t t - h o u r p e r c u b i c i n c h ) .
8. Float Charne. T h e c o n d i t i o n o f a s e c o n d a r y b a t t e r y b e i n g m a i n t a i n e d i n t h e f u l l y c h a r g e d s t a t e b y s t e a d y a p p l i c a t i o n o f c h a r g i n g p o w e r ( c o n s t a n t v o l t a g e o r v o l t a g e l i m i t e d ) s u f -
f i c i e n t t o o v e r c o m e i n t e r n a l b a t t e r y p o w e r l o s s e s a t t h e a p p l i e d v o l t a g e b u t n o t s u f f i c i e n t t o c a u s e s i g n i f i c a n t g a s e v o l u t i o n w i t h i n t h e b a t t e r y c e l l s .
. . t. I n t e r n a l R e s i s t a n c e . Resistance to electric current i n s i d e t h e b a t t e r y .
UO Open-Circuit Voltap;e, T h e n o - l o a d v o l t a g e o f a c e l l o r b a t t e r y m e a s u r e d w i t h a h i g h - r e s i s t a n c e v o l t m e t e r .
77. P i l o t C e l l . O n e o r m o r e c e l l s t h a t a r e u s e d a s a g e n e r a l i n d i c a t o r o f t h e e n t i r e b a t t e r y i n r e g a r d s t o v o l t a g e ,
s p e c i f i c g r a v i t y a n d t e m p e r a t u r e .
Wa P r i m a r y B a t t e r y . A b a t t e r y d e s i g n e d t o b e d i s c h a r g e d a n d t h e n d i s c a r d e d ; n o t d e s i g n e d t o b e r e c h a r g e d .
X0 Recharneable. D e s i g n e d t o b e e l e c t r i c a l l y d i s c h a r g e d a n d r e c h a r g e d f o r m u l t i p l e c y c l e s . ( S e e S e c o n d a r y B a t t e r y . )
Y 0 S e c o n d a r y B a t t e r y . A b a t t e r y w h i c h c a n b e r e c h a r g e d a f t e r b e i n g d i s c h a r g e d u n d e r s p e c i f i e d c o n d i t i o n s o f u s e .
2. S e l f - D i s c h a r g e R a t e . T h e r a t e a t w h i c h a b a t t e r y l o s e s c a p a c i t y w h e n s t a n d i n g o p e n - c i r c u i t .
86. S e p a r a t o r . A p o r o u s , n o n c o n d u c t i v e , m a t e r i a l p l a c e d b e t w e e n p o s i t i v e a n d n e g a t i v e p l a t e s .
bb l T r i c k l e Charninq. M e t h o d o f c h a r g i n g i n w h i c h a s e c o n d a r y c e l l i s c o n n e c t e d t o a c o n s t a n t - c u r r e n t s u p p l y t h a t m a i n t a i n s t h e c e l l i n f u l l y o r n e a r f u l l y c h a r g e d c o n d i t i o n ( n o t used f o r r e c h a r g i n g ) .
cc 0 Wet Charned. A c h a r g e d b a t t e r y t h a t i s f i l l e d w i t h e l e c t r o l y t e .
7 OBJECTIVE l T h e o b j e c t i v e o f t h i s p u b l i c a t i o n i s t o p r o v i d e d&n e n g i n e e r s a n d i n s t a l l a t i o n t e c h n i c i a n s w i t h p e r t i n e n t
i n f o r m a t i o n w h i c h w i l l a i d i n s e l e c t i n g a n d i n s t a l l i n g t h e o p t i m u m s e c o n d a r y b a t t e r y s y s t e m i n f a c i l i t i e s a n d e q u i p m e n t c o n t r o l l e d b y t h e F A A .
8 0 SCOPE. T h i s o r d e r a d d r e s s e s l e a d - a c i d a n d nickel-cadmiuma l k a l i n e s e c o n d a r y b a t t e r i e s w h i c h ure m o s t s u i t a b l e f o r p r e s e n t a n d n e a r f u t u r e a p p l i c a t i o n s i n F A A f a c i l i t i e s a n d e q u i p m e n t s . I n f o r m a t i o n p r e s e n t e d i n t h e f o l l o w i n g c h a p t e r s w i l l g i v e t h e
Chap 1
. Par 6 P a g e 3
6980.24A . July 12, 1988
P a g e 4
Chap 1 P8f 8
July 12, 1988 - 6980.24s
CHAPTER 2. BATTERY THEORY
CHAPTER 2. BATTERY THEORY
9 IjASIC THEORY. Batteries store and provide direct Current 8;8OtriC!ity through internal 818Ctro~hemical FBaCtiOnS. The electrochemical reactions are termed oxidation and reduction reactions. Oxidation i8 defined as a reaction in which the stat8 of a substance becomes more electrically positive. In reduotion, the substance becomes leas eleotrioally positive. Oxidation oan be considered as th8 loss of electrons by a substame; reduction as the gain of electrons by a substance. The substanoes involved in these reaationa are the active materials in the battery electrodes (plates).
a. The neative batt8rv term- is connected to the negative battery plate (spongy, metallie lead in a lead-acid battery and metallic cadmium In a nickel-cadmium-alkaline battery). The negative plate Is called the oathode plate beoauae of the electrochemical ionization reactions assoolat8d with it. On disoharge, the anode plate undergoes an oxidation type of reaction, giving off eleotrona to th8 external circuit and reo8lvlng negative ions from the 818OtrOlyte. The process is reversed during charging. (Refer to an aleotrooheni~al textbook for a diaousaion of cation and anion preferential adsorption.)
b u is connected to the poSitiv8 battery plate (lead peroxide in a lead-acid battery and a nlakel plated steel in a nlokel-oadmlum-alkaline battery). The positive battery plate is called the anode plate beaauae of the associated 8leotrooh8mical ionization raaotiona. On dlaaharge, the oathode plate undergoes reduction, receiving eleatrona from the external ciroult to form negative ions with the eleatrolyte, the process being reversed during aharging.
c. The battarv el8CtrOlVt8 is the medium for Ionic exchange in the electrochemical reactions. It la aontalned within each cell as a liquid or as a past8 or jelly. Liquid 8180trOlyt88 may be free to move within the sell or held in place by a mat or spongy material.
d m batterlea follow this baaia eleatroahemioal prinai- Pl8, vkying In the materials utilized. Various materlala are chosen for aonatruation of the eleotrod88 and formulation of the electrolyte to provide aartaln aharaaterlatlca (sad as more energy per weight, more energy per volume, lower ooat of construction, longer cycle life (aeaondary batterl88), 1888 affected by temperature extremes, eta.), depending on the requirements of the partiaular situation. The materials that react with each other in an eleatrochemloal raaatlon and the potential they generate in a cell can be determined by referring to an electromotive series in a cheaioal referenae publiaatlon. The material higher in the series will be the anode and the other will be the aathode. The difference between the eleatromotiva force (emf)
Chap 2 Par 9 Page 5
6980.24A July 12, 1988
values in the eleatromotfve series will predict the total potential between the electrodes of a cell. As the materials in the battery react with one another, the reaction will slow down a8 the material is exhausted. In the lead-acid battery, electrons are being drawn out of th8 cell rapidly, the material next to the eleatrodes will reaat and use up the electrolyte. This oondition, called stratification, will reduce the battery output until the electrolyte from the remainder of the cell electrolyte diffuses to th8 area next to the electrodes. This resistance to the eleotrooh8mical reaction may be seen as one cause of internal resistance in the electrochemical cell. The electrical reaistance of the internal electrical circuit (metal straps and grids) also oontributea to the internal realstanoe of the battery.
8. Battery ratippa are measures of battery performance. Typical ratings which may be encountered are voltage, capacity, discharge ourrent, and ambient temperature.
(1) Boltage Is typically given as a NOMINAL value, the term nominal being somewhat misleading. Possibly nominal load voltage value would b8 a better choice, but the desired result is a oonvenlent indication of the battery voltage for general description, such as a 12-volt oar battery. The stabilized, open circuit voltage of a single charged lead acid oell la approximately 2.05 volts at 1.200 apeoific gravity (It should be noted that voltage will vary with eleotrolyte concentration). That of a single, charged nlokel-cadmium-alkaline oell is approximately 1.23 volts. Battery voltage is determined by cell chemfstry and the number of cells electrlaally connected in series within the battery. A 12-volt car battery would require 6 series-aonnected lead-aold cells or 10 series-oonn8cted nlckelcadmium-alkaline cells.
(2) macitv la a measure of the battery’s capability to provide current for a period of time. Because th8 battery voltage decreases as it oontlnues to provide aument, the capacity is associated with some voltage value (referred t0 as cutoff voltage) at which further discharging is no longer useful. Basically, capacltp is the time integral of the diacharge aurrent. For many applications, capacity la stated in term8 of ampere-hours, e.g., the produot of diaoharge Current in amperes multiplied by the time in hours that the current exists before th8 battery voltage d8cr8a888 to th8 outoff Voltage. s88 appendix 1 for calaulatlng the aapaclty required by complex discharge aurrent loads. For automotive batteries, the Society of Automotive Engineers 9 Standard 35375 deaaribea rating teats for reserve capacity and cold aranking. The reserve capacity rating Indicates the number of minutes that the teat battery can be discharged at a constant 25 amperes before the battery voltage decreases to 1.75 volts per cell (in an 80 degr88 fahrenheit ambient). The rating for cold oranking lndlcates the oonatant, continuous current that the battery will provide for a standard
July 12, 1988 6980.24A
t e s t t i m e p e r i o d (30 s e c o n d s o r 9 0 s e c o n d s ) w i t h t h e v o l t a g e r e m a i n i n g a b o v e c u t o f f ( 1 . 2 v o l t s o r 1 . 0 v o l t s p e r c e l l ) at a s t a n d a r d t e s t t e m p e r a t u r e ( 0 o r - 2 0 d e g r e e f a h r e n h e i t ) . C a p a c i t y c a p a b i l i t y i s a f f e c t e d b y t h e m a g n i t u d e o f t h e d i s c h a r g e c u r r e n t
( r a t e ) a n d t e m p e r a t u r e , a s w e l l a s t h e q u a n t i t y o f a c t i v e p l a t e m a t e r i a l s a n d e l e c t r o l y t e .
(3) D i s c h a r g e c u r r e n t o r r a t e c a p a b i l i t y m a y b e expressed in terms of a C-rate, hour rate, or amperes. B a t t e r y d i s c h a r g e c u r r e n t c a p a b i l i t y i s d e p e n d e n t u p o n f a c t o r s s u c h a s
i n t e r n a l e l e c t r i c a l r e s i s t a n c e , t e m p e r a t u r e , s t a t e o f c h a r g e , a n d p l a t e c u r r e n t d e n s i t y ( a m p e r e s p e r u n i t a r e a o f p l a t e surfsce). A s t h e d i s c h a r g e c u r r e n t i s i n c r e a s e d , t h e a v a i l a b l e b a t t e r y
c a p a c i t y i s d e c r e a s e d . The capacity change is more pronounced f o r l e a d - a c i d b a t t e r i e s t h a n f o r n i c k e l - c a d m i u m - a l k a l i n e b a t - t e r i e s S a n d v a r i e s w i t h b a t t e r y d e s i g n a n d c o n s t r u c t i o n .
( a ) T h e h o u r r a t e i s c o m m o n l y e n c o u n t e r e d a n d d e s c r i b e s t h e n u m b e r o f h o u r s f o r d i s c h a r g i n g t h e b a t t e r y a t c o n s t a n t c u r r e n t t o a c u t o f f v o l t a g e . An eight-hour rate means t h a t t h e b a t t e r y c a p a c i t y i s d i s c h a r g e d i n e i g h t h o u r s . Typical- 1Y ) t h e n o m i n a l , o r b a s e l i n e c a p a c i t y r a t e f o r l e a d - a c i d s t a t i o n a r y b a t t e r i e s i s t h e 8-hour r a t e . F o r aickel-cadmiuma l k a l i n e s t a t i o n a r y b a t t e r i e s ) t h e 5-hour r a t e c a p a c i t y i s c o m m o n l y l i s t e d . T h e d i s c h a r g e c u r r e n t ( a m p e r a g e ) v a l u e o f a p a r t i c u l a r h o u r r a t e i s t h e b a t t e r y c a p a c i t y v a l u e d i v i d e d b y t h e h o u r 8 o f d i s c h a r g e . F o r t h e s a m e b a t t e r y , e a c h d i f f e r e n t h o u r r a t e w i l l h a v e a d i f f e r e n t c a p a c i t y v a l u e a s s o c i a t e d w i t h i t .
(b) O c c a s i o n a l l y , C - r a t e s m a y b e e n c o u n t e r e d . C - r a t e s a r e t h e d i s c h a r g e c u r r e n t v a l u e s e x p r e s s e d a s a f r a c t i o n o r m u l t i p l e o f t h e b a s e l i n e o r n o m i n a l c a p a c i t y o f t h e b a t t e r y . S o m e c o m m e r c i a l b a t t e r y s a l e s b r o c h u r e s a r e a m b i g u o u s i n t h i s respect) i n d i c a t i n g t h a t C - r a t e s a r e a n o t h e r w a y o f d e s c r i b i n g h o u r r a t e s . T h i s i s o n l y t r u e f o r t h e b a s e l i n e o r n o m i n a l r a t e . F o r a b a t t e r y i n vhich n o m i n a l c a p a c i t y (C) h a d b e e n d e t e r m i n e d a t t h e 8-hour r a t e , t h e d i s c h a r g e c u r r e n t v a l u e s f o r t h e 5-hour r a t e a n d C/5 r a t e w o u l d e a c h b e d i f f e r e n t v a l u e s , a s w o u l d t h e r e s u l t i n g c a p a c i t y v a l u e s . T h e d i s c h a r g e c u r r e n t f o r t h e 5-hour r a t e w o u l d b e s l i g h t l y l e s s t h a n t h e d i s c h a r g e c u r r e n t f o r t h e C / 5 r a t e . But s f o r t h i s p a r t i c u l a r b a t t e r y , t h e d i s c h a r g e c u r r e n t v a l u e s a n d r e s u l t i n g c a p a c i t y w o u l d b e t h e s a m e f o r t h e 8-hour r a t e a n d C/8 r a t e . F o r C-r8tes s t h e d i s c h a r g e c u r r e n t value) or amperage 3 i s t h e n o m i n a l ( o r b a s e l i n e ) c a p a c i t y m u l t i p l i e d b y t h e s t a t e d f r a c t i o n o r i n t e g e r .
(c) D i s c h a r g e r a t e s i n t e r m s o f c o n s t a n t p o w e r , o r W8ttS, m a y b e s p e c i f i e d m e a n i n g t h a t a s t h e b a t t e r y d i s - charges j t h e c u r r e n t i s i n c r e a s e d t o o f f s e t t h e d e c l i n e i n b a t t e r y v o l t a g e s u c h t h a t t h e p r o d u c t o f v o l t a g e m u l t i p l i e d b y
c u r r e n t i s m a i n t a i n e d a t t h e w a t t a g e s p e c i f i e d . A d e s c r i p t i v e d i s c h a r g e c u r r e n t c a p a b i l i t y r a t i n g i s a s t a t e m e n t o f t h e
Chap 2 P a r 9 Page 7
6g80.24A July 12, 1988
constant, continuous current (amperes) that a battery is designed to supply, but this rating is not always available in commercial sales brochures.
(d) - m rate low-rate, frequently encountered tkaa,’
and medium-rate are but they are relative indications, translating into amperes only when the basis for comparison is known. A 1 C or C/2 rate might be thought of as medium rate, 2 C or 3 C as being a high rate, and C14 or C/8 as a low rate, but no convention has been standardized. Changing discharge rates can result In a different oapacity value due to limitations on the rate of electrochemloal reactions at the plate surfaces, diffusion of fresh electrolyte to the plate aurfaoea,and changes
in battery Internal temperatures affecting Internal electrloal resistance. As the diaoharge rate increases, the capacity available tends to decrease.
(4) AAratinn indicates that a battery has been designed for use within a specific stated temperature range. An example would be a lead-acid battery designed for low (relative) temperature operation through use of electrolyte havfng higher speoifia gravity than that used In a battery designed for high temperature operation. Temperature rating is occasionally confused with rating temperature, rating temperature being the specific temperature at which a test is accomplished
(such as the 0 degree fahrenheit rating temperature for the automotive battery cold cranking test). As the temperature of a particular battery is increased, the available capacity tends to increase. To convert temperatures between degrees Centigrade and degrees Fahrenheit, see appendix 2.
Y CELLS Primary 0811s are not reohargeable. Primary iea ar8°00naumab18 in that they are exhausted by degrees as th8 chemioala whioh they contain react with one another to generate eleotrloity. When their chemical components will no longer generate eleatrlcity, they must be disposed of in an approved manner. Primary cells are available in many electrochemical combinations for appllaatlona ranging from carbon zinc flashlight cells to lithium-thlonyl ahloride cells for military US8, While true primary aella are not rechargeable, some commercially available primary aella can be recharged to varying degrees under preai8ely aontrolled aonditlons. Reaharging of primary aells is not recommended In FAA appllaations. Primary cells tend to have higher energy densities (or aapacities) and much better charge retention than 88aondary batteries.
11 SECONDaRYa Seaondary aella or storage batteries are a&lar to primary a811 batterie8 in their ability to produce electricity through the reaction of chemiaala with one another. The difference is that secondary cells aan also be completely recharged and discharged again. The repetition of discharging and recharging is called cycling. Secondary oella are available
Page 8’
July 12, 1988 6980.24A
i n n u m e r o u s e l e c t r o c h e m i c a l c o m b i n a t i o n s , a s a r e p r i m a r y c e l l s . However s o n l y l e a d - a c i d a n d n i c k e l - c a d m i u m - a l k a l i n e a r e n o r m a l l y u s e d i n F A A f a c i l i t i e s a n d e q u i p m e n t , d u e t o t h e i r r e l i a b i l i t y , a p p l i c a b i l i t y a n d l i f e c y c l e c o s t a d v a n t a g e . The FAA nomenclat u r e s f o r t h e t y p e s , c l a s s e s , a n d s t y l e s o f s e c o n d a r y c e l l s u s e d i s d e s c r i b e d i n t h e f o l l o w i n g p a r a g r a p h s , B a s i c a l l y , t y p e vi11 i n d i c a t e t h e b a t t e r y a p p l i c a t i o n , c l a s s w i l l i n d i c a t e b a t t e r y m a i n t a i n a b i l i t y , a n d s t y l e w i l l i n d i c a t e b a t t e r y p o s i t i o n s e n s i t i v i t y o r f r e e e l e c t r o l y t e . T h e typess c l a s s e s , a n d s t y l e s a r e f o r F A A purpo8es, and may not be the same as manufacturer's d e s i g n a t i o n s .
a . T y p e I . S t a t i o n a r y s t a n d - b y f l o a t ( f o r u n i n t e r r u p t i b l e p o w e r s u p p l i e s , s w i t c h g e a r , c o m m u n i c a t i o n s ) .
b 0 T y p e I I . S t a t i o n a r y e n g i n e g e n e r a t o r s t a r t i n g .
c . T y p e I I I . V e h i c l e s t a r t i n g a n d a u x i l i a r y p o w e r . ( S o m e t i m e s r e f e r r e d t o i n c o m m e r c i a l l i t e r a t u r e a 8 a u t o m o t i v e s t a r t i n g s l i g h t i n g s a n d i g n i t i o n b a t t e r i e s . )
d 0 Type IV. D e e p d i s c h a r g e c y c l e m o t i v e . ( F o r k l i f t t r u c k s , g o l f c a r t s s e t c .)
e . Type V. E m e r g e n c y l i g h t i n g , p o r t s b l e t e s t e q u i p m e n t .
f Type V I . Renevab le energy storage. ( U s e d with s o l a r c e l l , iindmills, e t c . )
8 0 C l a s s 1 . Regular maintenance.
h 0 Cla8s 2. Low maintenance.
i . C l a u s 3 . Sealed s no maintenance.
. J 0 S t y l e A . F r e e e l e c t r o l y t e , o r o r i e n t a t i o n o r a t t i t u d e neens it ive.
k 0 S t y l e B . N o n - s p i l l a b l e e l e c t r o l y t e a n d n o t o r i e n t a t i o n o r a t t i t u d e 8enritive ( N o t e : n o r m a l l y , S t y l e B i s a p p l i c a b l e o n l y t o Cl888 3 b a t t e r i e s . )
12 APPLICABILITY. E a c h o f t h e t y p e s , c l a s s e s , a n d s t y l e s l&ted ( u s i n g F A A n o m e n c l a t u r e ) i s n o r m a l l y d e s i g n e d a n d c o n - s t r u c t e d w i t h distingui8hing p e r f o r m a n c e char8cteriatics a n d festures m o s t s u i t a b l e f o r p a r t i c u l a r use8. I n m o s t applicat ions a s e v e r a l or 811 b s t t e r y types c o u l d b e used 8 8 cy, s i n c e a l l c a n s u p p l y p o w e r . But the use o f a b s t t e r y t y p e o u t s i d e i t s d e s i g n a p p l i c a t i o n d o e s n o t t a k e f u l l a d v a n t a g e o f i t s p a r t i c u l a r p e r f o r m a n c e c h a r a c t e r i s t i c 8 o r f e a t u r e s a n d w i l l p r o b a b l y r e s u l t i n r e d u c e d c a p a b i l i t y . F o r i n s t a n c e , T y p e I I I
8n exped ien-
Chap 2 Par 11 Page 9
6g80.24A July 12, 1988
vehlole starting and auxiliary power (automotive) batterlea will
fumtion in atatlonary atandbp float applicationa, but may experience shortened life when frequently deep-discharged. And the use of automotive-type batterlea for emergency (stationary standby) systems ia- apeoifioally prohibited by the National Electrio Code of 1987 (Artlale 700-12(a)). In order to determine the appropriate type, claaa, and style for a battery, thorough aonslderation of the partiaular appliaatlon is necessary.
a. Stationarv. zstagdbv float (Type I) batteries should be used in stationary applications to provide emergency or backup power when the primary power (normally aommercial eleatrlc line) falls. The equipment that theae (Type I) batterlea will power normally aonalata of uninterruptible power supplies, awltah gear, such aa relaya, and oommunlaation reaeivers and transmittera.
(1) Piat- charaateristloa of the Type I battery appliaation are stationary operation, aontinuoua battery charging (float operation) when primary power la available, long duration (houra) diaaharging at low to moderate rate8 (although some applications involve complete disaharging at high current in as few aa ten minutea or momentary loada with high aurgea) and moderate to high capaaity in term8 of ampere-houra. Battery ayatem voltage8 typiaally range from 12 volts (or lower) to more than 500 volta.
(2) The tvDica1 envuonmee of a Type I battery fs normally indoors at moderate humidity, with a moderately narrow temperature rage, and free of vibration, shoak, and acaelera- Hon. When the Type I battery ia installed In a battery box located out-of doors, provfalona ahould be Incorporated to minimize temperature extremea, or a higher aapaaity battery may be required. The Type I battery ia normally installed inaide equipment or in racka bolted to the floor near the equipment.
(3) In US-, the installation la typically permanent for the life of the battwy. A Type I bgttery normally experientea infrequent (one or lear per month) diaahargea to varying deptha (100 peraent or leira). The Type I battery la maintained at full state of charge, ready for we aondltlon, by float charging from a aon8tant voltage source. Reahargea after diachargea are normally completed within from 2 to 24 houra.
(4) Due to the normav l@ruQ aizea, manufacturer8 supply the Type I battery aa individual 0811s or cell paaka (2 or more cell8 in the same aaaeably) for assembling into a complete battery at the Installation site.
(5) M&acturera’ deautionp for stationary, standby float (Type I) batteries will vary. One manufaaturer may list a battery aacording to a particular intended use auah as
July 12, 1988 6980.24A
svitchgesr 3 w h i l e a n o t h e r m a y l i s t a b a t t e r y w i t h a l m o s t t h e s a m e p e r f o r m a n c e c h a r a c t e r i s t i c s a s high r a t e / s h o r t d u r a t i o n o r a8 h i g h p e r f o r m a n c e . O r , a m a n u f a c t u r e r m a y l i s t t h e s a m e b a t t e r y p a r t n u m b e r u n d e r s e v e r a l d i f f e r e n t a p p l i c a t i o n s . The intended u s e a n d b a t t e r y p e r f o r m a n c e r e q u i r e m e n t s s h o u l d b e d e s c r i b e d a s a c c u r a t e l y a s p o s s i b l e i n o r d e r t o a s s i s t t e c h n i c a l p e r s o n n e l i n s e l e c t i n g vhich b a t t e r i e s w i l l give t h e r e q u i r e d p e r f o r m a n c e a n d t o a l l o v e f f e c t i v e r e v i e w o f b a t t e r y p r o p o s a l s r e c e i v e d i n respon8e t o s o l i c i t a t i o n . C l a s s a n d s t y l e a r e o p t i o n a l , d e p e n d - i n g u p o n t h e n e e d s o f t h e p a r t i c u l a r a p p l i c a t i o n , F A A p o l i c y , a n d c o m m e r c i a l a v a i l a b i l i t y . However, T y p e I b a t t e r i e s a r e t y p i c a l l y Class 1 o r C l a s s 2 , a n d S t y l e A .
b S t a t i o n a r y e n g i n e g e n e r a t o r s t a r t i n g ( T y p e I I ) b a t t e r i e s should’be u s e d f o r s t a r t i n g b o t h g a s o l i n e a n d d i e s e l , s t a t i o n a r y i n t e r n a l c o m b u s t i o n ( r e c i p r o c a t i n g ) e n g i n e s t h a t p o v e r e l e c t r i c generator8 e
(1) Distinnuishinn c h a r a c t e r i s t i c s o f t h e T y p e I I b a t t e r y a p p l i c a t i o n a r e s t a t i o n a r y o p e r a t i o n , d a i l y b o o s t
c h a r g i n g c o n t r o l l e d b y a t i m e r a n d t e m p e r a t u r e v o l t a g e r e l a y w i t h e q u a l i z e c h a r g i n g c a p a b i l i t y , a n d h i g h c u r r e n t s t a r t e r m o t o r d i s c h a r g e l o a d s l a s t i n g u p t o o n e m i n u t e . Battery system v o l t a g e s a r e n o r m a l l y 3 2 v o l t s .
(2) T h e e n v i r o n m e n t o f a T y p e I I b a t t e r y m a y b e i n s t a l l e d o u t d o o r s i n a v e l l v e n t i l a t e d c o v e r e d b o x o r i n d o o r s i n r a c k s n e a r t h e e n g i n e g e n e r a t o r . W h e n l o c a t e d o u t d o o r s , t h e b a t t e r y vi11 b e s u b j e c t e d t o a w i d e t e m p e r a t u r e a n d h u m i d i t y
r a n g e d e p e n d e n t o n t h e l o c a l c l i m a t e .
(3) I n usage,t h e T y p e I I b a t t e r y m a y e x p e r i e n c e 1 o r 2 e n g i n e s t a r t s p e r m o n t h . T h e d i s c h a r g e s a r e a t h i g h c u r r e n t , b u t n o r m a l l y l a s t o n l y 2 - 5 s e c o n d s . R e q u i r e m e n t s f o r 30 s e c o n d o r 6 0 s e c o n d e n g i n e c r a n k i n g c a p a b i l i t y a r e d e m o n s t r a t e d b y p e r i o d i c t e s t i n g . T h e T y p e I I b a t t e r y i s m a i n t a i n e d f u l l y c h a r g e d b y b o o s t c h a r g i n g o n a d a i l y b a s i s , w i t h e q u a l i z e charging when needed.
(4) D u e t o r e s e r v e d t i m e f o r e n g i n e t e s t i n g , p o s s i b l e f r e q u e n t r e s t a r t s a n d a d v e r s e t e m p e r a t u r e e x t r e m e s , t h e T y p e I I b a t t e r i e s a r e l a r g e . A d d i t i o n a l l y , t h e s e b a t t e r y c e l l s e m p l o y l a r g e n u m b e r s o f p l a t e s t o o b t a i n h i g h t o t a l p l a t e s u r f a c e a r e a s f o r h i g h r a t e s , l i m i t a t i o n s o n t h e p h y s i c a l h e i g h t o f t h e c e l l s t o r e d u c e e l e c t r o l y t e s t r a t i f i c a t i o n problema, g e n e r a l l y h e a v i e r g r i d s a n d s t r a p s t o r e d u c e i n t e r n a l r e s i s t a n c e a n d r e s i s t c o r r o s i o n S a n d w r a p p i n g o f t h e p o s i t i v e p l a t e s t o p r e v e n t
s h e d d i n g o f a c t i v e m a t e r i a l .
(5) I n p r a c t i c e , T y p e I I b a t t e r i e s a r e g e n e r a l l y t h e l e a d - a c i d t y p e , d u e t o t h e l o v e r i n i t i a l c o s t a s c o m p a r e d t o n i c k e l - c a d m i u m - a l k a l i n e b a t t e r i e s , numerou8 c o m m e r c i a l 8ource8,
Chap 2 Par 12 Page 11
6980.24A July 12, 1988
a n d f a m i l i a r i t y . T y p i c a l l y , f o u r (4) c e l l b a t t e r i e s a r e u s e d i n FAA s y s t e m s . C l a s s a n d s t y l e a r e n o r m a l l y C l a s s 1 , S t y l e A .
c . V e h i c l e s t a r t i n g a n d a u x i l i a r y p o w e r ( T y p e I I I ) b a t - t e r i e s a r e sometimes. r e f e r r e d t o i n l i t e r a t u r e a s a u t o m o t i v e s t a r t i n g a l i g h t i n g a n d i g n i t i o n b a t t e r i e s , o r s i m p l y c a r b a t - teries. U n d e r t h i s ( T y p e III) g r o u p i n g a r e i n c l u d e d r e c r e a t i o n a l v e h i c l e (RV) b a t t e r i e s , a n d m a r i n e b a t t e r i e s . Farm machinery b a t t e r i e s s l a w n t r a c t o r b a t t e r i e s , m o t o r c y c l e b a t t e r i e s , a n d c o n s t r u c t i o n a n d i n d u s t r i a l m a c h i n e r y b a t t e r i e s a r e a l s o
i n c l u d e d . T y p e I I I b a t t e r i e s should b e u s e d f o r t h e s e a p p l i c a - t i o n s .
( 1 ) D i s t i n g u i s h i n g characteri8tics o f t h e T y p e I I I b a t t e r y a p p l i c a t i o n s a r e t h e i r u s e t o p r o v i d e e l e c t r i c p o w e r t o e n g i n e s t a r t i n g m o t o r s i n m o b i l e e q u i p m e n t a n d v e h i c l e s a n d t o p r o v i d e a u x i l i a r y e l e c t r i c p o w e r t o t h e s e v e h i c l e s a n d e q u i p - ment. T h e S o c i e t y o f A u t o m o t i v e E n g i n e e r s S t a n d a r d S A E - J 5 3 7 , w h i c h s t a n d a r d i z e s t h e s e b a t t e r i e s , a d d s t h e r e q u i r e m e n t t h a t t h e e q u i p m e n t a n d v e h i c l e s b e e q u i p p e d w i t h r e g u l a t e d b a t t e r y c h a r g i n g s y s t e m s . T h e b a t t e r y v o l t a g e i s c o m m o n l y 1 2 v o l t s , a l t h o u g h 8ome b a t t e r i e s a r e a v a i l a b l e i n o t h e r v o l t a g e s .
(2) T h e e n v i r o n m e n t o f a T y p e I I I b a t t e r y i s a n i n s t a l l a t i o n i n a b a t t e r y b o x , c o m p a r t m e n t , o r s p a c e i n o r n e a r t h e e n g i n e c o m p a r t m e n t o f t h e v e h i c l e o r e q u i p m e n t . T h e b a t t e r y w i l l b e s u b j e c t e d t o t h e w i d e s t t e m p e r a t u r e r a n g e o f a l l t y p e s . T h e t e m p e r a t u r e r a n g e i s d e p e n d e n t u p o n t h e l o c a l c l i m a t e a n d u p o n t h e u p p e r a m b i e n t 8 r e a c h e d i n o r n e a r t h e e n g i n e c o m p a r t - ment. T h e b a t t e r y w i l l b e e x p o s e d t o h u m i d i t y l e v e l s t o 1 0 0 percents i n c l u d i n g c o n d e n s a t i o n d u e t o t e m p e r a t u r e c h a n g e s . T h e b a t t e r y w i l l a l s o b e s u b j e c t e d t o v i b r a t i o n a n d l o w l e v e l s o f m e c h a n i c a l s h o c k a n d a c c e l e r a t i o n .
( 3 ) I n usaRe, t h e b a t t e r y m a y e x p e r i e n c e v a r y i n g demands s r a n g i n g f r o m s e v e r a l e n g i n e c r a n k i n g d i s c h a r g e s p e r d a y t o v e r y f e w d i s c h a r g e s p e r m o n t h , d e p e n d i n g o n t h e v e h i c l e o r equipment usage. M o s t e n g i n e s t a r t s o c c u r within 5 s e c o n d s o r less a b u t l o n g e r d u r a t i o n s o r s e v e r a l a t t e m p t 8 m a y b e n e c e s s a r y i n some instanceah T h e b a t t e r y i s r e c h a r g e d i m m e d i a t e l y a f t e r s t a r t i n g u8e ( u n l e s s t h e e q u i p m e n t h a s m a l f u n c t i o n e d ) . It may a l s o p r o v i d e a u x i l i a r y power t o l i g h t s , r a d i o s , o r a c c e s s o r i e s when the engine is not running. B e c a u s e o f t h e e x t r e m e c o n d i - tions and demands, a s w e l l a s t h i n n e r p l a t e c o n s t r u c t i o n , t h e s e b a t t e r i e s t e n d t o s h o r t e r l i f e t i m e s .
(4) B e c a u s e t h e s e (TyDe I I I ) b a t t e r i e s a r e f o r u8e i n m o b i l e a p p l i c a t i o n s a n d d o n ’ t n o r m a l l y r e q u i r e h i g h ( r e l a t i v e )
c a p a c i t y , t h e y t e n d t o b e p o r t a b l e b y o n e p e r s o n . They are m o d e r a t e i n p h y s i c a l s i t e a n d a r e d e s i g n e d w i t h l a r g e c e l l p l a t e
s u r f a c e a r e a s t o p r o v i d e h i g h c r a n k i n g c u r r e n t . RV and some m a r i n e b a t t e r i e s ( c o m m e r c i a l d e s i g n a t i o n s ) t e n d t o h a v e a l o v e r
July 12, 1988 6980.24A
d i s c h a r g e r a t e c a p a b i l i t y - - i n t e n d e d m o r e f o r l i g h t i n g o r a u x i l i a r y p o w e r - - and g r e a t e r t o l e r a n c e o f d i s c h a r g e t o d e e p e r l e v e l s w i t h s o m e d e l a y b e f o r e r e c h a r g i n g t h r o u g h u s e o f t h i c k e r c e l l p l a t e s o r h e a v i e r p l a t e g r i d s . R V o r m a r i n e b a t t e r i e s m a y b e c o n n e c t e d i n p a r a l l e l t o p r o v i d e h i g h e r s t a r t i n g c u r r e n t c a p a b i l i t y . ’
(5) I n p r a c t i c e , T y p e I I I b a t t e r i e s a r e g e n e r a l l y o f t h e l e a d - a c i d t y p e , d u e t o l o w c o s t , n u m e r o u s c o m m e r c i a l s o u r c e s , a n d f a m i l i a r i t y . In a i r c r a f t a p p l i c a t i o n s h o w e v e r , t h e v e i g h t c o m p a r i s o n a n d e x t r e m e l y h i g h s t a r t i n g c u r r e n t n e e d s u s u a l l y r e s u l t i n t h e s e l e c t i o n o f n i c k e l - c a d m i u m - a l k a l i n e b a t t e r i e s . S A E S t a n d a r d 3 5 3 7 s h o u l d b e c o n s u l t e d f o r s t a n d a r d s i z e s a n d t e r m i n a l c o n n e c t i o n s o f T y p e I I I b a t t e r i e s . C l a s s a n d s t y l e a r e o p t i o n a l (meet n e w c a r b a t t e r i e s a r e c u r r e n t l y C l a n s 2 o r C l a s s 3 , a n d S t y l e A), d e p e n d i n g o n t h e p a r t i c u l a r a p p l i c a t i o n needs a F A A p o l i c y , a n d c o m m e r c i a l a v a i l a b i l i t y .
d D e e p d i s c h a r g e c y c l e m o t i v e ( T y p e I V ) b a t t e r i e s s h o u l d b e u s e d i n v e h i c l e s r e q u i r i n g b a t t e r i e s f o r m o t i v e p o w e r . These v e h i c l e s i n c l u d e i n d u s t r i a l e l e c t r i c f o r k l i f t t r u c k s a n d transporter8) g o l f c a r t s , a n d e l e c t r i c v e h i c l e s .
(1) Distinnniehing c h a r a c t e r i s t i c s o f t h e T y p e I V b a t t e r y a p p l i c a t i o n a r e v a r y i n g d i s c h a r g e l o a d s a n d e x t e n d e d
p e r i o d s ( d a y s o r w e e k s ) i n a p a r t i a l l y d i s c h a r g e d s t a t e . B a t t e r y s y s t e m v o l t a g e 8 w i l l b e f r o m 6 t o 4 8 v o l t s ( o r h i g h e r f o r s o m e e l e c t r i c v e h i c l e s ) .
(2) T h e e n v i r o n m e n t o f a T y p e I V b a t t e r y w i l l d e p e n d u p o n t h e a p p l i c a t i o n - i t m a y b e i n d o o r s i n a f a c t o r y r e s u l t i n g
i n a r e l a t i v e l y n a r r o w t e m p e r a t u r e r a n g e o r o u t - o f - d o o r s w i t h t h e t e m p e r a t u r e r a n g e d e t e r m i n e d b y l o c a l c l i m a t e . T h e b a t t e r y w i l l b e s u b jetted t o m i n o r (lov) l e v e l s o f v i b r a t i o n , s h o c k , a n d
a c c e l e r a t i o n .
(3) I n usage,t h e b a t t e r y w i l l b e s u b j e c t e d t o m o d e r a t e d i s c h a r g e r a t e s w i t h s h o r t d u r a t i o n h i g h r a t e d e m a n d s . T h e b a t t e r y m a y e x p e r i e n c e c o m p l e t e d i s c h a r g e i n o n e d a y , p o s s i b l y t o s u c h d e p t h t h a t t h e v e h i c l e b e c o m e s i m m o b i l e . O r , t h e b a t t e r y m a y b e d i s c h a r g e d a small p e r c e n t a g e o f t o t a l c a p a c i t y e a c h d a y f o r s e v e r a l d a y s o r w e e k s r e s u l t i n g i n e x t e n d e d p e r i o d 8 i n a s t a t e o f p a r t i a l d i s c h a r g e .
(4) Type I V b a t t e r i e s t e n d t o b e l a r g e , a p p r o a c h i n g l i m i t 8 d i c t a t e d b y e q u i p m e n t m o b i l i t y , i n o r d e r t o p r o v i d e h i g h c a p a c i t y a n d h i g h p o w e r l e v e l s . T h e e x t e n d e d p e r i o d s o f p a r t i a l d i s c h a r g e a n d p o s s i b l e d e e p d i s c h a r g i n g m a k e t h e a n t i m o n y a l l o y g r i d s m o r e s u i t a b l e i n T y p e I V b a t t e r i e s , a l t h o u g h c a l c i u m a l l o y 8 m a y r e s u l t i n b e t t e r c h a r g e r e t e n t i o n d u r i n g l o n g s t a n d t i m e s .
. Chap 2
P a r 12 Page 13
6980.24A July 12, 1988
(5) xn wactioQ, Type IV batteries tend to be of the lead-aoid type, due to the large capaoitlea and lower initial oo8t 0 They al8o require more frequent equalize charging due to long 8tand time8 and deep diboharging. Higher water consumption re8ult8 because of equalize oharging. The Society of Automotive Engineer8 ha8 establi8hed Aero8pace Recommended Practice ARP 1817 to de8cribe industrial, lead-acid batteries for use in electric powered ground support equipment, offering a 8pecifioatlon-type of battery description which may be useful when reviewing manufacturer8 literature. Class and 8tyle are normally Cla88 1, Style A.
8. ~nera~cv 1lRhtiw or Dortablg test equipment batteries (Type V) are used to provide eleotrio power to building light8 that operate when oommercial power fails or to operate portable test equipment. Emergency lighting in building8 18 required by building oode8 to illuminate exit ways and exit8 for oooupant8. Some portable t88t equipment require8 electrio power for operation and an internally in8tall8d power 8ource may be most suitable.
(1) JliatlnnuiahLpn a~aracteriatlc~ of the Type V battery applioation are relatively low and 8teady discharge - current8 with recharging when ooamer~ial power is available. They are maintained In a full 8tate-of-c!harge by float oharglng between u888. Beoauae of the low power and bhort duration di8oharg88 required, or portability n8ed8, they tend to be small in aize.
(2) The enrlroppaent of a Type V battery 18 typically that for an indoor8 area ocoupied by personnel. Portable t88t equipment might experienoe Intermittent we out-of-doors, but environment extreme8 would be limited by the equipment operating capability. Most portable test equipment would, how8ver, require a battery with all-position oapabllity. And 8om8 portable te8t equipment would experience low level mechanical shook.
(3) wuaans, the Type V battery in8talled in emergency lighting systems will erperlenoe ea8entlally the same operation aa the Type I stationary battery, di8oharging when primary power f8118. Portable t88t equipment batterie8 would probably be u88d more often. Becau88 the Type V batterie8 power equipment and lighting that may not have voltage autoff protection, Type V batter188 are more likely to erperienoe deep di8charging, continuing until the equipment fall8 to provide required performance and bometiaes until the battery voltage r8aOh88 zero. Energenoy lighting in exit waya may be required . for only a few minutes which would result in a high rate battery discharge (15 minute8 would b8 a 4 C rate). MO8t portable t88t equipment applioationa would b8 at a muoh lower rate. Type v battery dlacharge current8 muat be accurately described.
July 12, 1988 6g80.24A
(4) D to the normally low total watt-hour (low total power or short duration discharge) needs of emergency lighting
systems and portability requirements for portable test equipment, Type V batteries tend to be small in physical size. Some stationary emergency lighting systems may use small Type I stationary batteries, provided that the equipment has discharge voltage cutoff protection. Emergency lighting batteries should generally be Class 2 or Class 3, requiring low or no maintenance and may be Style A (unless all-position capability will be required) or Style B. Portable test equipment batteries must be Class 3, Style B, to allow for the possibility of all position operation.
(5) Jn vactice, Type V batteries are commercially available in both lead-acid and nickel-cadmium-alkaline electrochemistries. The selection of electrochemistry may be dictated by initial cost, sizes available, life cycle cost analysis, area chemical compatibilities, or keeping the same part number when making replacements. Suitable batteries are usually available from numerous sources. (When desirable to operate without charging capability, primary batteries might be considered due to their long stand time capability and higher energy density
(capacity) .) Numerous emergency lighting systems currently use low - or no - maintenance cells (Class 2 or Class 3). Portable test equipment tends to use Class 3, Style B nickel-cadmiumalkaline batteries (installed as cells) when the required capacity is relatively small and the battery is installed inside the equipment. When the battery is carried along with the equipment, but not mounted on or in the equipment, Class 3, Style B lead-acid batteries tend to be used (except in hospital equipment, which usually employs nickel-cadmium-alkaline batteries).
f Renewable enerav storage batteries (Type VI) are used for electrical energy storage with solar cells, wind-driven generators, or other renewable energy sources. These systems may be used in locations where access is limited or in remote areas away from commercial power sources. As Type VI batteries are categorized based on the use of renewable energy sources for charging, they can be applied in almost any system where sufficient renewable energy (wind, solar, geothermal, etc.) is available, along with adequate energy conversion and charging devices.
(1) Pistinnuishina characteristics of the Type VI battery application are normally a daily cycle routine of discharge while the renewable energy source is unavailable and recharge when the renewable energy source becomes available. These applications normally use a battery of sufficient capacity
Chap 2 Par 12 Page 15
6980.24A July 12, 1988
to operate the system for more than one day (cycle) - up to 4 or 5 days in some cases - without significant recharge, in order to allow for the possible unavailability of the renewable energy source.
(2) The environment of a Type VI battery is typically that of a covered battery box, equipment compartment, or other shelter which has no ambient conditioning (heating or cooling) other than venting to the ambient air outside the facility. The temperature range will be determined by the local climate and insulating performance of the installation. The environment of a typical application will be free of vibration, shock, and acceleration. Humidity levels may reach 100 percent, including condensation due to temperature changes.
(3) Jn usaRe, the Type VI may not be fully recharged after each discharge period. However, the charging system should be capable of eventually returning the battery to a state of full charge for more than half of the battery lifetime. Discharge rates will vary according to the application. Discharge capacities will be determined by the individual cycle needs and the desired amount of reserve capacity for extra cycles without signif icant recharge, as well as battery charger capability.
(4) Due to possiblv limited accessibility of the intended installation, these (Type VI) batteries may or may not require portability considerations for physical size and style
(Style B versus Style A). Also, accessibility may limit maintenance visits, requiring Class 2 or Class 3 (low or no maintenance).
(5) In practice, Type VI batteries are available from several manufacturers, sometimes under the description of photovoltaic or solar batteries. Battery use in renewable energy storage applications requires thorough consideration of charging capabilities, availability of the renewable energy, and the needs for assurance of availability of equipment operating power, in addition to discharge loading.
13 l LEAD-ACID.
a. Theory and Chemistrv The lead-acid battery consist of positive and negative electrod& which are separated from each other, sequenced in pairs, and immersed in an electrolyte solution of sulfuric acid. In the fully-charged condition, the active material of the positive electrode is lead dioxide (Pb02), and the active material of the negative electrode is lead (Pb). As the cell is being discharged, the lead dioxide of the positive electrodes, and the lead of the negative electrodes is converted to lead sulfate utilizing the sulfuric acid electrolyte by the following reaction:
July 12, 1988 6980.24A
Charned C o n d i t i o n D i s c h a r g e d C o n d i t i o n
Pb02 + Pb + 2 H2S04
2 PbS04 + 2 H20
2 PbS04 + 2 H20
T h a t i s , l e a d , l e a d d i o x i d e , a n d s u l f u r i c a c i d a r e c o n s u m e d , a n d l e a d s u l f a t e a n d w a t e r p r o d u c e d . During the process, the e l e c t r o d e 8 r e m a i n i n s o l u b l e : l e a d , l e a d d i o x i d e , a n d l e a d s u l f a t e a r e r e l a t i v e l y i n s o l u b l e i n t h e s u l f u r i c a c i d . B a t t e r y c a p a c i t y i s d e p e n d e n t u p o n t h e a m o u n t a c t i v e m a t e r i a l s i n t h e p o s i t i v e a n d n e g a t i v e p l a t e s , t h e q u a n t i t y a n d c o n c e n t r a t i o n o f t h e e l e c t r o l y t e , a n d t h e d i f f u s i o n r a t e o f t h e e l e c t r o l y t e t h r o u g h t h e s e p a r a t i n g m a t e r i a l s . T h e c o n d u c t i v i t y o f t h e a c t i v e material8 s the supporting network s a n d p l a t e s t r a p s a l s o e n t e r i n t o t h e d i s c h a r g e c h a r a c t e r i s t its.
b T h e L e a d - A c i d S y s t e m I s R e v e r s i b l e . When current is f o r c e d ’ t h r o u g h t h e c e l l i n t h e o p p o s i t e d i r e c t i o n o f c u r r e n t f l o w d u r i n g dischqrge, c h e m i c a l r e a c t i o n s c o n v e r t t h e d i s c h a r g e d m a t e r i a l s ( l e a d s u l f a t e a n d w a t e r ) t o l e a d d i o x i d e a n d l e a d , a n d
r e l e a s e s u l f u r i c a c i d i n t o s o l u t i o n . A s i n g l e d i s c h a r g e f o l l o w e d b y a c h a r g e i s d e f i n e d a s a c y c l e . A f t e r a n u m b e r o f cyclee, a c e l l w i l l f a i l t o d e l i v e r i t s r a t e d c a p a c i t y b e c a u s e o f c e r t a i n
i r r e v e r s i b l e c h a n g e s t h a t o c c u r d u r i n g c y c l i n g . T h e t y p e s o f c h a n g e s , a n d c o n s e q u e n t l y c y c l e l i f e s v a r i e s a m o n g t h e d i f f e r e n t l e a d - a c i d s y s t e m s , a n d a r e s e n s i t i v e t o s u c h p a r a m e t e r s a s d e p t h o f d i s c h a r g e , d e g r e e o f o v e r c h a r g e , c h a r g e r a t e , e n v i r o n m e n t d u r i n g s e r v i c e , e l e c t r o d e c o n s t r u c t i o n , a n d s e p a r a t o r m a t e r i a l s .
c . C a p a c i t y R a t i n g s . O n e mea8ure o f c a p a c i t y i s ampereh o u r s a n d i s m e a s u r e d b y m u l t i p l y i n g t h e c u r r e n t d r a i n t i m e s t h e d u r a t i o n o f t h e c u r r e n t d r a i n . T h e A m p e r e - h o u r r a t i n g o f a leada c i d s t a t i o n a r y b a t t e r y i s b a s e d o n a n 8 - h o u r d i s c h a r g e p e r i o d t o a n e n d v o l t a g e o f 1 . 7 5 V / c . T h e a m p e r e - h o u r r a t i n g o f a b a t t e r y w i l l d e c r e a s e a s t h e d i s c h a r g e d r a t e i s i n c r e a s e d . T h e r a t i n g s l i s t e d f o r s p e c i f i c m o d e l b a t t e r i e s a r e u s u a l l y b a s e d o n a s p e c i f i c g r a v i t y o f 1 . 2 1 0 o r 1 .
2 1 5 a l t h o u g h f o r s p e c i f i c a p p l i c a - t i o n s ( e . g . , p h o t o v o l t a i c ) a n d o t h e r t y p e o f b a t t e r y c o n s t r u c t i o n a m o r e c o n c e n t r a t e d ( h i g h e r s p e c i f i c g r a v i t y ) e l e c t r o l y t e m a y b e used l F o r a s p e c i f i c a p p l i c a t i o n s u c h a8 l o w o r h i g h t e m p e r a t u r e environment8 a t h e n o r m a l s p e c i f i c g r a v i t y e l e c t r o l y t e o f a s t a n d a r d b a t t e r y c a n b e r e p l a c e d w i t h e l e c t r o l y t e o f h i g h e r o r l o v e r ( r e s p e c t i v e l y ) s p e c i f i c g r a v i t y w h i c h w i l l c h a n g e t h e p e r f o r m a n c e c h a r a c t e r i s t its f r o m t h a t g i v e n f o r t h e b a t t e r y w i t h t h e n o r m a l s p e c i f i c g r a v i t y . E n g i n e s t a r t i n g b a t t e r i e s a r e r a t e d in c o l d c r a n k i n g a m p s a n d r e s e r v e c a p a c i t y .
C o l d c r a n k i n g a m p e r e s i s t h e n u m b e r o f a m p e r e s a b a t t e r y w i l l d e l i v e r a t 0 d e g r e e f a h r e n h e i t f o r 30 s e c o n d 8 t o a v o l t a g e o f 1 . 2 v o l t s p e r c e l l . T h e r e s e r v e c a p a c i t y i s t h e n u m b e r o f m i n u t e s a b a t t e r y w i l l p r o v i d e 2 5 a m p e r e s t o a n e n d v o l t a g e o f 1 . 7 5 v o l t s p e r c e l l .
Chap 2 Par 13 Page 17
6g80.24A July 12, 1988
(1) mnDerature Effecta 0 Lead-acid batteries are Sensitive to t8mp8ratUr8S above and below the normal room temperature of 77 d8gr88 iahreaheit as listed in table 2-1 and the following paragraphs:
(a) mh temPeratUr8 shortens the life due to accelerated corrosion and deterioration of the plates and separators by the electrolyte. Constant ambient temperatures of 15 degree fahrenheit or more above 77 degree fahrenheit will typically cut the life in half. This affect can b8 partially compensated for by reducing the specific gravity (activity) of the 818CtrOlyt8.
(b) bow temeratura will reduce the available Capacity of the battery. Dropping from the normal of '17 degree fahr8nh8it to 40 degree fahrenheit will give approximat8ly 3/9 the rated oapacity. As the battery is discharged, the 818CtrOlyt8 specific gravity i8 reduced, thereby raising it8 freezing point and susceptibility of the battery to permanent damage. A dimharged stationary battery could freeze at a temperature as high as +I6 degree8 fahrenheit constant ambient temperature.
(2) Ratea. The magnitude of the discharge current affects th8 total quantity of ampere hour8 that the battery can deliver before the battery voltage deereas to the cutoff value. Rate capability depend8 basically upon the total plate surfaoe area for each plate polarity. th8 plate 8urfaoe area d8termin8s plate ourrent density for any given di8oharg8 ourrent. High-rate 0811s have more and thinner plater, than lowrat8 ~811 of the same physical 8128. A8 the discharge rat8 inCr8a888 s the capacity available from any particular ~811 deCr8a888. additional factors affecting battery capability are the eleotrlcal resistance of Internal conductor8, cell design
L ABLE 2-l LEAD-ACID B ATTERY CAPACITY CS TEMPERATURE
L ABLE 2-l LEAD-ACID B ATTERY CAPACITY CS TEMPERATURE
Electrolyte
Temperature
Percent Capacity and Discharge Rate
“F 8 Hour 1 Minute
110 110 117 90 105 108 77 100 100 60 90 88 40 77 73 20 62 58 10 54 49
July 12, 1988
geometry and construction, and chemical concentrations. Because of the many variables affecting rate, a single precise description of rate effects on capacity cannot be developed for application to all lead-acid batteries. Table 2-2 provides an example of rate effects on the capacity of a particular lead acid battery.
d l Charainq.
(1) Float Charge. A fully charged battery will gradually lose some of its charge due to internal losses (termed self-discharge). Proper float charging supplies enough electric energy to over come these internal losses without causing significant gas evolution. Float voltage is higher than the open circuit cell voltage (see table 2-3).
(2) Eaualize Charging Equalize charging assures completion of recharge, eliminating cell voltage imbalances and electrolyte stratification. The schedule for periodic equalizing charges will be determined by the cell type and operating conditions (e.g., frequency and depth of discharges). Equalize charging may be necessary as often as monthly. And some batteries, such as low-maintenance (Class 2) and no-maintenance (Class 3) sh ould never need equalizing (and may be damaged by heavy equalize charging). The antimony type lead-acid battery may require more frequent equalizing charges. The antimony battery will provide greater cycle life than the calcium battery. when used for deep discharge cycling but at the penalty of more
frequent equalize charges and higher water usage because of the equalize charging. Antimony does not retain its charge as well as does the calcium, due to higher self discharge losses. Equalize charging, while necessary in certain situations, must be
TABLE 2-2 EXAMPLE OF LEAD-ACID LOW RATE STATIONARY
TABLE 2-2 EXAMPLE OF LEAD-ACID LOW RATE STATIONARY
BATTERY CAPACITY' VERSUS RATE
DISCHARGE RATE PERCENT CAPACITY
c / 4 6 c/18 c/10 C/8 c / 6 c / 5 c/4 c/3 c/2
1c
157% 139% 114% 100% 86% 79% 71% 52% 26% 1%
'NOTE: Capacity to cutoff voltage of 1.75 volts per cell, 77'F ambient, C is the capacity at the 8-hour rate.
DISCHARGE RATE PERCENT CAPACITY
Chap 2 Par 13 Page 19
6980.248 July 12, 1988
carefully controlled to prevent battery damage due to water loss, increased grid corrosion, plate warpage (from too great of current), or excessive temperature. Along with hydrogen and oxygen evolved during overcharge of lead-acid batteries, stibine or arsine gases may be present. Stibine (SbH3) is a poisonous gas resulting from any antimony present within the cell. Arsine, also a poisonous gas, results from the presence of arsenic in the lead plates. Stibine and arsine are removed with the other evolved gasses by proper facility ventilation. Equalize charging is indicated when the batteries are fully charged and:
(a) The temperature-corrected specific gravity of the pilot cell of a floating battery has dropped more than 10 points (e.g., from 1.215 to 1.205) below its full charge reading.
(b) When the voltage of a cell on float is more than 0.05 volts below the average of the cells in the battery.
l
e; Service Lif e . Exact discharge/recharge cycle life of cells is difficult to predict due to the effect of varying charge/discharge conditions (depth, rates, frequency of use) on cycle life, Batteries consistently over charged will experience a shortened life due to grid corrosion, over activity of the electrolyte from the increased temperature and voltages, and an increase in electrolyte concentration from water being driven off of the electrolyte. High current rates will also cause the plates to expand and contract and shed active material. Batteries not completely recharged will suffer the same problems as a battery allowed to stand discharged, resulting in a potentially permanent sulfation of the battery plates. Shock and vibration are harmful to the soft lead materials in a lead-acid battery,
TABLE 2-3, LEAD-ACID BATTERY CHARGE VOLTAGE
TABLE 2-3, LEAD-ACID BATTERY CHARGE VOLTAGE
LEAD-ACID FLOAT EQUALIZE BATTERY TYPES VOLTAGES VOLTAGE
Lead Antimony 2.19VK 2.3OWC
Lead Calcium 2.26v/c 2,34V/C
Automobile
Maintenance-Free 2.245V/C 2.395v/c Ordinary 2.OlOV/C 2.2gv/c
Gelled Electrolyte 2.275V/C N/A
1
July 12, 1988 6980.248
LEAD-ACID FLOAT EQUALIZE BATTERY TYPES VOLTAGES VOLTAGE
causing loss of active materials from plates and structural damage. Cracks in the insulation material between plates will allow conductive deposits to form and internally short the cell. Poor maintenance can allow external shorting through conductive contamination of the battery case and internal contamination of the electrolyte which can reduce its activity, increase corrosive effects on the plates and connectors, and cause internal shorting, depending on the substance that causes the contamination. Salt water entering the battery can result in the release of chlorine gas, due to reaction with the positive plates. Highrate discharges to low end voltages will shorten a battery's life considerably. In general, a lead-acid battery should not be discharged below 1.75 V/c. A discharged lead-acid battery should not be allowed to stand for zn extended period in a discharged condition or, because of suliation, it may not accept a recharge. Recharge should be initiated immediately if possible, and within 2 days to minimize sulfation damage and grid corrosion. High-rate recharging of lead-acid batteries may also reduce their life through heating, plate warping, or capacity percent overcharge. Lead-antimony cells are capable of about 150 to 200 discharge/recharge cycles when discharged at the normal 8-hour rate to 1.75 volts per cell and recharged at a normal rate to 2.15 - 2.25 volts per cell. Under the same conditions, leadcalcium cells are capable of about 50 to 75 discharge/recharge cycles.
f Storage. The storage area should be dry and clean. A storage temperature from 60 to 80 degrees fahrenheit is preferred. Battery storage (charged and wet) at temperatures below 20 degrees fahrenheit could result in freezing of the electrolyte in a wet cell (depending on the specific gravity) which may damage the cell. Storage at temperatures above 90 degrees fahrenheit can result in a shortened life, as well as faster self discharge. Dry charged cells can be stored up to one year without deterioration. The storage temperature should be as constant as possible. Wet charged cells should not be stored longer than 90 days without recharging. Large temperature fluctuations will cause air to enter unsealed dry charged batteries when they cool, and expel air as they become warm. Every time air enters the dry charged battery, it will bring moisture and air to th8 plate's active material, adversely affecting them. However, wet and charged cells must be given an Initial charge within 3 months from the date of shipment if the battery is of the lead-antimony type and within 6 months if of the lead-calcium type, to avoid sulfation of the plates. Sulfation of the plates can adversely affect electrical performance and expected life. If an extended storage period becomes necessary, additional charges should be provided at 3 month intervals. The extended storage of wet, charged batteries is not recommended. Batteries that are to be removed from service and stored should be charged, cleaned and stored as described above for new wet, charged batteries.
Chap 2 Par 13 Page 21
6980.248 July 12, 1988
g re Modes. performance requirements,
When the battery can no longer meet its it is considered to have failed. Causes of failure are normal ageing, manufacturing defects, improper maintenance, misuse, and damage.
(1) Batteries can suffer from reduced capacity which normally occurs gradually and is a failure mode that occurs with warning and will allow time to correct without an interruption in service. This type of problem occurs at the end of battery life and can be caused from contamination and/or active material shedding within the battery. Batteries also suffer from catastrophic failures such as open circuits and battery rupture. This will typically be due to poor construction or improper mainten-
ance. This type of problem can occur without warning and cause unplanned interruption of service.
(2) The main causes of aging failures are grid corrosion, cell shorting, loss of active materials from plates, and sulfation. Grid corrosion is oxidation of the plate grids caused by overcharging and oxygen formation at the positive plate. As grids corrode, they become brittle and lose structural strength and capability to conduct electric current. Cell shorting, or contact between conductors of opposite polarity, can occur because of damage or accumulation of conducting material (shedded active plate material) that forms a bridge between plates of opposite polarity. Active material that is lost from plates can no longer participate in the electrochemical reactions, resulting in lost capability. Sulfation results from undercharging or remaining too long in the discharged state. After sufficient time to crystalize and harden, the sulfate can no longer be converted by charging.
14 0 NICKEL-CADMIUM-ALKALINE a
14 0 NICKEL-CADMIUM-ALKALINE a
a. Theory And Chemistry cell involves little or no change
Operation of a nickel-cadmium
in electrolyte concentration. The active material of both electrodes, in both charged and discharged states, is relatively insoluble in the alkaline electrolyte. Because of these and other properties, nickelcadmium-alkaline cells are characterized by long life in both cyclic and standby operation, and by a relatively flat voltage profile withln a wide discharge current range. In the discharged state, nickel hydroxide is the active material of the positive electrode, and cadmium hydroxide that of the negative. During charge, nickel hydroxide, Ni(OH) is converted to a higher valence oxide. And at the negat ie electrode, if cadmium hydroxide, Cd(OH)2 is converted to a higher valence oxide. The overall reaction is:
July 12, 1988 6980.24A
Charged Condition Discharned Condltiog
Positive Negative Positive Negative plate plate plate plate
2NlOOH + Cd + 2H20 -W-W--W > < -wwww-w 2Ni(HO12 + Cd(OH)2
From the above formula it is obvious that the capacity is dependent only upon the amount of material in the positive and negative plates. The conductivity of the active materials, the supporting network, and plate straps also enter into the discharge characteristics of the nickel-cadmium-alkaline cells. A nickel-cadmium-alkaline cell Is charged by forcing a direct current through the cell In the direction opposite that of the discharge current. In the discharged state, the material in the interstices of the positive electrode consists mostly of nickel hydroxide 9 and that in the negative is mostly cadmium hydroxide. During charge, nickel hydroxide is converted to higher valence nickel hydroxides (NiOOH; trivalent state.
Ni[OH13), most of which are in the Oxygen may be evolved by the positive 8lectrode during charge. The amount of oxygen generated is determined by the state-of-charge of the electrode, current density, and temperature. As the state-of-oharge is increased, the fraction of the current utilized to convert the remaining nickel hydroxide is decreased. Similarly, when the current density is low (on the' order of the C/100 rate), the charge efficiency is reduced to such a degree that the cell never becomes fully charged. At high temperatures the charge efficiency is lowered, and a higher minimum current density is required to effectively charge a cell.
b hours, l 0. A measure of capacity is amperemeasured by multiplying the current drain times the duration of the current drain. Large stationary nickel-cadmlumalkaline batteries are typically rated for several different discharge rates in the referenoe literature. The dlaoharge rate affects the nickel-oadaium-alkaline battery capacity that can be withdrawn above cutoff voltage. Increasing the rate decreases the available capacity. However, when compared with lead-acid batteries, the magnitude of the change is nauch smaller. Table 2-4 provides an example of rate effects on the capacity of a particular nickel-cadmium-alkaline battery.
c. r8 Effeetq As with lead-acid batteries, temperature also affects the ierforrance of nickel-cadmiumalkaline batteries. The effect on capacity, life, and the freezing temperature Is discussed in the following paragraphs.
(1) CaDacitb As with a lead-acid battery, the capacity of a nickel-cadmium-alkaline battery is dependent on the
Chap 2 ‘Par 14 Page 23
6980.248 July 12, 1988
electrolyte temperature and discharge rate. Table 2-5 lists the decrease in capacity for temperatures below 77 degrees fahrenheit
for discharge rates of 8 hours and 1 minute of a typical nickelcadmium-alkaline cell. The capacity characteristic varies between cell type more than with lead-acid batteries. The
TABLE 2-4 EXAMPLE OF NICKEL-CADMIUM-ALKALINE
TABLE 2-4 EXAMPLE OF NICKEL-CADMIUM-ALKALINE
POCKET PLATE CELL CAPACITY' VERSUS RATE
DISCHARGE RATE PERCENT CAPACITY
lo-HOUR 105% 8-HOUR 103% S-HOUR 100% 3-HOUR 961 l-HOUR 81% 300MINUTE 64% l-MINUTE 5%
'NOTE: Capacity to cutoff voltage of 1.00 volts at 77 degrees fahrenheit ambient. The 5-hour capacity is the baseline or nominal rate.
DISCHARGE RATE PERCENT CAPACITY
manufacturer should be consulted for the discharge character-
istics for a specific cell. The increase in capacity above 77 degrees fahrenheit is usually ignored and the life effect is also not significant unless temperatures are high enough
(130 degrees fahrenheit continuous ambient) to do short term damage to the cells.
TABLE 2-5 NICKEL-CADMIUM-ALKALINE BATTERY CAPACITY VS TEMPERATURE
TABLE 2-5 NICKEL-CADMIUM-ALKALINE BATTERY CAPACITY VS TEMPERATURE
Electrolyte Percent Capacity Temperature and Discharge Rate
OF 8 HR 1 MIN
77 100% 100% 60 95% 90% 40 84% 78% 20 75% 68% 0 65% 57% - 2 0 56% 47%
(2) Freezing Temperature. The standard specific gravity of the electrolyte in a typical stationary nickelcadmium-alkaline battery is 1.180 which is a safe condition down
OF 8 HR 1 MIN
July 12, 1988 6980.248
to -25 degrees fahrenheit. For extremely low temperatures a specific gravity of 1.225 can be used which provides safe operation down to -54 degrees fahrenheit. Specific gravity does not change with state of charge in a nickel-cadmium-alkaline battery.
d 0 CharQiag l
(1) Float Charm Nickel-cadmium-alkaline batteries operating at temperatures fro; 60 to 80 degrees fahrenheit are normally float charged at 1.40 to 1.42 V/c. Random variations in temperature from about 40 to 85 degrees fahrenheit will have no significant effect on the charging. If the operating temperature is consistently high or low, some adjustment in the float voltage must be made. This adjustment amounts to 1 percent per 8 degrees fahrenheit. At low temperatures the float voltage is increased and at high temperatures it is decreased.
(2) Pisch-rate Charge The batteries are recharged automatically by the charger folliwing a discharge (e.g l 9 power outage) at a voltage higher than the normal float voltage. This higher voltage Is referred to as the high-rate oharge voltage. Nickel-cadmium-alkaline batteries will accept ourrent at a much greater rate than lead-acid batteries without permanent damage
(e.g., buckled plates) as long as the battery is not allowed to heat to the point of boiling the electrolyte or softening the case material. Hence, the term high-rate oharging. The recommended high rate charge voltage varies from 1.50 to 1.70 V/c depending on the manufaoturer*s oell type. High-rate recharging following a discharge can be avoided by raising the normal float voltage. However, the water loss will increase. Table 2-6 lists the effects of various float voltages on water oonsumption and recharging characteristics of typical nickel-oadmium-alkaline batteries.
e. Servfce Life. The life of a nickel-cadmium-alkaline battery Is not affected by high temperature as much as lead-acid batteries. At a continuous temperature of 115 degrees fahrenheit the life of a nickel-cadmium-alkalina battery will be 65 percent of the life at 77 degrees fahrenhelt while the life of a leadacid battery will be only about 27 percent of the 77 degrees fahrenheit life. At 90 degrees fahrenheit the nickel-cadmlumalkaline battery life will be approximately 88 percent while the life of a lead-acid battery will be approximately 50 percent of the life at 77 degrees fahrenheit.
f Storage. The storage area should be clean and A storage'temperature of 60 to 80 degrees fahrenheit is
dry.
preferred. Storage at temperatures down to -10 degrees fahrenheit is safe. Storage at temperatures above 110 degrees fahrenhelt should be avoided since at this temperature a
Chap 2 Par 14 Page 25
6g80.24A July 12, 1988
shortening of cell life begins. Unfilled cells can be stored for an unlimited time. Filled cells that are to be stored for up to 1 year should be given a charge. Before storage the electrolyte level should be checked. Electrolyte of the proper specific gravity should be added if necessary to bring the level up. If the plates are exposed and electrolyte is not available just enough distilled or deionized water should be added to cover the plates. When electrolyte becomes available it can be added to bring the level up. The battery can then be charged and the electrolyte specific gravity adjusted to the correct value. Adjustment is accomplished by adding water or removing electrolyte and adding water if the specific gravity is high. If the specific gravity is low, the battery can be given an extended charge, which allows electrolysis to take place and then adding electrolyte.
TABLE 2-6, FLOAT VOLTAGE EFFECTS 0N NICKEL-CADMIUM-ALKALINE BATTERIES
TABLE 2-6, FLOAT VOLTAGE EFFECTS 0N NICKEL-CADMIUM-ALKALINE BATTERIES
v/c Watering Recharging Intervals Characteristics
1.40-l .42 2-5 years Equalizing charges required if complete discharges occur more often than once a year.
1 . 4 4 - 1 . 4 7
1.50-1.53
1.55-1.60
18-36 months Battery will be fully charged even if complete discharges occur as often as once per month.
g-18 months Battery will be fully charged even if complete discharges occur as often as once per week.
1-6 months Battery will be fully charged even if complete discharges occur as often as once per day, Not recommended for continuous use because of excessive water consumption.
-~ N O T E : Unlike lead-acid batteries, nickel-cadmium-alkaline batteries do not require periodic equalizing charges.
g Failure Modes, When the battery can no longer meet its performance requirements, it is considered to have failed.
July 12, 1988 6980.248
Approaching the end of life a nickel-cadmium-alkaline battery will gradually loose capacity. The only way to detect this type of failure is to run periodic capacity tests on the batteries. A more rapid type of faflure is caused by internal shorting between plates of the battery cell. This type of failure is evidenced by the affected‘ cell having a lower voltage reading on float than the other cells in the battery.
(1) Memorv effect is an apparent loss of capacity occurring in some nickel-cadmium-alkaline batteries, small sealed cells, aa a result of regular shallow discharging at the same rate to the same depth. When deeper discharging Is attempted, the battery voltage drops off, as if fully discharged. Normally, capacity can be restored by reconditioning the battery with a few cycles of complete discharge and full recharge.
(2) Thermal rugawav is a serious failure, basically being internal cell shorting during charge. In this condition, the separator material has deteriorated and internal shorting occurs. Internal temperatures rise and the charge current increases, driving up the temperatures further. As the electrfoal energy is dissipated internally, damage Increases. The battery will get hot, smoke, release hazardous vapors, and may catch fire or explode. Nickel-cadmium-alkaline battery float charging sbould be accomplished using chargers with a low current limit to reduce the consequences of thermal runavay.
Chap 2 Par 14 page 27(and 28)
July 12, 1988
CHAPTER 3. BATTERY SELECTION
CHAPTER 3. BATTERY SELECTION
6980.24A
15 CHAPTER OVERVIEW. This chapter offers guidance for t&n and sizing of secondary (rechargeable) batteries for
selec-
application in FAA facilities and equipment. It is divided into 2 sections: section 1 describes the selection of new (original) batteries, and Section 2 discusses selecting replacement batteries. To assist in documenting battery requirements, section 1 includes a data sheet format for collecting information about the battery application. A quick reference guide, the Battery Selection Flow Chart, is included at the end of section 1.
SECTION 1. NEW (ORIGINAL) BATTERIES
SECTION 1. NEW (ORIGINAL) BATTERIES
16 SYSTEM APPROACH. The selection and sizing of secondary batteries is an important step toward ensuring satisfactory system operation. Battery selection may begin at the earliest time the electrical parameters of the equipment can be defined. Battery specifications and data published by manufacturers should be consulted when comparing electrical parameters of batteryusing equipment with batteries that are commercially available. Selection of commercial batteries inevitably involves some degree of trade-off between performance ideals and commercial availability. When possible, battery selection and sizing should be coordinated with facility or equipment designing in relation to the charge and discharge electrical parameters, battery space, temperature environment, and ventilation for optimizing system performance. Battery selection and sizing can be accomplished using the procedures given herein and results compared with recommendations from manufacturers.
17 needs
INITIAL PROCESS. When equipment or facility electric power have been defined, it should be determined if a battery power source is applicable. The guidance provided in the latest edition of the Electrical Power Policy, Order 6030.20, and Power Policy Implementation of National Airspace System, Order 6950.2, should be applied in the determination of facility requirements. If the equipment or facility cannot tolerate an unscheduled power loss, or requires high reliability or portability, battery power as either the primary or backup source is probably necessary. Basic to these considerations are policy considerations and an
initial value analysis dependent on the application needs. If, after initial value analysis, it has been determined that secondary batteries are needed, selection of the battery may begin. In the most difficult case, a new facility or equipment has been or is being designed and will need secondary batteries. Selection will include determining if the application environment is suitable for batteries or needs modification and what electrochemistry to use, in addition to determining battery parameters.
Chap 3 -Par 15 Page 29
6980.24A July 12, 1988
SHEET. Figure 3-1, The Facility Battery Selection Data is intended as a working paper to use in collecting information about the battery application. Completion of the data sheet should be as accurate as possible, because it provides basic information for selecting and applying the battery in the system. The data sheet should be completed prior to or as the first step in using the flow-chart battery selection procedures. A discussion of entry information items follows the data sheet.
a. Selecting Office. This is the office code or identification of the person filling out the data sheet.
b identiiies
Where Battery To Be Used (Facilitv/Eauipment)
the intended operational site of the battery;
This ego 9 HIGH ALTITUDE VORTAC, INDIANAPOLIS, INDIANA or HIGH ALTITUDE VORTAC, CONTINENTAL U.S. or All Maintenance Facilities, AN/XYC PORTABLE DIGITAL VOLTMETERS. The description should always include the equipment designation and type of facility. If the battery will be used in only one specific geographic location, that location may be included.
c. ADDlication or Use of the Battery to be Selected. The intended application or use of the battery will lead to determination of battery type. Data entry should include a descrip- * tion of the intended application or use in general terms for mobility (stationary, mobile, man portable, other terms), using equipment (relays, forklift, etc.), charging scheme (recharge and float, equalizing recharge and stand, automotive regulated, solar, wind generated, other terms), and discharging purpose (engine starting, emergency lighting, motive power, normal primary operating power, other terms).
d Scheduled maintenance interval which maintenance
List the interval at operations, including battery maintenance, will be performed (six months, no scheduled maintenance planned, etc.).
e. Maintainabilitv considerations. Other maintainability considerations to be listed include whether or not battery maintenance such as voltage measurements or water level measurements or water addition can be accomplished with the system operating, whether or not special provisions such as removal of the battery from the equipment are necessary to test battery capacity, and whether or not battery performance is monitored remotely.
f SDecial reauirements includes requirements for allposit&n capability, special chemical compatibility, connection of a gas collection manifold to battery vents, or other battery physical capabilities not generally available.
July 12, 1988 6980.24A
GURE 3-l. BATTERY FACILITY DATA SHEET
GURE 3-l. BATTERY FACILITY DATA SHEET
FACILITY BATTERY SELECTION
DATA SHEET
. Date
Selecting Office
Where Battery to be used (Facility/Equipment)
Describe application or Use of Battery to be Selected
Scheduled Maintenance Interval
MaIntainability Considerations
Special Requirements (All-Position Use) (Chemical
DATA SHEET
Compatibility) (Gaming Manifold) (etc)
Remarks
Chap 3 Par18 Page 31
6980.248 July 12, 1988
UY FACILITY DATA SHEET (Continued)
FACILITY BATTERY SELECTION DATA SHEET
Facility Application Environments (Operational Battery Ambients)
Minimum Expected Temperatur8 OF Duration
Maximum Expected Temperature OF Duration
FACILITY BATTERY SELECTION DATA SHEET
Normal Expected Temperature OF Duration
Describe Unusual Conditions (Shock) (Vibration) (Rain)
(Sunlight) (Altitude) (Dust) (etc.)
Battery Discharge Load Profile Into Equipment
Maximum Voltage Tolerated Volts '1
Lowest Voltage for Required Performance
)r
Volts
Maximum Current (inrush, splkes) Amps
Normal Operating Current Amps
Complex Load Considerations (see Appendix 1
--_-~ ~~ _ _~
Discharge Duration
Maximum Calculated Ampere-Hours Capacity (Inolude any
design safety margins) Ampere-Hours
Anticipated Frequency of Deep 075%) Discharge %
July 12, 1988 6980.24A
IGURE 7-l BATTERY FACIUTY DATA SHEET
IGURE 7-l BATTERY FACIUTY DATA SHEET
(Cant inued)
FACILITY BATTERY SELECTION DATA SHEET
Charge Characteristics Available
Charger power from: (Commercial line, renewable energy,
etc.)
When is Recharge Started
Tine Available for Recharge Hours
Maxfmum Voltage to Battery Volts
Maximum Current to Battery Amps
FACILITY BATTERY SELECTION DATA SHEET
Method of Recharge (Constant Potential)
(Constant Current) (Hybrid Description) (Pulse Charging)
MiaoellaneoudOther
8 0 A reuru section is Included to use for pertinent notes or oomments.
h expectid temperature values,
ts inolude the durations, and unusual environments.
(1) Th8 8m8ct8d t8mperatur8 values are the expected ambient8 a t t h e b a t t e r y locration. The durations may be expressed as a cumulat$ve percentage of a calendar year and may Include a daily (or other) duration limit for continuous exposure. Temperature expectations may be determined from c!limatic charts, facility criteria, or actual measurement8.
(2) Unusual envlroumentaa conditions to be 118ted includ8 expect8d shock or vibration (describe levels, other known
Chap 3 P a r 18 Page 33
6980.24A July 12, 1988
paraneter8) t unprotected battery expo8ure to rain, dire& sunlight, or oheniaal du8t8, altitude8 greater than 10,000 feet, etc.
(3) Jifent&latioq that ia available shall be described. The type of ventilation, Le., 8eparate ventilation fam, fr88h make up air a8 part of the heating and aooling 8y8t8!E or special ventilation nanifold8. The quantity of ventilation air In cubio feet per minute if available. The amount of natural infiltration due to the type of structure, Le., old zstructure or new well
insulated and 88al8d 8truoture.
I equlpna~nt,
n(~ load profile Into a de8oription of the battery di8oharge 18 developed.
(1) Maw volt- tolerated is the maximum voltage value from the battery that the equipment can tolerate without equipment damage oaaurring. If thi8 value differ8 from the maximum value for required equipment operation (performance), both value8 should be noted.
(2) Govest volt- for required performanae 18 the lowe8t voltage value from the battery that the equipment can u8e to provide required performance.
(3) m Current (inrush, apikea) 18 the highmt current value that the equipment will require from the battery.
(4) l!orma oDerati= current 18 the aontinuou8, 8t8ady 8tate, or average current that the battery will be expected to provide to the equipment.
(5) Complex load conaideratlon8, de8aribed in appendix 1 g are applicable for capaalty determination In aam involving non-uniform or Irregular di8charge aurrent8. The complex load d88cription should be 8ummariz8d in the 8paae provided. If the load profile 18 aomplsr--generally apeaking, not a fixed reahtanaa load or constant wzrrent load--the exact load profile definition (graph or equation) may be required for purpo8e8 of rate and aapaoity determination8.
(6) Duhae duatlop la the time (total, unlnterrupted) In hours, that the battery ia required to provide power to the equipment. If there are no mean8 8uoh a8 voltage cutoff relay or timer within the equipment to autonatiaally 8top the discharge, and manual termination of the dl8aharge might not be aaaomplished, then the battery might be over-di8aharged to a8 low a8 zero Volts. Thi8 po88ibility of over di8aharging to zero volt8 8hould be Included, along with the planned disoharge duration.
(7) ne rnari~urn ampere-hour oapacity, including any design safety margin in accordanoe with ourrent FAA policy or
Page 3S
July 12, 1988 6980.248
circumstances should be calculated and entered on the appropriate blank. It should noted that this value is uncorrected for temperature, rate, or other variations. If capacity is being specified for automotive batteries in terms of seconds of cold cranking time, rate and rating temperature should also be specified along with reserve capacity. The data sheet term AMPERE-HOURS should be marked out and the appropriate unit terms Inserted for automotive batteries.
(8) The anticioated frequency of discharging to greater than 75 percent of calculated capacity should be entered
in the appropriate space, expressing the frequency as a percentage of the total number of cycles that the battery will experience. For Type VI renewable energy storage batteries, the total number per year of anticipated occurrences of discharging more than 75 percent should be given.
3 arp1e characteristics, all available detail8 of charger performance are entered. If the charger parameters have not been defined because the charger ha8 not been aelected, then so note and change the data sheet sub-heading to charge characteristics required.
(1) The source of power to the battery charger should . be entered in the appropriate blank.
(2) The auestiog, WHEN IS RECHARGE STARTED? should be answered with, when engine starts, when commercial power is available, or other appropriate description.
Note: If delay of the recharge for more than 2 day8 is anticipated, this fact must be Included.
(3) Time available for recharge In hours should be listed. Current FAA practice is that the time for recharging shall be greater than or equal to twice the discharge time, but in no case greater than 24 hours, according to the formula: (2 l discharge duratlon)<(recharge duratlon)<(24 hours).
(4) The maximum voltane to battery is the highest voltage that will be available to the battery from the charger.
If the charger ha8 2 voltage steps such aa for recharging at a low rate, followed by equalize charging or for equalizing recharge followed by float, both voltage values should be listed. If the charger has an adjustable voltage range, the range should be listed.
(5) urrent to battery is the highest current that the charger can deliver to the battery. If the ' charger has different current capabilities, the capabilities should be described as were the voltage values. Generally, the maximum charging current available should not exceed the maximum discharge current required. If the charger will be providing
Chap 3 Par18 Page 35
6980.24s July 12, 1988
. . operating p&r to the equipment at the same time It Is recharging the battery, the maximum charging current available should not exceed twice the maximum battery discharge current. If the charging method is by constant current (see next entry), the current should result In replacement of 110 percent to
125 percent of the battery capacity (greater than 100 percent due to battery charge efficiency losses) in the time allowed for recharging. For recharging by the constant current method, actual battery charge efficiency must b8 determined, as well as the amount of overcharge that the battery can withstand wfthout damage or hazardous release of stlbine or arsine gases (from lead-acid batteries containing antimony or arsenic).
(6) The iptended method of recharge should be described in the appropriate space. The most common recharge method for lead acid batteries i8 a one-or two-step constant
potentfal recharge with a current limit that Is low enough to prevent battery damage but high enough to allow complete recharging well within the allowable time. Nickel-cadmium-alkaline batteries ace typically recharged by the constant current method.
k Miscellaneous/other allows recording of pertinent cornme& or additional information at the discretion of the person filling out the data sheet.
19 0 NEia (ORIGINAL) BATTERY SELECTION.
a. St(bD 1. Collect D,C. Power Reauremepts Selection of new (original) secondary batteries begins with coilectlon and review of D.C. power requirements and facility details, Including environment8. Complete the Facility Battery Selection Data Sheet previously discussed to initfate the selection process. The selection process will continue with determination of battery type, Ch88, style, capacity, environment, number of cells and voltage, charging requirements, maintainability, and remaining parameters for speciflcatlon. In the end, availability, cost and satisfaction of requirements should be considered to determine realism. Value analyaia may b8 nece8sary, if electroch8mistry ha8 not yet been 8818cted.
rv Tvne The type (FAA re) of battery de8crib88 the Intended application in FAA facilities or equipment. Battery design and construction is influ8nC8d by intended u8e or application. A brief discussion of the relation8hips between type and typical applications follows, with a more detailed discussion contained under the applicability paragraph in Chapter 2. To 88lect battery type, determine from the li8ted applications the one that best fits the Particular need and 8peciiy the corresponding type number (reman numeral).
(1) Tvpe I batteries are designed to be maintained on standby on continuous float charge with occasional discharge into
July 12, 1988 6980.24A
loads such as uninterruptable power supplies, switohgear, or oommunications equipment.
(2) TVD~ II and TVD~ III batteries are designed to provide high currents for short durations to engine cranking
(starter) motors, followed immediately by recharging. Type II batteries are used with stationary engines. Selection of capacity of Type II batteries Is facilitated by referring to engine start battery table, table 3-4. Type III batteries are used with motor vehicles and are smaller and more resistant to vibration than type II batteries. Descriptions of the configurations of currently manufactured Type III batteries for automotive applications are contained in Society of Automotive Engineers Specification 5537.
(3) TVD~ IV batteries are designed for intermittent discharging at moderate power levels (electric motor loads) with extended stand time (days or weeks) in various states of disoharge. Type IV batteries are used to provide motive energy in electric forklifts, transporters, and electric vehicles.
(4) TvDe V batt cries are normally of a sealed design, used for low power discharging in portable test equipment or emergency lights, and are normally recharged within 2 days after use,
(5) TvDe VI batteries are designed for cycle use at various depths of discharge and low to moderate power levels. A significant portion of the cycle recharges will be incomplete, such cycling being typical of solar power source or wind power source applications.
c. Ster,. Determine Maiat nags e e Interval The class (FAA nomenclature) of battery describes the maintainability of the battery. To specify class, determine from the listed maintenance intervals the class that fits the partioular application, considering current FAA maintenance philosophy and maintenance requirements of collooated equipment, the suitability of the battery installation for accomplishing maintenance, and the different amounts of work (maintenance operations) needed by the different olasses. Then specify the corresponding class number (arable numeral) see table 3-l. Additional diaousslon of typical associations between class and type is contained under the appllcabllity paragraph in chapter 2. The relationship between class and maintainability is described below,
(1) Class 1 (FAA nomeulature) regular (high) maintenance batteries may require distilled water additions at sfx month intervals to restore cell electrolyte levels. At l - y e a r intervals9 oell voltage and the electrolyte specifio gravity should be measured, equalize charging should be performed, and battery terminals should be cleaned, treated with corrosion preventative, and retorqued, Note, that some battery charging methods auto-
Chap 3 P8r 19 Page 37
6980.248 July 12, 1988
matioa1l.y accomplish an equalizing recharge after every discharge or on a daily basis through use of 2-step charging, high rate time controlled oharglng, or daily boost charging controlled by a timer or voltage sen8itlve relay. All Class 1 batteries should be given an annual equalizing charge to achieve or verify the fully charged state wherein the cell voltages are properly balanced within the battery and, for lead acid batteries, that the electrolyte has the proper speolfic gravity without tending to lnoreasa In value as the equalize charge is continued. (If the speoific gravity of lead-acid batteries tended to increase, the electrolyte may have been stratified, plate sulfatlon may be decreasing, or significant water consumption due to electrolysis may be occurring. If the electrolyte specific gravity remains steadily below the proper value, excess water addition may have oourred or sulfurla aaid may have been lost during specific gravity measurements or through venting aerosol.) Class 1 batteries should be 8p8cified when FAA policy permits that level o f maintainablllty, the installation is suitable for it, and the batteries may experience frequent deep discharging or abusive conditions.
(2) Class 2 (FAA ngmqclature) low maintenanae batteries may require water addftions at one-year intervals to restore cell eleatrolyte levels. Typically, manufacturers reaommend against high rate equalize aharging of lowmaintenance batteries. Automatic equalizing chargers should have lower voltage limits, to provide lower rate equalizing. A typical lower rate equalize aharge cell voltage limit for leadacid batteries would be in the range of 2.3 to 2.4 volts as opposed to 2.4 to 2.7 volts for high rate equalizing. Class 2 should be specified when FAA policy permits or requires that level of maintainability, the installation is suitable for it, and the batteries will not experienae frequent deep discharging or abusive aonditions.