Order 6950.19A Practices and Procedures for Lightning Protection Grounding, Bonding, and Shielding Implementation

This document is cancelled. It may have been replaced. Check the official source before relying on it.

Official source ↗ Open PDF

Text read by OCR from a scanned file (350 of 353 pages). Check the original, as some words may be misread.

ORDER 6950.19A

ORDER 6950.19A

PRACTICES AND PROCEDURES FOR

LIGHTNING PROTECTION, GROUNDING, BONDING,

AND SHIELDING IMPLEMENTATION

FEDERAL AVIATION

July 1, 1996

U.S. DEPARTMENT OF TRANSPORTATION FEDERAL AVIATION ADMINISTRATION

Distribution: Initiated By: ANS-600 A-W(AF/RA)-3 A0S-1000 A-X(AF)-3; A-YZ-3; A-FAF-2(STD)

U.S. DEPARTMENT OF TRANSPORTATION FEDERAL AVIATION ADMINISTRATION

FOREWORD

This order provides design guidelines for implementation of effective lightning protection, .grounding, bonding, shielding, and surge and transient protection for use by Headquarters and Region Design Engineers in designing new FAA electronic facilities and electronic equipment installations. A survey procedure for existing electronic facilities is also included, and is for use by Headquarters, Regional and System Management Office (SMO) personnel in evaluating the effectiveness of the lightning protection, grounding, bonding, shielding, and surge and transient protection presently in use. The survey procedures also provide guidance for the evaluation of deficiencies discovered during accomplishment of the survey in determining whether or not corrective action is warranted and for the inspection and acceptance or rejection during the Joint Acceptance Inspection (JAI).

THE MATERIAL IN THIS ORDER PROVIDES GENERAL DIRECTION AND GUIDANCE TO FACILITATE EFFECTIVE DESIGNS IN THE AREAS NOTED ABOVE. HOWEVER, IT IS NOT POSSIBLE TO SPECIFICALLY DETAIL, ON AN ITEM-TO-ITEM BASIS, EXACT DESIGN PROCEDURES TO BE USED. THEREFORE, THE USER MUST BECOME FAMILIAR WITH THE CONTENTS OF THE ORDER, AND SUBSEQUENTLY APPLY THE KNOWLEDGE GAINED TO SPECIFIC AND DETAILED DESIGN METHODS AND PRACTICES.

Stanley Rivers Acting Director of Airway Facilities, AAF-1

07/01/96

TABLE OF CONTENTS

TABLE OF CONTENTS

CHAPTER 1. GENERAL 1. PURPOSE. 2. DISTRIBUTION 3. CANCELLATION. 4. BACKGROUND. 5. ACTION. 6. DEFINITIONS. 7. AUTHORITY TO CHANGE ORDER 8. - 10. RESERVED

CHAPTER 2. NEW FACILITIES DESIGN CRITERIA 11. GENERAL

SECTION 1. EARTH ELECTRODE SYSTEM 12. GENERAL 13. DETERMINATION OF SITE PARAMETERS 14. GEOLOGICAL EFFECTS IDENTIFICATION 15. PHYSICAL FEATURES 16. LOCAL CLIMATE 17. DESIGN PROCEDURE 18. ALTERNATE CONFIGURATIONS 19. DESIGN GUIDELINES 20. INSTALLATION PRACTICES. 21. - 29. RESERVED

CHAPTER 2. NEW FACILITIES DESIGN CRITERIA 11. GENERAL

SECTION 2. LIGHTNING PROTECTION FOR STRUCTURES 30. PRINCIPLES OF LIGHTNING PROTECTION 31. INTEGRAL PROTECTION SYSTEM 32. AIR TERMINALS 33. LIGHTNING PROTECTION CONDUCTORS 34. ROOF CONDUCTORS. 35. DOWN CONDUCTORS. 36. FASTENERS 37. SEPARATELY MOUNTED PROTECTION SYSTEM 38. ANTENNA TOWERS 39. FENCES 40. GUYED TOWERS 41. BONDS AND CONNECTORS 42. ELECTROLYTIC COUPLES AND CORROSION CONTROL 43. INSTALLATION AND MATERIALS 44. - 49. RESERVED

SECTION 3. GROUNDING NETWORKS FOR NEW FACILITIES 50. GENERAL 51. ELECTRONIC EQUIPMENT GROUNDING SYSTEMS 52. POWER DISTRIBUTION SYSTEM GROUNDING 53. COMBINED FACILITY GROUNDING 54. MOBILE FACILITIES 55. - 59. RESERVED

6950.19A

Page 1 1 1 1 1 2 3 11 11

12 12

13 13 13 18 18 18 19 21 22 32 34

35 35 36 36 43 44 46 48 48 49 52 53 53 55 56 56

57 57 57 78 81 83 85

Page iii

6950.19A

07/01/96

SECTION 4. BONDING PRACTICES 60. GENERAL . 61. APPLICATION GUIDELINES 62. SURFACE PREPARATION 63. BOND PROTECTION CODE 64. TYPICAL TYPES OF STRUCTURAL BONDS 65. - 69. RESERVED

SECTION 5. SHIELDING DESIGN AND IMPLEMENTATION 70. GENERAL 71. ESTABLISHMENT OF REQUIREMENTS 72. DESIGN GUIDELINES 73. SELECTION OF MATERIALS 74. CONSTRUCTION GUIDELINES 75. - 79. RESERVED

Page 86 86 86 89 90 96 104

105 105 105 111 112 117 126

SECTION 6. LIGHTNING INDUCED SURGE AND TRANSIENT PROTECTION

FOR ELECTRICAL AND ELECTRONIC SYSTEMS 80. GENERAL . SURGE AND TRANSIENT SOURCES

FOR ELECTRICAL AND ELECTRONIC SYSTEMS 80. GENERAL . SURGE AND TRANSIENT SOURCES

127 127

EQUIPMENT DAMAGE

81. AND 82. MINIMIZING DAMAGE 83. SUSCEPTIBLE COMPONENTS

127 128 129

FREQUENCY OF SURGE AND TRANSIENT OCCURRENCE

84.

130

SURGE DEFINITION, AC SERVICE CONDUCTORS

85.

130

METHODS FOR SURGE PROTECTION ON AC SERVICE

METHODS FOR SURGE PROTECTION ON AC SERVICE

86. CONDUCTORS 87. USE OF FERROUS METAL CONDUITS 88. USE OF GUARD WIRES 89. SECONDARY AC SURGE ARRESTER 90. SURGE ARRESTER INSTALLATION

135 136 136 138 139

OPERATING CHARACTERISTICS OF SURGE ARRESTERS

91. CHARACTERISTICS OF DIFFERENT TYPES

143

OF SURGE

92. ARRESTERS TRANSIENT PROTECTION FOR EXTERNALLY

92. ARRESTERS TRANSIENT PROTECTION FOR EXTERNALLY

148

EXPOSED

93. ELECTRONIC EQUIPMENT LINES 94. FREQUENCY OF TRANSIENT OCCURRENCE

154 154

TRANSIENTS

95. AMPLITUDES AND WAVEFORMS OF OCCURRING 96. EQUIPMENT WITHSTAND LEVELS 97. PROTECTION METHODS AGAINST TRANSIENTS

155 155 157

ENCLOSING CABLE RUNS IN RIGID GALVANIZED

98. 99. BURIED GUARD WIRES 100. TRANSIENT SUPPRESSION 101. TYPES OF TRANSIENT SUPPRESSORS

ENCLOSING CABLE RUNS IN RIGID GALVANIZED

STEEL

158 159 160 165

102. OPERATING CHARACTERISTICS OF TRANSIENT SUPPRESSOR

TYPES.

165

103. OPERATING CHARACTERISTICS FOR TRANSIENT

SUPPRESSORS. 104. TRANSIENT SUPPRESSOR PACKAGING DESIGN 105. METAL BULKHEAD CONNECTOR PLATE 106. GROUNDING OF UNUSED WIRES

167 167 168 169

107. TRANSIENT SUPPRESSION FOR RF AXIAL LINES

107. TRANSIENT SUPPRESSION FOR RF AXIAL LINES

169

108. ELECTRONIC EQUIPMENT-LEVEL TRANSIENT SUPPRESSION

Page iv

07/01/96

109. - 119. RESERVED

SECTION 7. COMMON-MODE NOISE AND INSTRUMENTATION 120. GENERAL 121. DESIGN PRACTICES. 122. INSTRUMENTATION CONSIDERATIONS 123. - 129. RESERVED

SECTION 8. ELECTROMAGNETIC PULSE (EMP) PROTECTION 130. GENERAL . 131. EARTH CONNECTION 132 EMP SHIELDING APPLICATIONS 133. EMP BONDING PRACTICES 134. CONSTRUCTION GUIDELINES 135. - 139. RESERVED

109. - 119. RESERVED

SECTION 9. INSPECTION AND TEST PROCEDURES FOR A NEW FACILITY 140. GENERAL 141. EARTH ELECTRODE SYSTEM 142. LIGHTNING PROTECTION SYSTEM 143. ELECTRONIC EQUIPMENT GROUNDING SYSTEMS 144. POWER DISTRIBUTION GROUNDING 145. BONDS AND BONDING

6950.19A

171 171 171 173 174

175 175 175 175 176 176 180

181 181 181 182 183 185 185

TRANSIENT PROTECTION

TRANSIENT PROTECTION

146. LIGHTNING INDUCED SURGE AND 147. - 149. RESERVED

CHAPTER 3. EXISTING FACILITIES 150. INTRODUCTION

SECTION 1. EARTH ELECTRODE SYSTEM 151. GENERAL 152.- 159. RESERVED

SECTION 2. LIGHTNING PROTECTION SYSTEM 160. GENERAL 161. - 169. RESERVED

SECTION 3. ELECTRONIC SYSTEM GROUNDING NETWORKS 170. GENERAL 171. EVALUATION AND CORRECTIVE ACTION 172. - 179. RESERVED

SECTION 2. LIGHTNING PROTECTION SYSTEM 160. GENERAL 161. - 169. RESERVED

SECTION 4.

186 188

189 189

190 190 195

196 196 198

199 199 200 201

BOND EVALUATION AND RESISTANCE MEASUREMENTS

180. GENERAL 181.- 189. RESERVED

SECTION 5. SHIELDING EVALUATION 190. GENERAL 191. - 199. RESERVED

202 202 204

205 205 206

Page v

6950.19A

SECTION 6.

07/01/96

Page

LIGHTNING-INDUCED SURGE & TRANSIENT PROTECTION

EVALUATION 200. GENERAL 201. FAILURE MODE ANALYSIS 202. - 209. RESERVED

EVALUATION 200. GENERAL 201. FAILURE MODE ANALYSIS 202. - 209. RESERVED

SECTION 7. NEC COMPLIANCE EVALUATION 210. GENERAL 211. NEC COMPLIANCE INSPECTION 212. CORRECTION OF DEFICIENCIES 213. - 219.1 RESERVED

CHAPTER 4. ELECTRONIC EQUIPMENT DESIGN CRITERIA 220. INTRODUCTION

SECTION 1. GROUNDING PROCEDURES 221. ELECTRONIC SIGNAL GROUNDS 222. ELECTRONIC EQUIPMENT 223. FAULT PROTECTION 224. CABINET GROUNDING 225. - 229. RESERVED

SECTION 2.1 BONDING PRACTICES 230. GENERAL 231. - 239. RESERVED

SECTION 2.1 BONDING PRACTICES 230. GENERAL 231. - 239. RESERVED

SECTION 3. SHIELDING GUIDELINES 240. GENERAL 241. PARTS SELECTION 242. LAYOUT AND CONSTRUCTION 243. EQUIPMENT ENCLOSURES 244. - 249. RESERVED

SECTION 4. COMMON-MODE NOISE CONTROL AND

207 207 209 210

211 211 211 217 220

SECTION 4. COMMON-MODE NOISE CONTROL AND

221 221

223 223 223 240 242 243

244 244 252

253 253 253 254 255 263

INSTRUMENTATION

GROUNDING 250. GENERAL 251. INSTRUMENTATION GROUNDING 252. - 259. RESERVED

SECTION 5. EMP CONSIDERATIONS 260. GENERAL 261. - 269. RESERVED

SECTION 6. TRANSIENT PROTECTION 270. GENERAL 271. TRANSIENT DEFINITION 272. DETERMINATION OF EQUIPMENT DAMAGE

SECTION 5. EMP CONSIDERATIONS 260. GENERAL 261. - 269. RESERVED

264 264 264 274

275 275 276

277 277 277

(WITHSTAND)

LEVELS

278

DETERMINATION OF NEED FOR TRANSIENT PROTECTION

273. 274. MINIMIZING TRANSIENT DAMAGE 275. AC POWER INPUT TO ELECTRONIC EQUIPMENT

Page vi

280 280 281

07/01/96

6950.19A

Page

276. ELECTRONIC EQUIPMENT POWER SUPPLY TRANSIENT

SUPPRESSION 277. LANDLINE TRANSIENT SUPPRESSION 278. - 279. RESERVED

SUPPRESSION 277. LANDLINE TRANSIENT SUPPRESSION 278. - 279. RESERVED

SECTION 7. ELECTRONIC EQUIPMENT INSPECTION AND TEST PROCEDURES 280. GENERAL 281. LOW-FREQUENCY ELECTRONIC EQUIPMENT 282. HIGH-FREQUENCY EQUIPMENT 283. HYBRID EQUIPMENT 284. INSTALLED EQUIPMENT 285. EQUIPMENT GROUNDING 286. BONDING 287. SHIELDING 288. INSTRUMENTATION SYSTEMS 289. LIGHTNING-INDUCED TRANSIENT PROTECTION 290. EMP DESIGN 291. OTHER OBSERVATIONS

APPENDICES

APPENDIX 1. DESIGN CHECKLIST - NEW FACILITY ELECTRONIC

APPENDIX 1. DESIGN CHECKLIST - NEW FACILITY ELECTRONIC

287 288 299

300 300 300 304 306 306 306 306 307 307 307 308 308

1

EQUIPMENT

APPENDIX 2. DESIGN CHECKLIST - NEW APPENDIX 3. INSPECTION CHECKLIST

1 1

Page vii

LIST OF FIGURES

Figure Page 2-1. MEASUREMENT OF SOIL RESISTIVITY . 14 2-2. RESISTIVITY DETERMINATION OF A SMALL SITE 15 2-3. RATIO OF THE ACTUAL RESISTANCE OF A ROD ARRAY TO THE IDEAL RESISTANCE OF N RODS IN PARALLEL 17 2-4. TYPICAL EARTH ELECTRODE SYSTEM CONFIGURATION FOR RECTANGULAR SHAPED FACILITY 24 2-5. ELECTRODE CONFIGURATION FOR IRREGULAR SHAPED FACILITY 26 2-6. ELECTRODE CONFIGURATION FOR ADJACENT STRUCTURES 27 2-7. ELECTRODE CONFIGURATION FOR CLOSELY SPACED STRUCTURES 28 2-8. GROUNDING SYSTEM FOR TYPICAL RADAR INSTALLATION 29 2-9. DETAILS OF GROUND ROD/COUNTERPOISE INSTALLATION 30 2-10. ACCESS WELL . 31 2-11. CONNECTIONS TO EARTH ELECTRODE SYSTEM . 32 2-12. GROUNDING PRACTICES FOR LIGHTNING PROTECTION 37 2-13. LOCATION OF AIR TERMINALS FOR COMMON ROOF TYPES 39 2-14. LOCATION OF AIR TERMINALS ON GENTLY SLOPING ROOFS 40 2-15. AIR TERMINAL PLACEMENT ON FLAT-ROOFED STRUCTURES 41 2-16. ILLUSTRATION OF METHOD FOR DETERMINING THE PROTECTION OF FLAT SURFACES AS PROVIDED BY AIR TERMINALS 43 2-17. RECOMMENDED CONSTRUCTION PRACTICES FOR INTEGRAL LIGHTNING PROTECTION SYSTEMS. 45 2-18.

LIST OF FIGURES

OVERHEAD GROUND WIRE LIGHTNING PROTECTION SYSTEM 50 2-19. DIAGRAM OF THE SINGLE POINT GROUND SYSTEM 59 2-20. SINGLE POINT GROUND SYSTEM INSTALLATION 60 2-21. ELECTRONIC MAIN AND SINGLE POINT PLATES 62 2-22. GROUNDING GRID ESTABLISHED BY MULTIPOINT GROUND SYSTEM. 67 2-23. ELEMENTS OF THE MULTIPOINT GROUND SYSTEM 69 2-24. OVERALL FACILITY GROUNDING DIAGRAM 82 2-25. GROUNDING PRACTICES FOR MOBILE FACILITIES WITH INTEGRAL POWER SUPPLY 84 2-26. ORDER OF ASSEMBLY FOR BOLTED CONNECTION 88 2-27. BONDING BETWEEN SECTIONS OF CABLE TRAYS 96 2-28. BONDING OF EQUIPMENT CABINETS TO CABLE TRAY 97 2-29. BONDING TO FLEXIBLE CABLE AND CONDUIT 97 2-30. BONDING TO RIGID CONDUIT 98 2-31. CONNECTION OF BONDING JUMPERS TO FLAT SURFACE . 99 2-32. BOLTED BOND FLAT BASE . 100 2-33. BRACKET INSTALLATION (RIVET OR WELD) 100 2-34. USE OF BONDING STRAPS FOR STRUCTURAL STEEL INTERCONNECTIONS 101 2-35. DIRECT BONDING OF STRUCTURAL ELEMENTS 102 2-36. CONNECTION OF EARTH ELECTRODE RISER TO STRUCTURAL COLUMN. 103 2-37. MEASURED ELECTROMAGNETIC SHIELDING EFFECTIVENESS OF A TYPICAL BUILDING AT 6 FEET INSIDE OUTER WALL .

107 2-38. MEASURED ELECTROMAGNETIC SHIELDING EFFECTIVENESS OF A TYPICAL BUILDING AT 45 FEET INSIDE OUTER WALL 108 2-39. SHIELDING EFFECTIVENESS OF REBARS 109 2-4O. SHIELDING EFFECTIVENESS OF A GRID AS A FUNCTION OF WIRE DIAMETER, WIRE SPACING AND WAVELENGTH 110 2-41. SHIELD ABSORPTION LOSS NOMOGRAPH 114

Page viii

Figure Page 2-42. NOMOGRAPH FOR DETERMINING MAGNETIC FIELD REFLECTION LOSS 118 2-43. NOMOGRAPH FOR DETERMINING ELECTRIC FIELD REFLECTION LOSS . 119 2-44. NOMOGRAPH FOR DETERMINING PLANE WAVE REFLECTION LOSS 120 2-45. SHIELDING EFFECTIVENESS OF ALUMINUM FOIL SHIELDED ROOM. 121 2-46. SHIELDING EFFECTIVENESS OF COPPER FOIL SHIELDED ROOM 122 2-47. FORMATION OF PERMANENT OVERLEAF SEAM 123 2-48. GOOD CORNER SEAM DESIGN 124 2-49. PRESSURE DROP THROUGH VARIOUS MATERIALS USED TO SHIELD VENTILATION OPENINGS 125 2-5O. MEAN NUMBER OF THUNDERSTORM DAYS PER YEAR FOR THE UNITED STATES 131 2-51. SECONDARY AC SURGE ARRESTER INSTALLATION, GROUNDED SERVICE 141 2-52. SECONDARY AC ARRESTER INSTALLATION, UNGROUNDED SERVICE 142 2-53. TYPICAL OPERATING CURVE FOR THE SERIES OF GAS-FILLED SPARK GAP ARRESTERS WITH NON-LINEAR SERIES RESISTOR 151 2-54. TYPICAL ARRESTER OPERATING CURVES, SAS AND ZNR 156 2-55. TYPICAL TRANSIENT SUPPRESSOR INSTALLATION, FACILITY AND EQUIPMENT LEVEL 161 2-56. METHOD OF ENTRY OF EXTERNAL CONDUCTORS INTO EMP- SHIELDED ROOM OR STRUCTURE 177 2-57. ENTRY PLATE SHOWING RIGID CABLE, CONDUIT AND PIPE PENETRATIONS 178

3-1. TEST SETUP 191 3-2. CURVE OF GROUND RESISTANCE VERSUS DISTANCE 193 3-3. METHOD FOR DETERMINING THE EXISTENCE OF IMPROPER NEUTRAL GROUND CONNECTIONS 218

4-1. GROUNDING IN SINGLE POINT GROUND EQUIPMENT 224 4-2. COMPOSITE SIGNAL REFERENCE NETWORK FOR AN ELECTRONIC FACILITY 226 4-3. SINGLE POINT GROUND BUS BAR INSTALLATION IN RACK OR CABINET 227 4-4. USE OF BALANCED LINES TO AVOID GROUND LOOPS 229 4-5. EFFECT OF AN UNBALANCED CABLE ON THE SINGLE POINT GROUND. 231 4-6. EFFECT OF ARBITRARILY GROUNDING THE SOURCE END OF UNBALANCED ELECTRONIC EQUIPMENT INTERCONNECTING CABLES 232 4-7. METHOD OF GROUNDING THE INDIVIDUAL SHIELDS ON LONG LOW-FREQUENCY SIGNAL CABLES 234 4-8. GROUNDING OF OVERALL CABLE SHIELDS TO CONNECTORS AND PENETRATED WALLS . 236 4-9. GROUNDING OF OVERALL CABLE SHIELDS TO TERMINAL STRIPS 237 4-10. ESTABLISHMENT OF SHIELD CONTINUITY BETWEEN HIGH FREQUENCY EQUIPMENT 239 4-11. GROUNDING PRACTICES IN ELECTRONIC EQUIPMENT CONTAINING BOTH HIGH-FREQUENCIES AND LOW-FREQUENCY CIRCUITS 241 4-12. ACCEPTABLE AND UNACCEPTABLE USES OF BONDING JUMPERS 245 4-13. BONDING OF SUBASSEMBLIES TO EQUIPMENT CHASSIS 247

Page ix

Figure Page 4-14. BONDING G OF EQUIPMENT TO MOUNTING SURFACE . 247 4-15. TYPICAL METHOD OF BONDING EQUIPMENT FLANGES TO FRAME OR RACK 248 4-16. BONDING OF RACK-MOUNTED EQUIPMENTS EMPLOYING DAGGER PINS . 249 4-17. RECOMMENDED PRACTICES FOR EFFECTIVE BONDING IN CABINETS . 250 4-18. METHOD OF BONDING ACROSS HINGES 251 4-19. BONDING OF CONNECTOR TO MOUNTING SURFACE 252 4-20. METHODS OF MAKING PERMANENT SEAM USING A GASKET 257 4-21. MOUNTING OF GASKET ON HINGED SIDE OF EQUIPMENT DOOR AND PANELS . 258 4-22. ILLUSTRATION OF PROPER AND IMPROPER SHIELD PENETRATIONS 259 4-23. USE OF CYLINDRICAL WAVEGUIDE-BELOW-CUTOFF FOR CONTROL SHAFT SHIELD PENETRATION . 260 4-24. METHOD OF MOUNTING WIRE SCREEN OVER A LARGE APERTURE 261 4-25. ACCEPTABLE METHODS OF SHIELDING PANEL-MOUNTED METERS 262 4-26. GROUNDING PRACTICES FOR SINGLE-ENDED AMPLIFIERS 265 4-27. GROUNDING PRACTICES FOR DIFFERENTIAL AMPLIFIERS 266 4-28. METHOD OF GROUNDING BRIDGE TRANSDUCERS 267 4-29. USE OF ISOLATED DIFFERENTIAL AMPLIFIER WITH BALANCED BRIDGE TRANSDUCER 268 4-3O.

RECOMMENDED GROUNDING PRACTICES FOR FLOATING TRANSDUCERS 270 4-31. GROUNDING FOR SINGLE CHANNEL STRIP CHART RECORDER 272 4-32. RESISTIVE ISOLATION OF DATA CHANNELS 273 4-33. TYPICAL CONFIGURATION FOR PROTECTION OF ELECTRONIC EQUIP FROM CONDUCTED POWERLINE SURGES & TRANSIENTS (NEUTRAL GROUNDED) . 283 4-34. TYPICAL CONFIGURATION FOR PROTECTION OF ELECTRONIC EQUIP FROM CONDUCTED POWERLINE SURGES & TRANSIENTS (UNGROUNDED SERVICE) 284 4-35. TYPICAL CONFIGURATION FOR PROTECTION OF ELECTRONIC EQUIPMENT FROM CONDUCTED LANDLINE TRANSIENTS 289 4-36. TRANSIENT SUPPRESSION FOR COAXIAL LINES (DC TO 3 MHZ) 296 4-37. TRANSIENT SUPPRESSION FOR TWINAXIAL LINES (DC TO 3 MHZ) 297 4-38. SIGNAL GROUND TERMINAL ISOLATION TEST FOR AN INDIVIDUAL ITEM OF ELECTRONIC EQUIPMENT 302 4-39. SIGNAL GROUND TERMINAL ISOLATION RESISTANCE E TEST FOR AN ELECTRONIC EQUIPMENT ASSEMBLY . 303 4-40. MEASUREMENT OF CONNECTOR BONDING RESISTANCE 305

Page x

LIST OF TABLES

LIST OF TABLES

Table Page 2-1. RELATIVE ADVANTAGES AND DISADVANTAGES OF THE PRINCIPAL TYPES OF EARTH ELECTRODES 23 2-2. SIZE OF MULTIPOINT GROUND SYSTEM CABLES 71 2-3. MINIMUM TORQUE REQUIREMENTS FOR BOLTED BONDS 87 2-4. COMPATIBLE GROUPS OF COMMON METALS 91 2-5. BOND PROTECTION REQUIREMENTS 91 2-6. PROTECTIVE FINISHES FOR BOND MEMBERS 93 2-7. METAL CONNECTIONS FOR ALUMINUM AND COPPER JUMPERS 95 2-8. ATTENUATION CORRECTION FACTORS FOR REINFORCING STEEL 106 2-9. RELATIVE CONDUCTIVITY AND RELATIVE PERMEABILITY OF COMMON METALS 115 2-10. FREQUENCY OF TRANSIENT OCCURRENCES 130 2-11. PARAMETER FOR DIRECT LIGHTNING STRIKE CURRENT 133 2-12. PEAK CURRENTS FROM DIRECT LIGHTNING STRIKES 134 2-13. SURGE AMPLITUDES 135 2-14. SURGE OCCURRENCE, HIGH-INCIDENT LIGHTNING AREAS 143 2-15. SURGE OCCURRENCES, LOW-INCIDENT LIGHTNING AREAS 144 2-16. GENERALIZED CHARACTERISTICS FOR SURGE ARRESTERS BY TYPE. 146 2-17. TYPICAL MAXIMUM CLAMP VOLTAGE FOR SPARK GAP ARRESTERS 149 2-18. ZNR TYPE DEVICE (MOLDED CASE TYPE) TYPICAL CHARACTERISTICS 150 2-19. HIGH ENERGY ZNR SURGE ARRESTER TYPICAL CHARACTERISTICS 152 2-20. TEST RESULTS FOR PARALLEL-CONNECTED ZNR 152 2-21. TRANSIENTS PROJECTED TO OCCUR ON EXTERNALLY EXPOSED LINE IN HIGH-LIGHTNING AREA OVER 10-YEAR PERIOD 157 2-22. MINIMUM NO. OF TWISTS FOR POWER AND SIGNAL CONDUCTORS 173

3-1. SURVEY EQUIPMENT REQUIRED 189

3-1. SURVEY EQUIPMENT REQUIRED 189

4-1. LOW FREQUENCY PROPERTIES OF STANDARD SIDES OF HONEYCOMB 260 4-2. TRANSIENT SURGES, LINE-TO-GROUND, PROJECTED TO BE REFLECTED ACROSS ELECTRONIC EQUIPMENT BY SECONDARY AC SURGE SUPPRESSOR OVER A 10-YEAR PERIOD . 279 4-3. TRANSIENT SURGES, LINE-TO-LINE, PROJECTED TO BE REFLECTED ACROSS ELECTRONIC EQUIPMENT BY SECONDARY AC SURGE SUPPRESSOR OVER A 10-YEAR PERIOD (UNGROUNDED SERVICE ONLY) 279 4-4. TRANSIENTS PROJECTED TO OCCUR IN 10-YEAR PERIOD ON EXTERNALLY-EXPOSED LANDLINES 279

Page xi

CHAPTER 1.GENERAL

CHAPTER 1.GENERAL

1. PURPoSE. This directive describes practices and procedures to provide effective lightning protection, grounding,bonding, shielding, surge and transient protection for FAA facilities and electronic equipment that make up the National Airspace System (NAS). This Order requires compliance with FAA-STD-019, Lightning Protection, Grounding, Bonding, and Shielding for Facilities, and FAA-STD-020, Transient Protection, Grounding, Bonding and Shielding Requirements for Equipment. This mandate provides the recommended grounding, bonding, transient protection and shielding practices in the design of the electrical power distribution and grounding subsystems for both old and new electronic equipment and facilities. It provides guidelines for surveying existing facilities, and recommendations for the correction of deficiencies. Fundamental theory and technical background supporting this order are contained in a FAA Order 6950.20, Fundamental Considerations of Lightning Protection, Grounding, Bonding and Shielding. FAA-STD-019 and FAA-STD-020 provide the standard configuration for new construction, major modification to existing facilities, and new electronic equipment.

2. DISTRIBUTION. This order is distributed to division level in Airway Facilities, Associate Administrator for Research and Acquisition in Washington Headquarters; to branch level at the Mike Monroney Aeronautical Center and the William J. Hughes Technical Center; to branch level in the regional Airway Facilities divisions; and all Airway Facilities System Management Offices.

3. CANCELLATION. Order 6950.19, Practices and Procedures for Lightning Protection, Grounding, Bonding, and Shielding Implementation, dated July 28, i978 is hereby canceled.

4. BACKGROUND. National Airspace System solid-state electronic equipment has been severely damaged by lightning induced surges and transients entering facilities on AC power lines feeding the facility and on externally exposed landlines terminating at electronic equipments. Structures have been damaged by close proximity and direct lightning strikes to the structure. Electromagnetic interference (EMI) has caused electronic equipment to fail to operate properly. There are conflicts with National Fire Protection Association (NFPA) 70, National Electrical Code (NEC), in the electrical installations at some existing facilities and with NFPA 780, Lightning Protection Code, in the installation of the lightning protection system in and on the structures, thereby introducing hazards to personnel safety

and property. Incorrect grounding or the lack of grounding is often the cause of improper operation of the electrical, electronic and lightning protection systems as well as the cause for electromagnetic interference.

a. Cause of Problems. The widespread use of solid-state equipment has increased the frequency of problems due to lightning related incidents. Additionally, solid-state equipment has become more sensitive to noise because of the low operating voltages typical in its use; therefore, effective grounding needs to be maximized for reliable operation. Damage to structures from lightning strikes usually occurs because the structure does not have a physical lightning protection system, or an effective ground system, properly installed and bonded to each other. Most NEC violations exist because of a general lack of knowledge of the requirements of the NEC and its latest changes, and the importance of the NEC installation requirements to the safe operations of the facility.

b. Minimizing Problems. This order provides procedures which will minimize problems caused by poor lightning protection, grounding, bonding and shielding practices. Procedures are also provided for complying with the requirements of the National Electrical Code and the Lightning Protection Code. Chapter 3 provides a survey for use in determining if existing electronic facilities meet the requirements for new facilities, together with procedures for correcting deficiencies when considered necessary.

5. ACTION.

a. The practices, procedures, and design quidance given by Chapter 2 for new electronic facilities and by Chapter 4 for new electronic equipment shall be used to facilitate compliance with lightning protection, grounding, bonding, shielding and surge and transient protection requirements.

b. The survey procedures provided by Chapter 3 shall be used as guidance for identifying and correcting deficiencies at existing electronic facilities and for the Joint Acceptance Inspection (JAI). The inspection procedures provided by Chapter 3 shall be used as guidance for identifying and correcting deficiencies at existing electronic facilities. Where applicable, the design checklists of Appendix 1 may be utilized for the inspections at existing facilities to verify the integrity and effectiveness of the various systems." The inspection checklists of Appendix 3 may be used to assist personnel in determining the adequacy of the lightning and the lightning induced surge and transient protection systems, and the

various grounding systems (earth, power, and electronic). It may also be used in aid and guidance in the JAI.

6. DEFINITIONS. The definition for some of the words and terminology used in the text of this order are provided in this paragraph." Definitions are included only for words and terminology not of wide and ordinary use, or when the meaning of words is different than ordinary or normal usage.

a. Absorption Loss. The attenuation of an electromagnetic wave as it passes through a shield. This loss is primarily due to induced current and its associated I2R loss.

b. Access Well. A small opening in the earth using concrete, clay pipe or other wall material for the purpose of providing access to earth electrode system connections.

c. Air Terminal. An air terminal is that component of a lightning protection system that is intended to intercept lightning flashes.

d. Ampacity. The current in amperes that a conductor can carry continuously under normal conditions without exceeding its temperature rating.

e. Aperture. An opening in a shield through which electromagnetic energy passes.

f. Arc Voltage. The voltage that appears across the terminals of a spark gap when the spark gap is ionized and in full conduction.

g. Arrester. Component(s), device(s), or circuit(s) used to attenuate, suppress, and conduct surge and transient energy to ground. The terms arrester, suppressor and protector are generally used interchangeably except the term arrester which is used herein for components, devices and circuits at the service disconnecting means.

h. Balanced Line. A line or circuit using two conductors instead of one conductor and ground (common conductor). The two sides of the line are symmetrical with respect to ground. Line potentials to ground and line currents are equal but of opposite phase at corresponding points along the line.

i. Bond. The electrical connection between two metal surfaces established to provide a low-resistance path between them.

j. Bond, Direct. An electrical connection utilizing continuous metal-to-metal contact between the members being joined.

k. Bond, Indirect. An electrical connection employing an intermediate electrical conductor between the bonded members.

1. Bond, Permanent. A bond not expected to require disassembly for operational or maintenance purposes.

m. Bond, Semipermanent. Bonds expected to require periodic disassembly for maintenance, or system modifications, and that can be reassembled to continue to provide a low-resistance connection.

n. Bonding. The joining of metallic parts to form an electrically conductive path which will assure electrical continuity and the capacity to conduct safely any current likely to be imposed between the metallic parts.

o. Bonding Jumper. A reliable conductor to assure the required electrical conductivity between metal parts required to be electrically continuous.

p. Branch Circuit. The circuit conductors between the final over-current device protecting the circuit and the outlet(s).

q. Brazing. A joining process using a filler metal with working temperature above 800 degrees F, but below the melting point of the base metal. The fiiler material is distributed by capillary attraction.

r. Building. The fixed or transportable structure which provides environmental protection.

s. Cabinet. A protective housing or covering designed either for flush or surface mounting with a frame, mat or trim in which a swinging door or doors are or may be hung.

t. Case. A protective housing for a unit or piece of electrical or electronic equipment.

u. Chassis. The metal structure that supports the electrical or electronic components that make up the unit or system.

v. Circular Mil. A unit of area equal to the area of a circle whose diameter is one mil (1 mil = 0.001 inch).

w. Clamp Voltage. The maximum voltage that appears across a surge arrester or transient suppressor when discharging a surge or transient current to ground.

x. Common Mode Voltage. The amount of voltage common to both input terminals of a device.

y. Common Mode Rejection. The ability of a device to reject a signal which is common to both its input terminals.

z. Conducted Interference. Undesired signals that enter or leave an equipment along a conductive path.

aa. Conductor, Bare. A conductor having no covering or electrical insulation.

bb. Conductor, Insulated. A conductor encased within material of composition and thickness that is recognized by the National Electrical Code as electrical insulation.

cc. Conductor, Main, Lightning. A conductor intended to be used to carry lightning currents between air terminals and ground terminals. See Roof Conductors and Down Conductors, Lightning hereinafter.

dd. Coupling, Conducted. Energy transfer through a conductor.

ee. Coupling, Free-Space. Energy transfer via electromagnetic fields not in a conductor.

ff. Crowbar. Crowbar is the method of shorting a surge current to ground in surge protection devices. This method provides protection against more massive surges than other types, but lowers the clamping voltage below the operational voltage of the electronic equipment causing noise and operational problems. It also permits a follow current which can cause damage.

gg. Cutoff Frequency. The frequency below which electromagnetic energy will not propagate in a waveguide.

hh. Degradation. A decrease in the quality of a desired signal (i.e., decrease in the signal-to-noise ratio or an increase in distortion) or an undesired change in the operational performance of an equipment as the result of interference.

ii. Discharge Voltage. Same as clamp voltage.

jj. Down Conductor, Lightning. Part of the main conductor installation of a lightning protection system that connects the roof conductors and air terminals to the ground electrode system.

kk. Earth Electrode System. A network of buried electrically interconnected ground rods, plates, pipes, mats, or grids installed for the purpose of establishing a low resistance contact with earth. (Also known as the Grounding Electrode System).

ll. Electric Field. A vector field about a charged body. Its strength at any point is the force which would be extended on a unit positive charge at that point.

mm. Electromagnetic Compatibility (EMC). The capability of equipment or systems to be operated in their intended operational environment at designed levels of efficiency without causing or receiving degradation owing to unintentional interference.EMC is the result of an engineering planning process applied during the life cycle of equipment. The process involves careful considerations of frequency allocation, design, procurement, production, site selection, installation, operation, and maintenance.

nn. Electromagnetic Interference (EMI). Any emitted, conducted, radiated or induced voltage which degrades, obstructs, or repeatedly interrupts the desired performance of electronic equipment.

oo. Electromagnetic Pulse (EMP). A large impulsive type electromagnetic wave generated by man-made or natural explosions.

pp. Electronic Multipoint Ground System. An electrically continuous network for high frequency electronic systems consisting of interconnected ground plates, equipment racks, cabinets, conduit, junction boxes, raceways, duct work, pipes and other normally non-current carrying metal elements. It includes conductors, jumpers and straps that connect individual items of electronic equipment to the multipoint ground system. This system is most effective for frequencies above 100 kHz.

qq. Electronic Single Point Ground System. A single point reference in the facility for low frequency signals, which are installed in a trunk and branch arrangement to prevent conductive loops in the system. Isolated from ail other ground systems except for the interconnection, where applicable, to the electronic multipoint ground system at the main ground plate. The single point ground system consists of insulated conductors, copper ground plates mounted on insulated stands, and insulated

ground plates, buses or signal ground terminals in the electronic equipment which are isolated from the frame of the equipment. This system is most effective for signals below 100 kHz. Lightning protection is complicated by the use of single point grounding schemes.

rr. Equipment Grounding Conductor. The conductor used to connect non-current carrying metal parts of equipment, raceways, and other enclosures to the system grounded conductor and/or the grounding electrode conductor at the service disconnecting means or at the source of a separately derived system. This conductor must be routed in the same raceway or cable as the phase and neutral conductors.

ss. Facility Ground System. Consists of the complete ground system at a facility including the Earth Electrode System, Electronic Grounding Systems (Electronic Multipoint Ground System and/or Electronic Single Point Ground System), Fault Protection Grounding System (Grounding Electrode Conductor and Equipment Grounding Conductors), and the Lightning Protection System.

tt. Far Field. The region of the field of an antenna where the radiation field predominates and where the angular field distribution is essentially independent of the distance from the antenna.

uu. Fault. An unintentional short-circuit or partial short-circuit (usually of a power circuit) between energized conductors or between an energized conductor and ground.

vv. Ground. A conducting connection, whether intentional or accidental, between an electrical or electronic circuit or equipment and the earth, or to some conductive body that serves in place of the earth.

ww. Grounded Conductor (neutral). A system or circuit conductor that is intentionally grounded at the service entrance disconnecting means or at the source of a separately derived system.

xx. Grounded Effectively. Permanently and continuously connected to earth from circuits, equipment, and conductor enclosures through a ground connection having sufficient ampacity to conduct safely any fault current likely to be imposed on it, and having sufficiently low impedance to limit the voltage to ground and to facilitate the operation of the circuit protective devices in the circuit.

yy. Grounding Conductor. A conductor used to connect equipment or the grounded circuit of a wiring system to a grounding electrode or electrodes. (Note: In this Order, grounding conductors, not related to or not to be used as part of the electrical system grounding as required by the NEC, are used for the electronic equipment grounding systems.)

zz. Grounding Electrode Conductor. The conductor used to connect the grounding electrode system to the equipment grounding conductor and/or to the grounded conductor of the circuit at the service disconnecting means or at the source of a separately derived system.

aaa. Grounding Electrode System. See Earth Electrode System (Par. 6 kk).

bbb. Interface. Any electrical connection (encompassing power transfer, signaling, or control functions) between two or more items of equipment or systems.

ccc. Isokeraunic. Statistics showing average annual number of days with thunderstorms.

ddd. Isolation. Physical and electrical arrangement of the parts of equipment, system, or facility to prevent uncontrolled electrical contact within or between the parts.

eee. Landline. Any conductor, line, or cable installed externally above or below grade to interconnect electronic equipment in different facility structures or to connect externally mounted electronic equipment.

fff. National Electrical Code (NEC). The purpose of this code is the practical safeguarding of persons and property from hazards arising from the use of electricity. This code covers the installation of electrical conductors and equipment within or on buildings and other structures including mobile units and floating buildings; and other premises such as yards, parking and other lots. It is sponsored by the National Fire Protection Association (NFPA 70) and has been approved by the American National Standards Institute (ANSI).

ggg: Near Field. The region of the field immediately surrounding an antenna where the inductive and capacitive fields predominate. In this region, the angular distribution of the field varies with distance from the antenna.

hhh. Neutral. The AC power system circuit conductor that is intentionally grounded on the supply side of the service

disconnecting means. It is the grounded conductor of a single phase, 3-wire system or of a three phase, 4-wire system. This conductor is identified by white or natural gray insulation along its entire length, or where larger than No. 6 AWG, by white markings at its terminations and at all accessible places such as pull boxes. (Note: Green insulated conductors are not to be re-identified and used as the neutral conductor.)

iii. Overshoot Voltage. The fast rising voltage that appears. across transient suppressor terminals before the suppressor turns on (conducts current) and clamps the input voltage to a specified level.

jjj. Penetration. The passage through the partition or wall of an equipment or enclosure by a wire, cable, or other conductive object.

kkk. Plane Wave. An electromagnetic wave which predominates in the far field region of an antenna, and with a wavefront which is essentially in a flat plane. In free space, the characteristic impedance of a plane wave is 377 ohms.

1ll. Radiation resistance. The resistance which, if inserted in place of an antenna, would consume the same amount of power that is radiated by the antenna.

mmm. Radio Frequency Interference (RFI). Synonymous with electromagnetic interference.

nnn. Reference Plane or Point, Electronic Signal (Signal Ground). The conductive terminal, wire, bus, plane, or network which serves as the relative zero potential for all electronic signals referenced thereto.

ooo. Reflection Loss. The portion of the transition loss, expressed in decibels (dB), that is due to the reflection of power at a barrier or shield. Reflection loss is determined by the magnitude of the wave impedance inside the barrier relative to the wave impedance in the propagation medium outside the barrier.

ppp: Response Time. The time required for a surge arrester or transient suppressor to turn on (conduct) and clamp surge or transient after turnon or sparkover voltage is impressed across the device terminals

qqq. Reverse Standoff Voltage. The maximum voltage that can be applied across a surge arrester or transient suppressor without causing the arrester or suppressor to turn on and

conduct. Sometimes referred to as maximum operating voltage, primarily for spark gap arresters. Also referred to as maximum allowable voltage for metal oxide varistor (MoV) devices.

rrr. RF-Tight. Offering a high degree of electromagnetic shielding effectiveness.

sss. Roof Conductor (Lightning). The lightning protection system conductors on the roof of a structure that interconnect all the air terminals to form a two way path to ground from the base of each air terminal.

ttt. Secondary Lightning Bonding Conductor. A conductor used to bond a metal object within the zone of protection, that is subject to potential build-up different from the lightning current, to the lightning protection system.

uuu. Shield. A housing, screen or cover which substantially reduces the coupling or electric and magnetic fields into or out of circuits or prevents the accidental contact of objects or persons with parts or components operating at hazardous voltage levels.

vvv. Shielding Effectiveness. A measure of the reduction of attenuation in the electromagnetic field strength at a point in space caused by the insertion of a shield between the source and that point.

www. Signal Return. A current-carrying path between a load and the signal source. It is the low side of the closed loop energy transfer circuit between a source-load pair.

xxx. Supporting Structures, Electrical. Non-electrified conductive structural elements near energized electrical conductors such that a reasonable possibility exists of accidental contact with the energized conductor. Examples are conduit and associated fittings, junction and switch boxes, cable trays, electrical and electronic equipment racks, electrical wiring cabinets, and metallic cable sheaths.

yyy. Transducer. A device which converts the energy of one transmission system into the energy of another transmission system.

zzz. Thunderstorm Day. A local calendar day on which thunder is heard.

aaaa. Transient Suppressor. Component(s), device(s), or circuit designed attenuate, suppress or divert conducted transient(s) and surge energy to ground to protect electronic equipment.

bbbb. Turn-On Voltage. The voltage level that must be applied across the terminals of an arrester or suppressor to cause the device to turn on and conduct current. For solid-state and Mov devices, the specified voltage is normally that required to cause the device to conduct 1 miliiampere of current. The turn-on voltage for Mov devices is normally specified as a varistor voltage. The turn-on voltage for spark gaps is normally referred to as sparkover voltage, and varies greatly for different types of spark gaps.

cccc. Undesired Signal. Any signal which tends to produce degradation in the operation of equipments or systems.

dddd. Wave Impedance. The ratio of the electric field strength to the magnetic field strength at the point of observation.

eeee. Zinc Oxide Nonlinear Resistor (ZNR). A specific type of metal oxide varistor (Mov) with a specified voltage-current relationship.

7. AUTHORITY TO CHANGE ORDER. The Program Director, NAS Transition and Implementation (ANS-1), shall approve all changes to this order.

8. - 10. RESERVED.

CHAPTER 2. NEW FACILITIES DESIGN CRITERIA

CHAPTER 2. NEW FACILITIES DESIGN CRITERIA

11. GENERAL. This chapter presents the design, implementation, test, and check-out practices and procedures for effective grounding, lightning protection, bonding, shielding and lightning-induced surge and transient protection in a new facility. A new facility is one of new construction or one that is to undergo major renovation. The major elements of the facility covered here are the earth electrode system, power system fault protection network, lightning protection system, the electronic system grounding networks, i.e., single point and multipoint grounding systems, overall facility grounding system, facility shielding, system bonds, and lightning-induced surge and transient protection methods. Designs and construction steps for these eight elements are contained in Sections 1 through 6.

Supplemental measures that need to be incorporated into a new facility are contained in Sections 7 through 9. Reduction in common-mode and instrumentation noise problems in a facility are presented in Section 7. The special construction practices recommended to reduce facility vulnerability to the electromagnetic pulse (EMP) threat are contained in Section 8. And finaliy, new facility inspection and test procedures are provided in Section 9 to assist in verifying proper execution of recommended practices and procedures, and in establishing a performance baseline for comparison against future measurements.

To obtain optimum performance of electronic equipment, while providing proper protection against power system faults (as per NFPA 70, National Electrical Code) and lightning strikes (as per NFPA 780, Lightning Protection Code), thorough consideration must be given to the grounding system for the buiiding; to the bonds needed and the method of their implementation; and to the shielding needed throughout the building for personnel safety and equipment interference control. For a new facility, the requirements in each of these areas are defined and appropriate design steps set forth to assure that the necessary measures are incorporated into the final construction.

Page 12 Chap 2 Par11

SECTION 1. EARTH ELECTRODE SYSTEM

SECTION 1. EARTH ELECTRODE SYSTEM

12. GENERAL. The earth electrode system (grounding electrode system) establishes the electrical connection between the facility and the body of the earth. This connection is necessary for lightning protection, power fault protection, and the minimization of noise between interconnected facilities. The system should be tailored to reflect the characteristics of the site and the requirements of the facility. It must be properly installed and steps taken to assure that it continues to provide a low resistance connection throughout the life of the structure. To achieve these objectives, first determine the electrical and physical properties of the site, design an electrode system appropriate for the site, install the system in accordance with the recommended procedures, and finally, measure the earth resistance of the system to verify that it meets the recommended goals or design specifications.

13. DETERMINATION OF SITE PARAMETERS. Before beginning the design of the Earth Electrode System, conduct a survey of the site where the earth electrode system is to be installied. Through this survey, determine the resistivity of the soil, identify significant geological features, gather information on architectural and landscape features which may influence the design of the system, and review local climate effects. If possible, conduct this survey in advance of the final site selection in order to avoid particularly troublesome locations.

a. Soil Resistivity. Soil (earth) resistivity is the resistance of a cubic centimeter of earth measured between opposite surfaces expressed in ohm-centimeters. Soil resistivity varies due to the type of soil, its temperature, moisture content, compactness and homogeneity. Resistivity will vary as a function of seasonal changes such as freezing, or lengthy dry periods. Mixtures of materials in the soil (sand, loam, gravel, or rock), may be encountered which will cause the resistivity of the soii to vary. The four-probe method is the most accurate method in practice for measuring the resistivity of large volumes of undisturbed earth. This wili allow for mapping soil resistivity to specific depths, as determined by the spacing distances between the probes. It will also allow for locating the depth of the most homogeneous, moist layer of the soil.

b. Soil Resistivity Measurement. A four-terminal earth resistance test set is used to measure the soil resistivity. The measurement shall be made a minimum of 72 hours following measurable rainfall. In this test four small probes, normally furnished with the earth resistance test set, are used. These probes shall all be driven to the same depth and shall be equally

Chap 2 Page 13 Par12

spaced in a straight line as indicated in Figure 2-1. Four separate lead wires shall be connected from the four probes to the four terminals on the instrument, hence the name,""Four Probe" or "Four Terminal" Method. The wires are generally connected to the probes with clamps. The depth of the penetration (B) of the short probes must be small in comparison to the distance (A) between the probes. For convenience, a distance of 10 feet (3 meters) and a depth of penetration of not

EARTH RESISTANCE

EARTH RESISTANCE

TEST SET

C1 P1 P2 C2

C1 C2

P1 P2

111 EARTH

A = PROBE SPACING D = DEPTH AT WHICH

B = DEPTH OF RESISTIVITY IS

PENETRATION < A/20 DETERMINED = A

FIGURE 2-1. MEASUREMENT OF SOIL RESISTIVITY

more than 6 inches are recommended as a start. For small sites up to 2500 square feet (232 square meters), make at least one measurement at the center of the site and at each of the four corners of the site. Figure 2-2 shows this for a square site, 50 feet (15 m) on each side. These measurements should be made at distances between probes of 10, 20, 30, and 40 feet. Drive a stake or marker at the location shown (Figure 2-2). Position the potential and current probes in a straight line with the stake or marker centered between the probes. Make a resistance

FIGURE 2-1. MEASUREMENT OF SOIL RESISTIVITY

measurement at each of the locations shown and record the resistance. The average of the five readings for each spacing of probes is used to calculate the resistivity for the soil of the site. For large areas, make measurements every 100 to 150 feet (30 to 45 meters) over the site area. Include in the site area the location of the support elements such as the transformer banks, towers, engine-generator buildings, etc. Choose a sufficient number of test points to give an indication of the relative uniformity of the soil composition throughout the area. For each spacing of probes, a value (R ohms) will be recorded. (NoTE: If the probes are not available with the test set, four metal rods (of steel, copper, or aluminum) 1/4 to 3/8 inch (6 to 10 mm) in diameter and 12 to 18 inches (30.5 to 46 cm) in length may be used.)

STAKE8 OA MARKERS

STAKE8 OA MARKERS

P1 P2 G2 5o

-50

FIGURE 2-2. RESISTIVITY DETERMINATION OF A SMALL SITE

The following formula applies where the probe depth is kept small in comparison to the distance between the probes:

p = 2πAR

where p is the average soil resistivity in ohm-centimeters (ohmcm) to a depth A, which is the spacing of the probes in centimeters (cm), π is the constant 3.1416, A is the distance between probes in cm and R is the resistance reading of the test instrument in ohms.

FIGURE 2-2. RESISTIVITY DETERMINATION OF A SMALL SITE

c. Soil Resistivity Calculations. Assume that the distance between probes is 20 feet (610 cm) and that a resistance of 2 ohms is measured. The resistivity can be calculated from the above formula. Substitute the values of 3.1416 for π, A = 610 for 20 feet in cm, and R = 2 ohms.

p = 2πA x R p = 2 x 3.1416 x 610 x 2 = 7662 ohm-cm.

The reading obtained indicates the average soil resistivity in the immediate vicinity of the test area, at a depth of 20 feet.

d. Resistivity Profile. The information above may be used in determining what type of earth electrode system is most appropriate for the facility (complex, building, tower structure, transformer bank, substation, etc.). A plot of either ohm-cm, or R (ohms) versus depth or spacing can be used to determine the best rod lengths to be used. The soil resistivity is considered low when less than 2000 ohm-cm., average when between 2000 and 20,000 ohm-cm., and high when greater than 20,000 ohm-cm. The higher the soii resistivity, the more complex (and expensive) wiil be the earth electrode system necessary to achieve the desired resistance. Thus, take maximum advantage of the low resistivity soils wherever they exist.

e. Calculation of Earth Resistance. From the soil resistivity calculations and the plot layout, the lowest achievable resistivity (p) value can be selected and the resistance of a single rod driven to a depth determined by the spacing between the probes on the plot layout. The resistance of a single driven ground rod can be approximately calculated from the formula:

where R, is the resistance of a single ground rod in ohms, p is the soii resistivity in ohm-cm, l is the length of the ground rod in cm and d is the diameter of the ground rod in cm. Thus if the

design goal is a resistance of 10 ohms, the total number of ground rods spaced to fit the system, but spaced no closer together than the length of one ground rod can be approximated from the formula:

Rt B sK or,

where Rt = total (Goal) resistance, Rs = resistance of a single ground rod, N is the number of ground rods and K is the resistance ratio. The resistance ratio (K) can be determined from Figure 2-3. If it is desired to include the effects of the buried interconnecting conductor and the mutual effects of rod to wire, use the equations in FAA Order 6950.20.

10

7

2e

31 46 2 56 8=10€

10 20 30 40 50 8 70 8 NUMBER OF RODS IN ARRAYN

FIGURE 2-3. RATIO OF THE ACTUAL RESISTANCE OF A ROD ARRAY TO THE IDEAL RESISTANCE OF N RODS IN PARALLEL

14. GEOLOGICAL EFFECTS IDENTIFICATION.

a. Geological Features. Identify the significant geological features of the site. Specifically, attempt to establish:

(1) Distribution of major soil types to include the locations of sand and gravel deposits.

(2) Major rock formations.

(3) Presence of water sources to include underground streams.

(4) Depth of the water table.

b. Information Source. Utilize test borings, on-site inspections, studies of local maps, and interviews with local construction companies, well drillers, power companies, and other local personnel to obtain the desired information.

c. Evaluation. Evaluate the information provided by these sources for indications of particularly troublesome, or particularly helpful, characteristics that may influence the design or installation of the earth electrode system of the faciiity.

15. PHYSICAL FEATURES. Locate and identify other physical features that will influence the general placement of the earth electrode system, the location of the test and access points, physical protection requirements, and the cost of materials and installation. For example, indicate on the general site plan:

a. The planned physical layout of the building or structure.

b. Locations of paved roads and parking lots.

c. Drainage, both natural and man-made.

d. The location of buried metal objects such as pipes and tanks.

16. LOCAL CLIMATE.

a. Review local climatic conditions and determine the annual amount and seasonal distribution of rainfall, the relative incidence of lightning, and the depth of freezing (frostline) typical for the area.Obtain the rainfall and frostline

information from the local weather service; project the relative lightning incidence from the isokeraunic maps given in Order 6950.20, Fundamental Considerations of Lightning Protection, Grounding, Bonding and Shielding.

b. Record the data and make it a part of the facility files for the site. Use the information to aid in the design of the earth electrode system for the facility to be constructed at the site.

17. DESIGN PROCEDURE.

a. Selection of Electrode Configuration. Determine what type of electrode system is most appropriate for the facility (complex, building, structure, transformer bank, substation, etc.). Establish the primary functional requirements to be met by the electrode system. For example:

(1) Lightning. For a facility located in an area of high lightning incidence or a high degree of exposure to lightning, or both, the earth electrode system must safely dissipate the lightning energy without melting conductors or overheating the soil.

(2) Fault Current Magnitude. Where very large fault currents are likely (in power substations, for example), the electrode system must be capable of restraining hazardous step voltage levels, and must be capable of transporting the current into the soil while maintaining temperatures to less than the boiling point of water.

(3) Impulse Impedance Characteristics. Where EMP protection is necessary, low impulse impedance should be incorporated into the electrode system." Refer to Chapter 2, Section 8.

(4) Mobility. Mobile facilities or temporary transportable facilities will generally not justify the installation of an extensive fixed electrode system. For such facilities, install only a basic system capable of providing the minimum acceptable lightning and personnel fault protection. Refer to Section 3.

(5) Resistance. The desired value for the resistance of the earth electrode system is 10 ohms or less unless otherwise required in the design criteria. In high resistance soils this may not be economicaily feasible. In cases where the soil resistivity is very high, but will allow for deeper driven rods, the electrode system should be comprised of deeper buried rods

driven to reach the low resistivity soil levels. The minimum spacing of rods shall not be less than the driven length of the rods. Where the soil is not suitable for the installation of driven rods, such as in rock formations, vertical plates, grids or horizontal conductors of sufficient sizes and quantities shall be installed and spaced so that any current imposed on the system will be dissipated over a large area.

b. Evaluation of Local Conditions.

(1) Soil Resistivity. Is soil resistivity low (<2000 ohm-cm), average (2000-20,000 ohm-cm) or high (>20,000 ohm-cm)? The higher the soil resistivity, the more complex (and expensive) will be the electrode system necessary to achieve i0-ohms resistance. Thus, take maximum advantage of low resistivity soils wherever they exist.

(2) Moisture Content. Is the water table near the surface or far below grade, and is it subject to large seasonal variations? Design the earth electrode system so that it makes and maintains contact with soil that stays damp or moist year round if at all possible. Penetration of the permanent water table is highly desirable.

(3) Frostline. How deep does the frostline extend, even during coldest periods? The resistivity of soil rises greatly as the soil temperature drops below 32 degrees Fahrenheit. Thus for maximum stability of electrode resistance, the system should penetrate far enough into the soil so that the contact is always maintained with unfrozen soil. In permafrost, fault protection must be provided through the use of metallic returns accompanying the power conductors to insure the existence of a return path to the transformer or generator. Personnel protection in permafrost requires an even greater emphasis on the bonding of all metal objects subject to human contact together and to the power system neutral. Because of the high resistance of permafrost, stray earth currents can be expected to be minimal with consequently reduced concern with interfacility power frequency noise problems. In the event that earth-current-related noise problems exist, the common-mode rejection techniques should be applied. Refer to Order 6950.20.

(4) Rock Formations. Are major rock formations near the surface and are they large enough to influence the design and layout of the electrode system? In regions of shallow bedrock, vertical ground rods may not be usable and horizontal grids, wires, or plates, sloped downward away from the facility, must be used. Large rock outcroppings or subsurface boulders may force the alternate routing of conductors or the placement of rods.

There is no need to incur the expense of drilling holes in rock to insert rods or lay wires because the resistivity of rock is so high that generally the rods or wires would be ineffective.

(5) Architectural Layout. Design the electrode system so that it will not be materially influenced by the weather shielding effects of parapets or overhangs on the building. Lightning down conductor placement and routing will frequently be influenced by architectural considerations. Design the electrode system to accommodate such consideration by providing convenient connection points to ground rods in the earth electrode system near the lightning protection system down conductors to avoid any lengthy extensions between the down conductors and the effective grounding point. Configure the electrode system such that convenient connections are possible between the earth electrode system and the power grounding conductors and signal ground system conductors originating inside the facility.

(6) Landscape Features. Locate ground system conductors under sodded areas or those otherwise covered with vegetation. Locate conductors to take maximum advantage of the wetting effects of run-off or drainage water from the roof, parking lots, etc. Try to avoid placing major portions of the earth electrode system under extensive paved areas such as paved walkways, roads and parking lots.

c. Electrode Type. Consider the relative advantages and disadvantages given in Table 2-1, and choose a basic type of electrode most appropriate for meeting the functional requirements of the facility at the site under construction.

d. Cost. Estimate the relative costs to meet the objectives with the different types of configurations. Include the cost of materials, installation costs, and relative maintenance and upgrading costs.

18. ALTERNATE CONFIGURATIONS. Non-ideal sites will frequently be encountered. For example, large rock formations may be present which prevent the uniform placement of ground rods around the site; bedrock may be relatively near the surface; the water level may drop to several feet below grade; the soil resistivity may be very high; or architectural and landscape requirements may preclude locating ground rods at particular points. In such cases, modify the electrode configuration to conform to the constraints while achieving the desired resistance. Typical suggested alternatives are:

a. Change Number of Ground Rods. In many cases, fewer rods could be used and still meet a required earth resistance goal.

Thus, if rock outcroppings were present at certain points around the perimeter, it may be permissible to omit some of the rods. On the other hand, if the soil resistivity is very high, more ground rods would be necessary.

b. Use Longer Ground Rods. Ground rods longer than 10 feet (3 m)(can be realized by assembling 10-foot sections) may be used in high-resistivity soil in place of a larger number of i0-foot ground rods. Where the ground water table is greater than 10 feet below the surface at any season of the year or where the frostline is greater than 10 feet, use the longer rods to maintain contact with the permanent moist, unfrozen soil. When longer rods are used, the spacing between rods should be increased so as to maintain minimum spacing between rods and the length of the rods should be preferably two to three times the length of the ground rod.

c. Use Horizontal Wires and Vertical Plates Instead of Vertical Rods. Where bedrock or other obstacles prevent the effective use of vertical rods, horizontal wires, vertical plates, grids, or radials should be used. (See Order 6950.20 for design data and equations.) Rectangular grids should also be used in substations or any other locations where very high ground currents may be encountered. Star radials are required for EMP grounding and as antenna counterpoises. Radials may be desirable if the proposed ground rod location is in an area of high resistivity. Where horizontal wires radials are used, they shall be installed so as to slope downward away from the structure. Where plates are used, they shall be installed to be vertical. Where this is not feasible, the plates shall be installed to slope to the maximum extent practicable.

d. Lower the Soil Resistivity Through Chemical Enhancement (Salting). Where the above alternatives are not possible or are not cost effective, chemical enhancement is frequently the only choice left. Any chemical enhancement used must comply with local environmental regulations.

19. DESIGN GUIDELINES.

a. At each facility supplied by commercial electric power, at least one ground rod of the Earth Electrode System should be installed near the service disconnecting means. If the transformer is located on the site, a bare wire sized the same as the counterpoise wire of the Earth Electrode System, normally No. 4/0 AWG, should also interconnect the ground rod driven adjacent to the transformer with a ground rod in the related facility Earth Electrode System.

07/01/96

6950.19A

TABLE 2-1. RELATIVE ADVANTAGES AND DISADVANTAGES OF THE PRINCIPAL TYPES OF EARTH ELECTRODES

TYPE

Vertical Rods

Horizontal Grid

Plates

Horizontal Wires (Radials)

Incidental Electrodes (Utility pipes, building foundations, buried tanks)

ADVANTAGES

Straightforward design. Easiest to install (particularly around an existing facility). Hardware readily available. Can be extended to reach water table.

Minimum surface potential gradient. Straightforward installation if done before construction. Can achieve low resistance contact in areas where rock formations prevent use of vertical rods. Can be combined with vertical rods to stabilize resistance fluctuations.

Can achieve low-resistance in limited areas.

Can achieve low-resistance where rock formations prevent use of vertical rods. Low impulse impedance. Good rf counterpoise when laid in star pattern.

Can exhibit very lowresistance (if electrically continuous). Generally lowest initial cost (borne by others).

DISADVANTAGES

High impulse impedance. Not useful where large rock formations are near surface. Step voltage on earth surface can be excessive under high fault currents or during direct lightning strike.

Subject to resistance fluctuation with soil drying if vertical rods are not used.

Most difficult to install.

Subject to resistance fluctuations with soil drying.

Little or no control over future alterations.

b. For lightning protection purposes, very small facilities (ie. less than 10 sq ft) located in areas of low earth resistivity and very low lightning incidence may require only one ground rod. In regions of iow earth resistivity and high

Chap 2 Par 19

lightning incidence and at those facilities having structural extensions or equipment protrusions (such as antenna elements or towers) extending above the surrounding terrain, a minimum of two ground rods located on opposite corners of the facility should be installed.

c. Most installations will require more than two ground rods. A type of configuration similar to that shown in Figure 2-4 is adequate for most facilities.

GROUNDRODS COUNTERPOISE

GROUNDRODS COUNTERPOISE

OUTLINE OF STRUCTURE

FIGURE 2-4. TYPICAL EARTH ELECTRODE SYSTEM CONFIGURATION FOR RECTANGULAR SHAPED FACILITY

The number of ground rods actually required at a given location will be determined by the resistivity of the soil and the configuration of the installation. Ten-foot (3 m) ground rods installed at 20-foot (6 m) intervals around the perimeter of the structure provide good utilization of the effective radius of the rod while providing several points of contact with the earth. If longer rods are required to penetrate the lowest resistance as

FIGURE 2-4. TYPICAL EARTH ELECTRODE SYSTEM CONFIGURATION FOR RECTANGULAR SHAPED FACILITY

determined by the soil survey (see Paragraph 12), greater spacings shall be employed. The nominal spacing between ground rods should be between two and three times the length of the rod and in no case shall the spacing between ground rods be less than the length of the ground rod. Spacings may be predetermined by the size of the electrode system. A ground rod shall be installed at each corner of the earth electrode system, and in between as required.

d. Ground rods and their installation shall be in accordance with the following:

(1) Material and Size. Ground rods shall be of copper or copper clad steel and shall be a minimum of 10 feet (3 m) in length and 3/4-inch (19 mm) in diameter. Where corrosive soils are not compatible with copper or copper clad ground rods stainless steel rods may be used. If cladded rods are used, the copper cladding shall not be less than 1/64 inch (0.4mm) in thickness. Where deeper penetration is required, either additional ground rods exothermically butt welded together or sectionalized ground rods, complete with couplings and driving bolts (studs), shall be used. Ground rods shall bear the manufacturer's name, trade mark, and catalog number. Longer rods may be used to penetrate the frost line, or in high resistivity soil, in lieu of interconnecting 10-foot rods.

(2) Spacing. Ground rods shall be as widely spaced as practical, but in no case spaced closer together than the length of one ground rod. Nominal spacing between ground rods should be between two and three times the rod length.

(3) Location. Ground rods shall be located 2 to 6 feet (0.6 to 2 m) outside the foundation or exterior footings of the structure. At buildings with overhangs, the ground rods shall be located beyond the dripline of the structure to insure that rain, snow, and other precipitation wets the earth around the ground rods.

(4) Interconnection of ground rods. Ground rods shall be interconnected by means of a buried, bare, No. 4/0 AWG copper cable. The cable shall be buried at least two feet six inches below the finished grade level and the connections to the ground rods shall be made with exothermic welds. The interconnecting cable shall close upon itself forming a complete loop (counterpoise) with the ends exothermically welded together. Other connections to the ground rods and to the earth electrode system will be as indicated in other sections of this order.

e. For facilities which do not conform to a rectangular or square configuration, lay out the rod field to generally follow the perimeter of the structure as illustrated in Figure 2-5. Note that a ground rod is installed at each corner or change in direction of the earth electrode system.

OUTLINE OF STRUCTURE

OUTLINE OF STRUCTURE

COUNTERPOISE

GROUND RODS

FIGURE 2-5. ELECTRODE CONFIGURATION FOR IRREGULAR SHAPED FACILITY

f. Where two or more structures or facilities are located in the same general area and are electrically interconnected with AC power, signal, control and/or monitor circuits, either provide a common ground rod counterpoise system, or interconnect the separate earth electrode systems with buried bare copper cables sized the same as the counterpoise cable of the earth electrode systems.

FIGURE 2-5. ELECTRODE CONFIGURATION FOR IRREGULAR SHAPED FACILITY

A common example of an installation where two separate structures are involved is a radar or communications site where the equipment shelter is adjacent to the antenna tower. Signal cables, both coaxial and waveguide, control cables (electronic and/or power, and AC power conductors typically run between the tower and the shelter. The tower being taller than the shelter, is more susceptible to lightning strikes. To minimize voltage

differentials between the two structures, the facilities should effectively share a common ground. Separate structures spaced closer than 15 feet (4.5 m) should have a common-rod system installed that encircles both facilities as shown in Figure 2-6a. When the separation is between 15 and

TOWER OR AUXILIAAY STRUCTURF

TOWER OR AUXILIAAY STRUCTURF

D7

MAIN STHUCTURE MAIN STRUCTURE

L SEPARATION LESS THAN 15' (4.5 METERS) b. SEPARATION 15' TO 30 (4.5 TO 9 METERS)

FIGURE 2-6. ELECTRODE CONFIGURATION FOR ADJACENT STRUCTURES

30 feet (4.5 and 9 m), they may share a common side of the earth electrode systems as shown in Figure 2-6b. Figure 2-7 shows the recommended arrangement when the separation is greater than 30 feet (9m). A typical site installation involving three widely separated structures, such as a Radar Installation, is illustrated in Figure 2-8. The counterpoise wire noted may also serve as a guard wire for the buried power and electronic cables.

FIGURE 2-6. ELECTRODE CONFIGURATION FOR ADJACENT STRUCTURES

g. There may be a number of incidental, buried, metal structures in the vicinity of the earth electrode system. These structures should be connected to the system to reduce the danger of potential differences during lightning strikes or AC power faults. Their connection will also reduce the resistance to the earth of the electrode system. Such additions to the earth electrode system may include the rebar in concrete footings, and buried tanks and pipes. These objects shall be connected to the earth electrode system by a bare copper cable not smaller than No. 2 AWG utilizing exothermic welds or FAA approved type connectors. Exothermic welds shall not be used where hazards may exist, i.e., near fuel tanks.

6950.19A

BURIED CABLE

BURIED CABLE

07/01/96

SEPARATION30'19 METEAS) BURIED CABLE

MAIN STRUCTURE

ELECTRODE CONFIGURATION FOR CLOSELY SPACED

FIGURE 2-7. STRUCTURES

Page 28

Chap 2 Par 19

07/01/96

AIR

6950.19A

CONTROUDISPLAY BUILDING

TERMINALS

DOWN CONDUCTORS

EXOTHERMIC WELD

AUXILIARY STRUCTURE

GROUND RODS

EXOTHERMIC WELD

EXOTHERMIC WELD

AIR TERMINAL

COUNTERPOISE

ANTENNA GROUND ROD

RADOME

EXOTHERMIC WELD CABLE RUN

RADAR SET

RADAR TOWER

RADAR SET

GROUNDING SYSTEM FOR TYPICAL RADAR INSTALLATION

FIGURE 2-8.

Chap 2

Par 19

(1) Where rebar in the footings or foundations is intentionaily designed to be a significant portion of the facility grounding system, the rebar system interconnects shall have a bond resistance of 1 milliohm or less.

GROUNDING SYSTEM FOR TYPICAL RADAR INSTALLATION

(2) Where corrosion problems make it undesirable to ground fuei tanks and piping, an isolating section or bushing must be inserted in lines which feed FAA facilities. When this is accomplished the tank and piping system outside the isolating element need not be grounded. Any metallic pipe which enters the facility must be bonded to the earth electrode system to minimize transient entry.

h. To minimize resistance variations caused by surface drying of the soil and by freezing of the soil during winter and to minimize the possibility of mechanical damage to ground rods, connections, and interconnecting cables, the tops of the ground rods should be at least 1 1/2 feet below the finished grade level. The recommended practices are illustrated in Figure 2-9.

EXOTHERMIC WELD EXOTHERMIC WELD CONNECTION GRADE LEVEL

EXOTHERMIC WELD EXOTHERMIC WELD CONNECTION GRADE LEVEL

18 IN. EXOTHERMIC WEI MIN CONNECTION 30 IN. MIN.

NO.40 AWG COPPER CABLE V ELECTRONIC GROUNDING CABLE 3/4HN X 10-FOOT COPPEA CLAD ROD

FIGURE 2-9. DETAILS OF GROUND ROD/COUNTERPOISE INSTALLATION

i. If the Earth Electrode System is installed after foundations are poured, cables are installed, utility pipes installed, etc., make proper provisions for performing the needed interconnections between the water system piping, lightning down conductors, structural steel, buried lines and cables, and the electrodes.

FIGURE 2-9. DETAILS OF GROUND ROD/COUNTERPOISE INSTALLATION

j. Access to the earth electrode system may be provided through the installation of one or more access wells at each

site. An acceptable type of access well is illustrated in Figure 2-10. Access wells shall be of a non-conductive material

POURED CONCRETE

OR CLAY PIPE REMOVABLE EXOTHERMIC WELD

COVER CONNECTION

COVER CONNECTION

CONNECTOR AT

LEAST

30 IN:

NO.4/0 AWG ELECTRONIC COPPER CABLE GROUNDING CABLE

GROUND ROD

FIGURE 2-10. ACCESS WELL

and have a minimum opening area of 175 square inches. Removable access covers must be provided. In very large structures, particularly those in which grounding grids are installed underneath, the access well or wells may be located inside the building in an accessible location. More than one access well may be necessary depending upon the size of the facility, the extent of the electrode system, and the degree of accessibility to the electrodes deemed desirable. Locate at least one of the access wells in the area with access to open soil so that the resistance checks of the earth electrode system can be made once the building is in use.

FIGURE 2-10. ACCESS WELL

The top view of a representative ground rod installation is shown in Figure 2-11 illustrates the required connections to the electronic signal reference network, the lightning protection

TO 8ERVCE DISCONNECTINGMEANB

— TO MAN GROUND GROUNDING ELECTRODE CONDUCTOR PLATE TO AIA TERMINALS STEEL STRUCTURAL COLUMN

BUILDING FOUNDATION

BUILDING FOUNDATION

2 TO 5 ELECTRONIC GROUND SYSTEMS MAIN GROUND CABLE LIGHTNING DOWN CONDUCTOR STEEL BOND TO COLUMNS

NO.40 AWG

ACCESS WELL GROUND ROOS GROUND ROD

FIGURE 2-11. CONNECTIONS TO EARTH ELECTRODE SYSTEM

system and the facility power ground system. Connection to ground rods in access wells, except for the counterpoise conductor, may be by means of FAA approved connectors in lieu of exothermic welds. The counterpoise conductor connections to the ground rods shall be exothermically welded. Lightning protection down conductor and the grounding electrode conductor connections shall be exothermically welded to buried ground rods.

FIGURE 2-11. CONNECTIONS TO EARTH ELECTRODE SYSTEM

20. INSTALLATION PRACTICES.

a. Schedule the installation of the earth electrode system so that any needed excavation, such as hole and trench digging, can be performed while other excavating, clearing, and earth moving operations associated with construction of the facility are in progress. If the system is installed prior to completion of the other earth moving operations, take the precautions necessary to assure that the components are not damaged or broken.

b. Take special care to ensure that all underground metallic lines such as water and sewer pipelines, armored cable,

etc., are carefully bonded to the earth electrode system with a bare No. 2 AWG (minimum) copper conductor.

c. Before covering the electrode system with backfill dirt or otherwise rendering it inaccessible, make checks of all joints and connections to check mechanical integrity, to verify the absence of voids or other indications of poor bonding, and to see that all required interconnections are made.

d. All bonds in concealed locations must be exothermically welded. Any bonds between dissimilar metals, such as between a copper wire and cast iron or steel pipe, must be thoroughly sealed against moisture to minimize corrosion.

e. Drive rods only into undisturbed earth or into thoroughly tamped or compacted filled areas. Rods and cables should be placed in the backfill around foundations only after the soil has been compacted or has adequate time to settle. Do not drive or lay ground rods in gravel beds which have been installed for drainage purposes unless the rods extend through such beds far enough to provide at least 8 feet (2.4m) of contact with the undisturbed earth underneath. Do not lay horizontal in such beds under any circumstances.

f. Rods may be driven either by hand sledging or with the use of power drivers. Where a limited number of rods are installed in the earth of moderate compactness, hand sledging may be preferable. Use driving nuts to prevent damage to the driven end, particularly if the rods are of the sectional type. Deep driven rods or those driven into hard or rocky soil generally require the use of power drivers with special driving collars to prevent damage to the rod.

g. As the earth electrode system is installed, and prior to covering the counterpoise and ground rods, make a resistance check of the overall earth electrode system. If the measured resistance is less than the calculated resistance, the system as installed is acceptable. On the other hand, if the measured resistance of the ground rods is greater than calculated, additional rods or deeper driven rods should be installed during the construction stage rather than waiting until the facility is completed to add additional rods.

h. Where vertically driven ground rods are not practical, due to geological formations, rods may be slanted. The more vertical a rod is driven, the more effective it is. Plates are best mounted vertically to ensure the greatest possible soil contact.

21. - 29. RESERVED.

Page 34 Chap 2 Par21

SECTION 2. LIGHTNING PROTECTION FOR STRUCTURES

SECTION 2. LIGHTNING PROTECTION FOR STRUCTURES

30. PRINCIPLES OF LIGHTNING PROTECTION.

a. Lightning Protection Reguirements. A structure, for the purpose of lightning protection, is defined as a building, mast, tower, or similar self-supporting object other than power lines, power stations, and substations. To protect structures against direct lightning strikes, three requirements must be fulfilled:

(1) A conductive object must be provided to intentionally attract the lightning leader.

(2) Paths must be established that join this conductive object to earth with such a low impedance that the discharge follows the paths in preference to any others.

(3) A low resistance connection must be made with the body of the earth.

b. Protection Methods. These conditions are met when a lightning discharge is permitted to enter or leave the earth while passing through only conducting parts of a structure, and without causing damage to the facility or injury to personnel. The conditions can be satisfied by one of two methods, each meeting the requirements of The National Fire Protection Association, NFPA 780, Lightning Protection Code, and having specific applications. These methods are:

(1) The installation of an integral protection system consisting of air terminals interconnected with roof conductors and down conductors utilizing approved type connectors and fittings to form the shortest practical low impedance paths to a ground rod in an earth electrode system suitable for the purposes.

(2) The installation of a separately-mounted protection system of one of two types:

(a) A mast type consisting of a pole, either metal or of a non-conductive material, which acts as a support for a lightning air terminal may be used. The air terminal shall be mounted on the pole so that it is supported in accordance with the requirements of NFPA 780. The down conductor shall be connected to the air terminal and shall be run down the pole to the earth electrode system. The down conductor shall be run on the exterior of the pole and shall be fastened to the pole at intervals not exceeding three feet. The mast or pole supporting

the air terminal shall NOT be used as a substitute for the down conductor.

(b) Two or more poles supporting an overhead ground wire connected to the earth electrode system with a down conductor at each pole.

31. INTEGRAL PROTECTION SYSTEM. When designing and installing an integral lightning protection system, perform the following:

a. Provide a lightning protection system that shall meet the requirements of NFPA 780, Lightning Protection Code; UL 96A, Underwriter's Laboratories (UL) Installation Requirements Master Labeled Lightning Protection Systems; and as specified herein. All equipment shall be UL approved for use as part of a master labeled lightning protection system, and marked in accordance with UL procedures.

b. Provide air terminals for all parts of a structure that are likely to be damaged by direct lightning strikes. Air terminals shall be erected on the structure as required by NFPA 780 and hereinafter in this order. Metal parts of a structure that are exposed to direct lightning strikes and have a metal thickness of 3/i6 inches (4.8 mm) or greater are connected to the lightning protection system with main size conductors and bonding plates which have a minimum of 3 square inches of contact.

c. Install roof and down conductors so that they provide a two way path from each of the air terminals (except where NFPA 780 permits one way paths and dead ends) and offer the least possible impedance to the passage of stroke currents between the air terminals and the earth and provide the most direct path to the earth electrode system.

d. Distribute ground connections symmetrically about the perimeter of the structure rather than grouping to one side.

e. Interconnect all metal objects within six feet of the discharge path to prevent side flashes. Representative connections are shown in Figure 2-12.

32. AIR TERMINALS. The intent of air terminals is to intercept any lightning stroke that might otherwise strike the building or structure being protected.

a. Size and Materials. Air terminals shall be UL approved and shall be solid copper, aluminum, or bronze. Copper air terminals may be nickel plated. The minimum sizes are 1/2-inch

07/01/96

FAUCET

ELECTRIC SERVICE GROUND

ELECTRIC SERVICE GROUND

15'MAX.

EXOTHERMIC WELD

6950.19A

METALLIC EXTENSION

ACCEPTABLE GUTTER CONNECTION

INSIDE WATER PIPE

TELEPHONE GROUND

WATER MAIN

LIGHTNING PROTECTION

FIGURE 2-12.

GROUND

GROUNDING PRACTICES FOR LIGHTNING PROTECTION

Chap 2

Par 32

(12.7 mm) in diameter for solid copper or bronze air terminals and 5/8-inch (15.9 mm) in diameter for solid aluminum air terminals. Air terminals shall have rounded or blunted tips for safety.

GROUNDING PRACTICES FOR LIGHTNING PROTECTION

(1) Air terminals must extend at least 10 inches (250 mm) above the object being protected. Rather than arbitrarily choosing the shortest terminal which will provide this minimum height, all parts of the structure must be checked graphically or analytically in the manner described in the next section to determine if the zone of protection provided by the air terminal is adequate. Likewise a longer air terminal should not be arbitrarily selected. Where taller air terminals are required to provide complete protection, support and bracing as required by NFPA 780, Lightning Protection Code must be provided.

NOTE: Where a personnel injury risk exists, such as areas where maintenance activities are regularly performed, the tip of the mid-roof air terminals shall be not less than 5 feet above the walking or working surface.

(2) All air terminals shall be secured against overturning either by attachment to the object to be protected or by means of braces which shall be permanently and rigidly attached to the building. An air terminal exceeding 24 inches (0.6 m) shall be supported at a point not less than one-half its height.

(3) An ornament or decoration on a free-standing, unbraced air terminal shall not present, in any plane, a wind-resistance area in excess of 20 square inches (0.01 square meter). This will permit the use of a copper or aluminum ball 5 inches (127 mm) in diameter to be mounted at the top of the air terminal as a means to prevent the electrostatic discharge from interfering with communications equipments in facilities.

b. Location.

(1) Locate air terminals along the ridges of gable, gambrel, and hip roofs in the manner illustrated in Figure 2-13.

(2) Place air terminals on corners and along the edges of gently sloping roofs as shown in Figure 2-14. Gently sloping roofs are defined as (1) having a span of 40 feet (12 m) or less with a pitch (rise-to-run ratio) of less than one-eighth or (2) having a span of greater than 40 feet (12 m) and a pitch of iess than 1/4. Where gently sloping roofs exceed 50 feet in

GAEL

SHEO

H

FIGURE 2-13. LOCATION OF AIR TERMINALS FOR COMMON ROOF TYPES

FIGURE 2-13. LOCATION OF AIR TERMINALS FOR COMMON ROOF TYPES

8

A- 50'MAXIMUM SPACING

B- 20'OR 25' MAXIMUM SPACING

W· OVER 40-ROOF1/4 PITCHORLESS

40 OR LESS - ROOF 1/8 PITCH OR LESS

-GROUND ROD-LOCATED INCORNER OF EARTH

ELECTRODE SYSTEM

FIGURE 2-14. LOCATION OF AIR TERMINALS ON GENTLY SLOPING ROOFS

FIGURE 2-14. LOCATION OF AIR TERMINALS ON GENTLY SLOPING ROOFS

length or width, provide additional air terminals located at spacings not to exceed 50 feet (15 m) on the gently sloping area. In addition, if the roof has a width of over 20 feet, an air terminal shall be located at the ridge ends regardless of the pitch or span. (3) On flat roofs, position air terminals around the perimeter in the manner shown in Figure 2-15. Provide additional air terminals placed at 50 foot (15 m) intervals over the

BUGS CABLE

BUGS CABLE

ISZ S ES

FIGURE 2-15. AIR TERMINAL PLACEMENT ON FLAT-ROOFED STRUCTURES

interior of the flat roofs which exceed 50 feet in length or width. (SAFETY NOTE: Where a personnel injury risk exists, such as areas where maintenance activities are regularly performed, the tip of the mid-roof air terminals shall be not less than 5 feet above the walking or working surface.)

FIGURE 2-15. AIR TERMINAL PLACEMENT ON FLAT-ROOFED STRUCTURES

(4) Air Terminals shall be placed at or within 2 feet (0.6 m) of the ends of ridges or ends and corners of roofs.

(5) The height of air terminals shall be such as to bring the tip of the air terminal not less than 10 inches (254 mm) above the object to be protected for 20 foot (6 m) maximum intervals and not less than 2 feet (0.6 m) above the object to be protected for 25 feet (7.6 m) maximum intervals.

c. Zones of Protection. The zone of protection is that space adjacent to a lightning protection system that is substantially immune to direct lightning flashes. Ensure that no part of the structure extends outside the zone of protection established by the air terminals. Determine the zone of protection using the criteria in NFPA 780, Lightning Protection Code (additionai guidance may be found in Standard of Practice LPI-175 of the Lightning Protection Institute). Structures that do not exceed 50 feet (i5 m) above the earth may utilize the following:

(1) Protection for structures that do not exceed 25 feet above earth are considered to protect lower portions of a structure located in a one-to-two zone of protection and structures that do not exceed 50 feet (15 m) above earth are considered to protect lower portions located within a one-to-one zone of protection.

(2) Prominent projections, such as dormers, which are as high or higher than the main ridge shall be protected with air terminals, conductors and grounds as normally specified for a roof installation. Roof projections and dormers below the main ridge may be protected by a "dead ended" air terminal with only one path to a main conductor, provided the run from the air terminal to a main conductor is not more than 16 feet (4.9 m) in total length and maintains a horizontal or downward coursing.

(3) To determine if protection is provided for all parts of a flat roofed structure such as vents, pipes, cabling or raised extensions, use the method illustrated in Figure 2-16 to calculate the zone protected by two vertical air terminals. This method can also be used to determine the coverage provided by vertical masts or horizontal wires. In Figure 2-16, point P represents the point of discrimination (that is, the point of departure of the final stepped leader) of the downward traveling stroke. To determine if the air terminals are actually the nearest objects to point P, use P as a center and swing an arc of radius X through the tips of the terminals. Let the value of this radius X be 150 feet (45 m) as required by NFPA 780. Because of the large differences between the height of typical terminals and the striking distance X, graphical determination of

the protected zone will usually be awkward. For greater accuracy, calculate the critical distances through the use of the

P

NOTE: DRAWING MUST BE TO 8CALE LEGEND: HHEIGHT OF TERMINAL GELEVATIONCOMPLETELY PROTECTED §= SPACING BETWEEN TERMINALS AIR TERMINALS RADIUS (X) OF ARC= 150 FT(48M) P- POINT OF DISCRIMINATION OF FINAL STEPPED LEADER (CENTER OF ARC)

ROOF EXTENSIONS

G H ROOF LINE 4 S

FIGURE 2-16. ILLUSTRATION OF METHOD FOR DETERMINING THE PROTECTION OF FLAT SURFACES AS PROVIDED BY AIR TERMINALS

G H ROOF LINE 4 S

following equation which is valid for s ≤ 2X:

G = H - X + [X2 - (S/2)2]1⁄2

In this equation, G is the height between the two terminals that is completely protected, H is the height of the terminals, s is the spacing between the terminals, and X is the radius of the arc. (4) Receiving and transmitting antennas, used for air to ground (A/G) communication, shall be included within the zone of protection. The inclusion of all antennas within the zone of protection is a design goal. If it is not technically feasible to include all antennas within the zone, then those antennas not included should have their bases or mountings bonded to the structural lightning protection system. This bond shall be accomplished with main conductors.

33. LIGHTNING PROTECTION CONDUCTORS. Provide each air terminal with a two-way path to earth through the installation of main (roof and down) conductors conforming to the appropriate tables in NFPA 780, Lightning Protection Code; Class I Materials for

structures not exceeding 75 feet (23 m) in height and Class II Materials for structures exceeding 75 feet (23 m) in height. Exceptions to the two-way path are allowable one-way paths (See Par."34 c) and "dead ends"as defined in NFPA 780. Bonding Conductors shall be sized in accordance with the same tables defining the main cables noted above.

34.ROOF CONDUCTORS.

a. Course roof conductors are situated along ridges of gable, gambrel, shed, and hip roofs; around the perimeter of flat roofs; behind or on top of parapets; and across flat or gently sloping roof areas as required to connect all air terminals. Conductors shall be coursed through or around obstructions (such as cupolas, ventilators, etc.) in a horizontal plane with the main conductor. Roof conductors shall interconnect all air terminals including those on any roof projection (such as chimneys, air handiing units, cooling towers, etc.) and shall provide a two way path to ground from the base of the air terminal except where noted in Paragraphs 33 and 34(c) herein.