Order 6950.10 Removal of Lightning Arresters While Performing Tests
This document is cancelled. It may have been replaced. Check the official source before relying on it.
DEPARTMENT OF TRANSPORTATION ORDER FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION ORDER FEDERAL AVIATION ADMINISTRATION
GL6950.10 GREAT LAKES KEGIOH
20 Feb 73
SUBJ: REMOVAL OF LIGHTNING ARRESTERS WHILE PERFORMING TESTS
1- HIRTOSE. This Order directs personnel to disconnect lightning arresters from cabling when the test voltage will exceed the permissible line-togrpund voltage of the lightning arrester.
SUBJ: REMOVAL OF LIGHTNING ARRESTERS WHILE PERFORMING TESTS
2. DISTRIBUTION. This Order is distributed to the Airway Facilities Division, Branch level and above, and to all Airway Facilities field
offices.
3- CANCELLATION. Order CE 6950.5 is cancelled.
**"* BACKGROUND. When the permissible line-to-ground voltage of a lightning arrester is exceeded, it will conduct to ground and therefore indicate an erroneous insulation resistance reading for the cable. This has resulted in the unwarranted replacement to cables and arresters.
5. LIGHTNING ARRESTER DATA. Tabulated below are permissible line-toground voltages for lightning arresters commonly used by FAA. If the test voltage exceeds the permissible line-to-ground voltage shown, the arrester shall be disconnected.
Manufacturer's Circuit Permissible Line-to Model No. Voltage Ground Volts
G.E. 9L15CCB0Q1 120/2lf0 175
G.E. 9LA10C22 2iK)0/ln60 1*500
H. GLASS Chief, Airway Facilities Division
Distribution: RAF-3; FAF-0 (Normal) Initiated By: AGL-M+5
j$ U.S. GOVERNMENT PRINTING OFFICE: 1972-754-260
j$ U.S. GOVERNMENT PRINTING OFFICE: 1972-754-260