1

ORDER 6480.17

TERMINAL FACILITY MODERNIZATION/RELOCATION SURVEY AND EVALUATION HANDBOOK

September 4, 1985

DEPARTMENT OF TRANSPORTATION

FEDERAL AVIATION ADMINISTRATION

Distribution: A-WYZ-2; A-X-2(minus AF/AT); A-X(AF/AT)-3; Initiated By: APM-520 A-FAS-1 (LTD);A-FAF-2(LTD);A-FAT-2/8(LTD)

2

RECORD OF CHANGES

CHANGE SUPPLEMENTS TO BASIC

OPTIONAL USE

DIRECTIVE NO. 6480.17

CHANGE SUPPLEMENTS TO OPTIONAL USE BASIC

FAA Form 1320-5 (5-68) SUPERSEDES PREVIOUS EDITION

C FAA AC 72-6744

09/04/85 6480.17

FOREWORD

This order sets forth procedures for analyzing existing FAA-operated terminal air traffic control facilities relative to the scope of modernization work required or relative to establishing justification for facility relocation. This order shall apply to both FAA-owned and leased facilities.

3

Martin T. Poesky Director, Prgram Engineering and Maintenance Service

Page i (and ii)

0

09/04/85

TABLE OF CONTENTS

CHAPTER 1. GENERAL

1. Purpose 2. Distribution 3. Reserved 4. Changes 5. Applicability 6. Requests for Information 7. Procedures 8. Objectives 9. Scope 10. thru 21. Reserved

5

CHAPTER 2. DESCRIPTION OF PROCEDURES

SECTION 1. INTRODUCTION

22. Background 23. Objectives 24. Safety 25. thru 34. Reserved

SECTION 2. REGIONAL EVALUATION TEAM

35. Personnel Assigned to the Evaluation Team 36. Establishment of Coordinator 37. Coordinator's Responsibilities 38. thru 47. Reserved

SECTION 3. COORDINATION WITH FACILITY PERSONNEL

48. Lines of Communication 49. Scheduling 50. Obtaining Background Materials 51. Coordination of Survey Activities with Facility Staff 52. Initial On-Site Meeting 53. thru 62. Reserved

Page No

1

1 1 1 1 1 1 2 2 2 2

3

3

3 3 3 3

3

3 3 3 3

4

4

44

4 4 4

Page iii

6

CHAPTER 3. EVALUATION SYSTEM

63. Objectives 64. Worksheets 65. Air Traffic Evaluation Worksheet 66. Air Traffic Evaluation Worksheet - Part 1 67. Air Traffic Evaluation Worksheets - Part 2 68. Airway Facilities Evaluation Worksheets 69. Backup Sheets 70. Photographs 71. Spare Capacity 72. thru 81. Reserved

CHAPTER 4. COST ESTIMATE

82. Objective 83. Cost Estimate Forms 84. Cost Estimate Coordination 85. Engineering Cost Estimate 86. Establishment of Facility Replacement Cost 87. Lease Agreements 88. thru 97. Reserved

CHAPTER 5. MODERNIZATION/RELOCATION ANALYSIS

98. Objectives 99. Analysis of Evaluation Worksheets 100. Air Traffic Evaluation Worksheets - Part 2 101. Analysis of Engineering Cost Estimate 102. Summary Report 103. thru 112. Reserved

09/04/85

Page No. 5

5 5 5 6 7 8 10 10 10 10

11

11 11 11 11

13/14

15

15 15 16 16 18 19/20

21

TOWER STRUCTURES, CONTROL CAB AND TRACON REQUIREMENTS

CHAPTER 6.

SECTION 1. TOWER STRUCTURES

113. Location 114. Height 115. Orientation 116. Runway/Helipad Visibility 117. Traffic Pattern Visibility 118. Taxiway Visibility 119. Other Movement Area Visibility 120. Depth Perception 121. Parking 122. Accessibility 123. Physical Condition/Appearance 124. Fire Protection 125. Air Quality 126. Catwalks 127. Stairs

Page iv

21

23 23 23 23 23 23 23 23 24 24 24 23 25 25 25

7

09/04/85

128. Elevators 129. Toilet Room 130. Security 131. thru 140. Reserved

SECTION 2. CONTROL CAB

141. Cab Size 142. Cab Shape 143. Lighting - General 144. Lighting - Task 145. Ceiling - Height 146. Ceiling - Color 147. Acoustics 148. Visibility Obstructions - Internal 149. Noise - External 150. Physical Condition/Appearance 151. Air Quality 152. Glare 153. Stray Illumination 154. Proximity to TRACON Room 155. Proximity to Training Room 156. Proximity to Break Room/Locker Room 157. Proximity to Administrative Area 158. Console - Height/Depth 159. Drop Tubes 160. Position Equipment Layout 161. Interposition Workflow 162. Position Reconfiguration/Relocation Capability 163. Equipment Replacement Capability 164. Position Expansion Capability 165. Supervisor's Work Area 166. Convenience Area 167. Storage 168. Central Vacuum System 169. Flooring 170. Exhaust Fans 171. Equipment Maintenance Accessibility 172. Headset Storage 173. thru 181. Reserved

SECTION 3. TERMINAL RADAR APPROACH CONTROL (TRACON)

182. Size 183. Shape 184. Physical Condition 185. Lighting - General 186. Lighting - Task 187. Ceiling - Height 188. Ceiling - Color 189. Acoustics 190. Noise - Internal

Page No. 25 25 25 25

25

25 25 26 26 26 26 26 26 26 26 26 26 27 27 27 27 27 27 27 27 27 27 27 28 28 28 28 28 28 28 28 28 28

29

29 29 29 29 29 29 29 29 29

Page v

8

191. Noise - External 192. Stray Illumination/Light Reflections 193. Air Quality 194. Parking 195. Accessibility 196. Proximity to Cab 197. Proximity to Training Room 198. Proximity to Toilets 199. Proximity to Break Room/Locker Room 200. Proximity to Administrative Area 201. Consoles 202. Position Equipment Layout 203. Interposition Workflow 204. Position Reconfiguration/Relocation Capability 205. Equipment Replacement Capability 206. Position Expansion Capability 207. Supervisor's Work Area 208. Drinking Fountain 209. Storage 210. Central Vacuum System 211. Flooring 212. Exhaust Fans 213. Security 214. Equipment Control Panel 215. Display Boards 216. Equipment Maintenance Accessibility 217. Fire Protection 218. Headset Storage 219. thru 224. Reserved

SECTION 4 - ADMINISTRATIVE SPACE

225. Air Traffic Manager (ATM) 226. Assistant Air Traffic Manager (AATM) 227. Traffic Management Coordinator(TMC)

09/04/85

Page No. 29 29 29 30 30 30 30 30 30 30 31 31 31 31 31 31 31 31 31 31 31 32 32 32 32 32 32 32 32

32

32 32 32 32

Assistant Manager for Plans and Procedures (AMP)

228. 229. Assistant Manager for Training (AMT) 230. Assistant Manager for Automation (AMA) 231. Area Manager (ĀM) 232. Area Supervisor (AS) 233. Training Specialist'(TS) 234. Plans and Procedures Specialist (PPS) 235. Automation Specialist (AS) 236. Quality Assurance Specialist (QAS)

33 33 33 33 33 33 33 33 33

Quality Assurance and Training Specialist (QATS)

237. 238. Program Specialist (PS) 239. Administrative Officer (A0) 240. Education Specialist (ES) 241. ReceptionArea 242. Secretarial Area 243. Training Classroom 244. Conference Room

Page vi

33 33 33 33 33 33 33

9

09/04/85

245. Breakroom/Locker Room 246. Toilet Room 247. Tape Playback Room 248. Storage

Page No. 33 33 33 34 34

Computer Based Instruction (CBI) Laboratory

249. 250. Janitor's Closet

34 34

Functional Arrangement of Administrative Space

251. 252. Expansion 253. Air Quality 254. Lighting 255. Physicaǐ Condition 256. Acoustics 257. Security 258. Drinking Fountains 259. Noise - Internal 260. Noise - External 261. Parking 262. Accessibility 263. Copy Machine Space 264. Word Processing Space 265. thru 274. Reserved

34 34 34 35 35 35 35 35 35 35 35 36 36 36

37

CHAPTER 7. AIRWAY FACILITIES BUILDING REQUIREMENTS

SECTION 1. SPACE REQUIREMENTS

275. Administrative Space 276. Locker Space 277. Toilet Rooms 278. Communications Equipment Room 279. Radar Equipment Room 280. Telephone Equipment Room 281. Engine Generator Room 282. Mechanical Equipment Room 283. Electrical Equipment Room 284. PCS/Battery Room 285. Storage Rooms 286. Cable Chases 287. Internal Flexibility 288. Building Expansion 289. thru 297. Reserved

SECTION 2. BUILDING CODE

298. Number of Exits 299. Exit Distance 300. Labeled Doors 301. Corridors 302. Stairways, General 303. Tower Stairs 304. Fire Walls

37

37 37 38 38 39 39 40 40 41 41 41 41 41 42 42

42

42 43 43 44 44 45 46

Page vii

305. Fireproofing 306. thru. 315. Reserved

SECTION 3. GENERAL REQUIREMENTS

10

316. Windows 317. Cab Windows 318. Exterior Doors 319. Interior Doors 320. Interior Walls 321. Ceilings 322. Floors 323. Roof ing 324. Asbestos 325. Catwalks 326. Equipment Access to the Cab 327. Exterior Envelope 328. Elevator 329. Signage 330. Security 331. thru 340. Reserved

09/04/85

Page No. 46 47

47

47 48 48 49 50 51 51 51 52 53 53 53 54 54 55 55

56

SECTION 4 - PROVISIONS FOR PHYSICALLY HANDICAPPED

341. Curb Ramps 342. Ramps 343. Entrance Doors 344. Passageways 345. Stairs 346. Toilets 347. Hazards 348. Parking 349. Elevators 350. Miscellaneous 351. thru 359. Reserved

CHAPTER 8. STRUCTURAL

360. General 361. Settlement 362. Deterioration of Structural Members 363. Modifications to Structure 364. Live Loads 365. thru 373. Reserved

CHAPTER 9. MECHANICAL SYSTEMS

374. General

SECTION 1. HEATING SYSTEMS

375. Boiler (Hot Water/Steam, Gas, and Oil)

Page viii

56 57 58 59 59 60 62 62 63/64 63/64 63/64

65

65 65 65 66 67/68 67/68

69

69

69

11

09/04/85

376. Heat Exchangers (Shell-in-Tube) 377. Feedwater/Circulating Pumpsets 378. Steam/Condensate Piping 379. Heating Hot Water Piping 380. Forced Air Furnaces (Gas/Electric/0il) 381. Fintube/Radiators/Convection Units 382. Cabinet Unit Heaters (Steam/Hydronic/Electric) 383. Electric Heating Coils (All Types) 384. Steam/Hot Water Heat ing Coils 385. Unit Ventilators 386. thru 395. Reserved

SECTION 2. COOLING SYSTEMS

396.

09/04/85

Page No. 70 71 71 72 72 73 74 74 74 75 75

75

75

Liquid/Refrigerant Chillers (Water Cooled/Air Cooled)

397. Split System (Direct Expansion) Condensing Units 398. Cool ing Towers 399. Closed Loop (Air Cooled) Condensers 400. Heat Pumps'(Air-to-Air) 401. Self-Contained Air Conditioners 402. Chilled Water/(Condenser Water) Pumpsets 403. Chilled Water/(Condenser Water) Piping 404. Refrigerant Piping 405. Chilled Water Coils 406. Refrigerant Coils (Evaporator/Condenser) 407. thru 416. Reserved

SECTION 3. AIR DISTRIBUTION SYSTEMS

417. Air-Handling (Packaged/Built-Up) Systems 418. Ventilation and Exhaust Fan Systems 419. Fancoil Units 420. Louvers 421. Mixing Boxes 422. Ductwork/Dampers 423. Air Distribution System Balancing 424. thru 433. Reserved

SECTION 4. HVAC CONTROL SYSTEMS

434. Pneumatic System/Components 435. Electric Control Wiring 436. Control Components (Pneumatic/Electric) 437. thru 446. Reserved

SECTION 5. POTABLE WATER SYSTEMS

447. Well/Circulating/Booster Pumpsets 448. Distribution Piping (Potable Water) 449. Hot Water Heaters (Electric/Gas) 450. Tanks (Diaphragm/Storage) 451. thru 460 Reserved

76 77 77 77 78 78 79 80 80 81 82

82

82 83 84 84 84 85 85 86

86

86 87 87 87

88

88 88 88 89 89

Page ix

12

SECTION 6. FIRE PROTECTION SYSTEMS

461. Automatic Sprinkler Systems

09/04/85

Page No. 90

90 91

462. Automatic Total Flooding Gas Extinguishment Systems

463. thru 472. Reserved

SECTION 7. MISCELLANEOUS SYSTEMS AND EQUIPMENT

473. Sanitary Fixtures and Fittings 474. Fuel Oil Storage and Distribution Piping 475. Natural Gas Distribution Piping 476. thru 484. Reserved

CHAPTER 10. ELECTRICAL SYSTEMS

485. General

SECTION 1. EXTERIOR SYSTEMS

486. Obstruction Lights 487. Exterior Building Receptacles 488. thru 497. Reserved

SECTION 2. BUILDING SERVICE

498. Primary Switchgear 499. Oil-Filled Transformer 500. Secondary Feeders 501. thru 510. Reserved

SECTION 3. BUILDING DISTRIBUTION

511. Service Disconnect Switch 512. Critical Main Distribution Panel 513. Essential Main Distribution Panel 514. Non-Essential Main Distribution Panel 515. Panelboards 516. Circuit Breakers/Fusible Switches 517. Dry Type Transformers 518. Conductors 519. Conduits, Cable Trays, or Wireways 520. Receptacles 521. thru 530. Reserved

SECTION 4. MOTOR CONTROLS

531. Disconnect Switches 532. Starters 533. thru 542. Reserved

Page x

91

91 92 93/94 93/94

95

95

95

95 95 95

95

95 96 96 96

96

96 97 97 98 98 99 99 99 100 100 100

101

101 101 101

09/04/85

SECTION 5. LIGHTING

543. Illumination Levels 544. Exit Lights 545. Light Switches/Dimmers 546. thru 555. Reserved

SECTION 6. COMMUNICATION SYSTEM

556. Fire Alarm System 557. Intercom System 558. thru 567. Reserved

13

SECTION 7. STAND-BY POWER SYSTEM

568. Cab DC Power Systems 569. Battery Operated Lighting System 570. Emergency Light ing 571. Engine Generator 572. Transfer Switch 573. thru 582. Reserved

SECTION 8. SPECIAL SYSTEMS

583. Grounding 584. Lightning Protection 585. Surge Protection 586.

Page No.

101 102 102 102

103

103 104 104

105

105 105 105 106 106 107

108

107 107 107

Unbalanced and Single Phased Main Feeder Protection

587. Power Condit ioning System (PCS) 588. thru 596. Reserved

CHAPTER 11. SITE SPECIFIC

597. General

SECTION 1. SITE WORK

598. Access Roads 599. Parking Area 600. Sidewalks 601. Storm Drainage 602. thru 611. Reserved

SECTION 2. MECHANICAL

612. Sanitary Drainage Piping 613. Storm Water Drainage Piping 614. Subsoil Drainage System 615 Central Vacuum Systems 616. (LP)/Propane Gas Distribution Piping 617. Standpipe Systems (Wet/Dry)

108 108 108

109

109

109

109 109 110 110 110

110

110 110 111 111 111 111

Page xi

14

09/04/85 6480.17

Page No.

619. Solar Collectors (Air) 623. Sewage Treatment Facility 620. 621. 624. Sump Pumps 625. thru 634. Reserved 622. Evaporative (Swamp) Coolers and Condensers Humidifiers Absorption Chillers 113 113 114 114 114 115 115

SECTION 3. ELECTRICAL 115

635. Site Lighting 636. Car Heater Receptacles 637. Heat Tapes 638. thru 647. Reserved 115 115 115 116

APPENDIX Appendix 1. Referenced Documents (pages 1 and 2) Appendix 2. Evaluation and Analysis Worksheets (pages 1 thru 112) Appendix 3. Cost Estimate Worksheets (pages 1 thru 3) Appendix 4. FAA Standard Building Designs (pages 1 thru 22) Appendix 5. Typical Office Layouts (pages 1 and 2)

Page xii

15

09/04/85 6480.17

CHAPTER 1. GENERAL

1. PURPOSE. This order sets forth the procedures for analyzing existing FAA operated terminal air traffic control facilities relative to the scope of modernization work required or relative to establishing justification for facility relocation. This order shall apply to both FAA-owned and leased facilities. A complete list of documents referenced for this order is provided in Appendix 1. The serial designation of each reference shall be the latest year of adoption or revision, unless otherwise specified.

2. DISTRIBUTION. This order is distributed at division level to FAA headquarters, FAA regions, FAA Technical Center, Aeronautical Center, and at branch level to Air Traffic and Airway Facilities in the regional office. Distribution is also made to Airport District Offices, Airway Facilities General

NAS Sectors, Airport Traffic Control Towers, and Terminal Radar Approach Control facilities.

3. RESERVED.

4. CHANGES. Recommended additions, deletions, or modifications to this order shall be sent through normal channels to:

a. Airway Facilities Comments.

Structures Program Branch, APM-520 Program Engineering and Maintenance Service 800 Independence Avenue, S.W. Washington, D.C. 20591

b. Air Traffic Comments.

System Plans and Programs Division, ATR-100 800 Independence Avenue, S.W. Washington, D.C. 20591

5. APPLICABILITY. This order shall be used to analyze modernization or relocation requirements at existing FAA-owned, leased and FAA-occupied DOD terminal air traffic control facilities. The order will provide an avenue of support to terminal facilities modernization/relocation national program items in response to the annual Facilities and Equipment Call for Estimates.

6. REQUESTS FOR INFORMATION. Refer requests for further information or information on this order to:

Structures Program Branch, APM-520 Program Engineering and Maintenance Service 800 Independence Avenue, S.W. Washington, D.C. 20591

Chap 1 Par 1 Page 1

16

6480.17 09/04/85

7. PROCEDURES. The Federal Aviation Administration:

a. Continually monitors terminal air traffic control facilities with regard to suitability for mission performance.

b. Evaluates the need to either undergo a major modernization or relocate terminal air traffic control facilities to maintain a continual 10-year life expectancy for these facilities. (New facilities are expected to have a life expectancy of 20 years.)

c. Maintains a comprehensive national evaluation plan for major modernization or relocation of terminal air traffic control facilities. The comprehensive national evaluation plan is formulated and periodically updated through the use of a nationwide reporting system.

d. Has defined a cost estimating system to be included with major modernization or relocation actions which will indicate the cost versus benefit ratios for solutions which will satisfy operational requirements.

8. OBJECTIVES. The objectives of this order are as follows:

a. Combine in one source, either directly or by reference, all necessary information to establish either the need for a major modernization or relocation of an existing terminal air traffic control facility.

b. Provide uniform lists of evaluation items which will be applied to terminal facilities.

c. Provide guidelines which will establish consistency and uniformity in evaluation results.

d. Implement a standardized, weighted system for scoring facilities def ic ienc ies.

e. Establish a uniform cost estimating system to be applied to all evaluated facilities.

9. SCoPE. This order identifies specific items for evaluating operational/functional requirements, security, materials, building code safety, expansion capability, architectural and structural integrity, mechanical systems, and electrical systems as they relate to major modernization or relocat ion requirements.

10. thru 21. RESERVED.

Chap 1 Page 2 Par 7

17

09/04/85 6480.17

CHAPTER 2. DESCRIPTION OF PROCEDURES

SECTION 1 - INTRODUCTION

22. BACKGROUND. Most of the existing FAA terminal air traffic control facilities and supporting space will surpass their 20-year design life prior to the year 2000. The need for major modernization or relocation of these facilities must be determined in order to ensure the continued success of the FAA mission.

23. OBJECTIVES. The procedures set forth in this chapter should be followed to ensure that the evaluation process is uniform throughout the FAA system. (It is recognized that regional resources may not allow complete compliance with the procedures in this chapter however, it is recommended that the procedures be followed as closely as possible).

24. SAFETY. The possibility of electrical shock, falls from elevated platforms, becoming entangled with equipment and other hazards are present when performing the evaluation. Team members must continually be alert for hazardous or potentially hazardous situations and take appropriate action to avoid acc idents.

25. thru 34. RESERVED.

SECTION 2 - REGTONAL EVALUATION TEAM

35. PERSONNEL ASSIGNED TO THE EVALUATION TEAM. The most efficient method of conducting the evaluations described in this order is through the use of a multidisciplinary team. The expertise required on this team involves air traffic control, civil engineering (architectural/structural), mechanical engineering, electrical engineering, and electronic engineering.

36. ESTABLISHMENT OF COORDINATOR. If utilizing the team concept, the regional Air Traffic and Airway Facilities division managers should select an appropriate individual from the evaluation team to serve as a coordinator. This will provide continuity for the program.

37. COORDINATOR'S RESPONSIBILITIES. The coordinator's responsibilities would include the following:

a. Serve as a point of contact for the team.

b. Schedule surveys of facilities.

c. Serve as the liaison between the evaluation team and the facility staff as appropriate following regional protocol.

Chap 2 Par 22 Page 3

18

6480.17 09/04/85

d. Assist in interpreting conflicts or inconsistencies which may exist between the order's descriptions and field conditions.

e. Be responsible for the review of the final evaluation report and cost estimate to monitor consistency and completeness.

f. Review budgeted and planned programs for the facility.

38. thru 47. RESERVED.

SECTION 3 - COORDINATION WITH FACILITY PERSONNEL

48. LINES OF COMMUNICATION. It is important to the success of the evaluation effort that proper lines of communication be established between the evaluation personnel and the Air Traffic and Airway Facilities managers or designated representatives of the facility.

49. SCHEDULING. Scheduling should include dates for field trip, times of interviews with facility staff, any special testing procedures which require coordination with facility operational procedures, and due dates for completed evaluation worksheets,cost estimates, and reports.

50. OBTAINING BACKGROUND MATERIALS. The coordinator should request that al1 pertinent information about the facility to be surveyed such as drawings, specifications, calculations etc., be available at each facility during the evaluation survey. Individual evaluation team members shall be responsible for obtaining and reviewing any pertinent information which is available from the regional office prior to the field trip.

51. COORDINATION OF SURVEY ACTIVITIES WITH FACILITY STAFF. It is impOrtant that all designated facility personnel, both Air Traffic and Airway Facilities, be informed of the survey time and be available to provide any assistance and pertinent information needed by the evaluation team.

52. INITIAL ONSITE MEETING. The meeting should be attended by al1 members of the evaluation team, both Air Traffic and Airway Facilities, and by facility managers or designated representatives. The primary purpose of this meeting is to discuss known deficiencies in the facility which the evaluation team will need to address and to brief local facility managers or designated personnel on the plan for the evaluation.

53. thru 62. RESERVED.

Chap 2 Page 4 Par 37

19

09/04/85 6480.17

CHAPTER 3. EVALUATION SYSTEM

63. OBJECTIVES. The objectives of the evaluation system are as follows:

a. Provide worksheets on which to organize and identify individual items and conditions which may require correction at a particular facility.

b. Classify individual items based on the type of impact each item will have on the facility operation and environment.

c. Provide a vehicle for weighting items to ensure that those of more significance have a larger influence on facility score.

d. Limit the amount of subjective rating error introduced by different evaluators.

e. Provide facility evaluation data which the region will use in planning corrective action.

f. Aid in the formulation of an order of magnitude cost estimate for corrective action.

g. Aid in evaluating the merits of modernization versus relocation.

h. Establish a practice for evaluating individual facilities in view of operational and technical deficiencies on an equitable basis.

64. WORKSHEETS. Two sets of evaluation worksheets are provided, one for use by Air Traffic (operational impact) and one for use by Airway Facilities (technical deficiencies). Specific focus on these two major areas allows each group to do an indepth analysis of a facility, identifying significant operational and technical deficiencies in an objective manner. The area just above the remarks column on the front page of each set of forms is provided to list pertinent statistical details about the facility being evaluated.

65. AIR TRAFFIC EVALUATION WORKSHEET. These worksheets are designed for the evaluation of a facility from an Air Traffic view point. It is separated into two parts. Part 1 deals with deficiencies and problems viewed and weighted relative one to another. Part 2 provides a list of specific equipment items found in a terminal facility. These items, individually, may be satisfactory or may have deficiencies which suggest replacement of existing equipment, deletion of outdated equipment or addition of equipment not currentiy installed at the facility being evaluated.

Chap 3 Par63 Page 5

6480.17 09/04/85

66. AIR TRAFFIC EVALUATION WORKSHEET - PART 1. Each line on this worksheet is divided into a series of 7 columns. These columns add clarity to the analysis of each item. Complete all items pertinent to the facility being evaluated. Each column, one through seven, is discussed below:

20

a. Evaluation Item (Column 1). This column lists significant items to be evaluated at each facility. They are designed to highlight specific deficiencies. If additional deficiencies not included in those items listed are present, they may be entered in the blank spaces following each section.

b. Deficiency Score (Column 2). A blank box is provided on each line to record a numeric grade which describes the relative level of facility deficiency. The five possible levels are listed below:

(1) (0) - No defic iency.

(2) (1) - Minor deficiency - A detectable problem which has only a minor affect on the facility.

(3) (2) - Moderate deficiency - An obvious problem which is affecting the facility or its operation and has an impact between minor and significant scores.

(4) (3) - Significant deficiency - A problem which is readily apparent and needs to be dealt with through future action and has an adverse affect on the facility.

(5) (4) - Major deficiency-Efforts to deal with this class of deficiency requires actions which go beyond usual measures.

NOTE: Not all items listed in the evaluation worksheet will be applicable to every site. For all items which do not apply, enter N.A. in this column.

c. Relative Importance Factor (Column 3). A standard weighting factor which indicates the relative importance of each evaluation item. The weights were predetermined to ensure objectivity and consistency. The weighting factor is the multiplier which is used with the deficiency score to form a score for that item. The resulting score is placed in one of the three impact columns (columns 4, 5 and 6) which follow. If additional deficiencies are noted as stated in paragraph a above, the evaluator should assign a relative importance factor based on those assigned to similar items on the worksheet.

Chap 3 Page 6 Par 66

21

09/04/85 6480.17

d. Impact (Columns 4, 5 and 6). These three columns are used to classify each evaluation item in terms of its impact on the facility. Two boxes on each line are shaded, leaving only one to record the product of the Deficiency Score (column 2) and Relative Importance Factor (column 3). This box was predetermined and is intended to describe the type of impact resulting from the evaluation item. If additional deficiencies are noted as stated in paragraph a above, the evaluator should select the impact column most appropriate. Each category is described below:

(1) Operational Impact (Column 4). This column includes items which have impact predominately in operational areas.

(2) People Impact (Column 5). This column covers those areas which principaliy affect air traffic control personnel in the facility.

(3) Management Impact (Column 6). This column relates to items which hinder the management of a facility.

e. Remarks (Column 7). This column includes specific remarks which supplement and clarify conditions which are not afforded full credit through a numeric score.

67. AIR TRAFFIC EVALUATION WORKSHEETS - PART 2. Each numbered line on this part of the worksheet lists a piece/part of a system or subsystem of equipment used to support the air traffic operational function of the facility. The intent of the listing is to ensure a full identification of all possible deficiencies. For example, it is possible that an operational problem could be related to a piece of equipment or a iack of such equipment, which would not be covered under evaluation items in Part 1. The equipment evaluation items listed on this worksheet are not included in the narrative of the order (chapter 7). The worksheet consists of six columns. Each column is discussed below:

a. Equipment Item (Column 1). This column lists items/pieces of equipment found in a terminal air traffic control facility. Items of equipment not listed may be added in the blank spaces provided at the end of this worksheet.

b. Problem Exists (Column 2). This column is checked if there is a problem in the present facility which is associated with the piece of equipment listed in column 1. If checked, the problem should be briefly described in the Remarks Column (column 6). Description and comments may be continued, if necessary, on a separate sheet of paper. The continuation should be labeled with the appropriate line number.

Chap 3 Par 66 Page 7

22

6480.17 09/04/85

c. Equipment Required but not Available (Column 3). This column is checked if an item is needed, or additional units are required to adequately supplement that which exists. The deficiency should be briefly described in the Remarks Column (column 6). Descriptions and comments may be continued, if necessary, on a separate sheet of paper. The continuation should be labeled with the appropriate line number.

d. Should be Considered for Replacement (Column 4). This column is checked if equipment is considered to be out moded. It may not be possible to secure a replacement even during a modernization, however, this column should be checked if the evaluator deems it reasonable of note. The deficiency should be briefly described in the Remarks Column (column 6). Descriptions and comments may be continued, if necessary on a separate sheet of paper. The continuation should be labeled with the appropriate line number.

e. Other (Column 5). This column is checked if a comment is deemed necessary, but which is not covered by preceding columns. The deficiency should be briefly described in the Remarks Column (column 6). Descriptions and comments may be continued, if necessary, on a separate sheet of paper. The continuation should be labeled with the appropriate line number.

f. Remarks (Column 6). Complete if a check mark appears in any one or more of the preceding columns.

68. AIRWAY FACILITIES EVALUATION WORKSHEETS. This worksheet is designed for the evaluation of a facility from an Airway Facilities view point. Each line on this worksheet is divided into eight columns. These columns add clarity to the analysis of each item. Complete all items pertinent to the facility being evaluated. Each column, one through eight, is discussed below:

a. Evaluation Item (Column 1). This column lists significant items to be evaluated at each facility. They are designed to highlight specific deficiencies. If additional deficiencies not included in those items listed are present, they may be entered in the blank spaces following each section.

b. Deficiency Score (Column 2). A blank box is provided on each line to record a numeric grade which describes the relative level of facility deficiency. The five possible levels are listed below:

(1) No work required.

(2) Minor repair required. A detectable problem exists and has only minor affect on the facility.

(3) Moderate repair required. An obvious problem which is affecting the facility or its operation and has an impact between minor and major repair scores.

Chap 3 Page 8 Par 67

23

09/04/85 6480.17

(4) Major repair required. A problem which is readily apparent and has an adverse impact on facility operations.

(5) Replacement required or item does not exist and must be installed. Efforts to deal with this deficiency requires action which goes beyond usual measures.

(When an individual item requires evaluation by more than one team member, the score will reflect a consensus of all members involved.)

NOTE: Not all items listed in the evaluation worksheet will be applicable to every site. For all items which do not apply, enter N.A. in this column.

c. Relative Importance Factor (Column 3). A standard weighting factor indicates the relative importance of each evaluation item. The weights were predetermined to insure objectivity and consistency. The weighting factor is the multiplier which is used with the deficiency score to form a score for that item. The resulting score is placed in one of the four impact columns (columns 4, 5, 6, and 7).

d. Impact (Columns 4, 5, 6, and 7). These columns are used to classify each evaluation item in terms of its impact on the facility. Three boxes on each line are shaded, leaving only one to record the product of the Deficiency Score (column 2) and Relative Importance Factor (column 3). The scoring box was predetermined to describe the type of impact resulting from each line item.

(1) Operational Impact (Column 4). This column includes items which affect the ability of the facility to perform the FAA mission.

(2) Code (Column 5). This column includes items which deal with code compliance.

(3) Support Function (Column 6). This column includes items which indirectly support facility performance of the FAA mission.

(4) Site Specific (Column 7). This column includes items which are not commonly found at all facilities but are required at specific installations due to unique requirements.

e. Remarks (Column 8). Specific remarks which supplement and clarify conditions which are not afforded full credit through a numeric score are recorded here. Remarks may be continued, if necessary, on a separate sheet of paper. The continuation should be labeled with the appropriate line number.

Par 68 Chap _3 Page 9

24

6480.17 09/04/85

69. BACKUP SHEETS. Detailed field notes should be compiled during the field survey. These backup sheets should be organized to follow the order of items listed on the evaluation worksheets and should be retained with the final report at the regional office.

70. PHOTOGRAPHS. Photographs may be useful in situations where the evaluation score cannot accurately reflect the actual field conditions. The photographs will be retained with the final report to the region as a tool for documenting unusual conditions. Situations which may require photographic documentation include, but are not limited to, the following:

a. Obstruction of control cab sightlines.

b. Limits to future expansion.

c. Structural deterioration.

71. SPARE CAPACITY. Unless stated otherwise, spare capacity shall be considered adequate if it is capable of accommodating all planned and budgeted future expansion or, if no expansion is planned or budgeted, a miniium of lù percent future growth.

72. thru 81. RESERVED.

Chap 3 Page 10 Par 69

25

09/04/85 6480.17

CHAPTER 4. COST ESTIMATE

82. OBJECTIVE. The objective of this chapter is to establish procedures for a universal system of estimating modernization or replacement costs for items or facilities that are found to be substandard or non-existent. Cost estimating procedures from region to region shall be equitable, taking into account variations in construction costs throughout the geographical area of FAA jurisdiction.

83. COST ESTIMATE FORMS.

a. The following forms shall be used in the preparation of engineers cost estimates:

(1) FAA Form 4450-8, Engineering Cost Estimate, see appendix 3, page 2.

(2) FAA Form 4450-9, Engineering Cost Estimate Summary, see appendix 3, page 3.

b. These forms are stocked at the FAA Depot under the NSN numbers and are available through normal supply channels. Unit of issue for each form is sheet. See appendix 3 for a sample of the forms.

84. COST ESTIMATE COORDINATION. Airway Facilities personnel will complete the cost estimate forms for both Airway Facilities and Air Traffic deficiency items. Airway Facilities must evaluate all Air Traffic spaces for physical condition and Air Traffic must brief Airway Facilities concerning the deficiencies noted in this evaluation.

85. ENGINEERING COST ESTIMATE.

a. General. The following sets forth the preferred method for preparing engineering cost estimates. Detailed directions'have been excluded and only general direction stated in order to permit a reasonable degree of judgment by the estimator.

b. Preparation of Engineering Cost Estimate. Cost estimates shall be prepared based on field observations. Cost estimate forms have been included in appendix 3. These forms shall be used to list all items included on the Air Traffic evaluation worksheets Part I and the Airway Facilities evaluation worksheets. These forms are to be used for recording remarks pertinent to the completion of FAA Form 4450-8 for each item. The basic details of the estimate shall be prepared on FAA Form 4450-8. Initially, the work usually performed by either the prime-contractor or a subcontractor should be identified and the

Chap 4 Par 82 Page 11

26

6480.17 09/04/85

estimate divided into categories accordingly. Work items will normally parallel the major work categories contained in a standard facility construction spec ification index. Each work item shall be subdivided into specific identifiable items of material and/or work. The quantity of each item based on unit measure shall be determined and the unit cost developed. These costs shall be developed by detailed investigations and calculations considering such applicable factors as energy conservation, published cost estimating data, item complexity, impact of large or small quantity on price, local conditions, labor conditions and restrictions, national and local economic factors, seasonal conditions and time of construction, analysis of similar items of work, etc. Individual item costs for each division on the evaluation form shall be grouped together and subtotaled. To this sum shall be added allowances such as subcontractor's overhead and profit, prime-contractor's handling or service charges, and all other costs associated with the specific division. The divisions of work with their individual total costs should be tabulated on FAA Form 4450-9, Engineering Cost Estimate Summary. An aggregate subtotal shall be obtained and to this sum added prime-contractor's job overhead (if not previously included), home office overhead, profit, and bond costs. The grand total of the above items is the engineers cost estimate.

c. Cost Data.

(1) Engineers shall consult Governmental, commercial, and industrial sources of cost data as a basis for preparing engineers cost estimates.

(2) The following estimating data sources are suggested for use as references. This list is not intended as all inclusive, but is for guidance only.

(a) Means, BUILDING CONSTRUCTION COST DATA.

(b) Walker, BUILDING ESTIMATOR'S REFERENCE BOOK.

(c) Marshall and Stevens, MARSHALL'S EVALUATION SERVICE.

(d) Architectural Record.

(e) Engineering News-Record.

(f) Local Contractors and Construction Associations.

(g) Previous FAA Construction Contracts.

(h) Gulf Publishing Company, ESTIMATOR'S MAN-HOUR LIBRARY.

(i) Craftsman Book Company, NATIONAL CONSTRUCTION ESTIMATOR.

Chap 4 Page 12 Par 85

27

09/04/85 6480.17

d. Documentation. A statement shall be made on the cover sheet of each engineers cost estimate attesting to the date of the estimate, the estimator's name(s), signature(s), facility type, and geographical location on which the estimate is based. Where applicable and if possible, the Engineering News-Record Building Cost Index or some other industry recognized cost index shall be stated and identified as it relates to the date of the estimate and geographical location.

e. Government Furnished Material (GFM). GFM and equipment shall be listed on the Cost Estimating Form 4450-8 in a separate division. The cost of equipment shall be from the latest available price list. All additional procedures shall be as outlined in paragraph b of this section.

86. ESTABLISHMENT OF FACILITY REPLACEMENT COST. Standard designs for terminal air traffic control facilities can be obtained from APM-500. Select the model facility to most adequately replace the existing facility. Obtain the standard cost estimate for this facility and adjust this cost as required for escalation, local conditions, labor conditions and restrictions, national and local economic factors, etc. This entry should be the last figure on all facility cost estimate summaries, FAA Form 4450-9. An exception will occur in the case of leased facilities. See appendix 4 for a description of standard designs available.

87. LEASE AGREEMENTS. In the case where facilities are leased, the last entry on FAA Form 4450-9 shall be 25 percent of the first year's rent minus the total dollar amount spent previously for improvements to the facility during the lease to date. In the case of rent-free or nominal fee lease agreements, the last entry on FAA Form 4450-9 shall be 15% of the fair market value of the property minus the sum of any improvements made in the current year to date and the rent fee, if any, paid in one year. If additional clarification is required, refer to Order 4660.1, Real Property, chapter 10, section 5.

88. thru 97. RESERVED.

Chap 4 Page 13 Par 85 (and 14)

29

09/04/85 6480.17

CHAPTER 5. MODERNIZATION/RELOCATION ANALYSIS

98. OBJECTIVES. The objectives of this chapter are as follows:

a. Establish a uniform process supporting the decision to recommend initiation of modernization and relocation projects.

b. Provide a system employing both the evaluation process and the engineering cost estimate.

c. Assure that the decision to modernize or relocate a facility will achieve the best cost versus benefit ratio for the agency.

99. ANALYSIS OF EVALUATION WORKSHEETS.

a. General. The analysis procedure outlined below will generate percentage values which may be used to compare different facilities with each other.

NOTE: It is not intended that numeric computations necessarily be the sole means of ranking or validating candidates for projects.

b. Analysis Worksheets. See appendix 2 for a blank worksheet and an example of a completed analysis worksheet. The worksheets are organized into two parts, one for Air Traffic and one for Airway Facilities. The chapters are listed vertically on the left side of the worksheet and broken down into the sections corresponding to the handbook. Listed horizontally across the top of the worksheets are impact (AT) (or division (AF)) columns corresponding to those found on the evaluation worksheets, a totals column, and percentage column.

c. Completion of Analysis Worksheets. The procedure for completing the Air Traffic and Airway Facilities portion of the analysis worksheet are the same with the exception of the impact (AT) or division (AF) listings at the top of the worksheet. (The following narrative uses the term "impact" corresponding to the Air Traffic portion of the worksheet. The Airway Facilities portion will be completed using the same procedures however. substitute the word "division" wherever "impact" appears.)

NOTE: See form following this item for location of data entries. Numbers on the form relate to the paragraph numbers below.

(1) Each chapter/section line is divided into two boxes. The top half of each box is used to record (by impact column) the actual facility score for each section. (Calculate this number by summing all the entries in each individual impact column for the chapter/section.) The bottom half of each box is used to record (by impact column) the total possible score each section may achieve. (Calculate this number by summing the relative importance factors for each item scored in each individual impact column and multiplying this sum by the maximum possible score of 4.)

Chap 5 Par 98 Page 15

30

6480.17 09/04/85

NOTE: The total possible score will be unigue for each facility because items that were "not applicable (NA)" will not be summed while any additions made to the evaluation worksheet during the field evaluation will be added.

(2) Once all the impact column boxes for a section have been filled in, sum the actual facilitiy scores (top halves) and the total possible scores (bottom halves) for the section and record in the corresponding box in the "section totals" column.

(3) Divide the section facility total score by the total possible score and multiply by 100. Enter this number in the column labelled "Percentage per Section."

(4) Repeat steps 1 through 3 for each chapter/section.

(5) When all section scores have been recorded for a chapter, calculate the "impact totals" by summing the facility total scores (top halves) and the total possible scores (bottom halves) for each impact column and record in the corresponding boxes in the "impact totals" line.

(6) For each impact column divide the facility total score by the total possible score and multiply by 100. Enter this number in the "Percentage per Impact" line.

(7) Calculate the chapter totals by summing the "impact totals" lines to arrive at the facility total score for the chapter and the total possible score for the chapter and record where indicated on the worksheet.

(8) Divide the chapter facility total score by the chapter total possible score and multiply by 100. Enter this number in the "Percentage this Chapter" box on the worksheet.

(9) Repeat steps 1 through 8 for all chapters.

100. AIR TRAFFIC EVALUATION WORKSHEET PART 2. No analysis of this worksheet is required. The completed worksheet should be included in the final summary report as described in paragraph 102.

101. ANALYSIS OF ENGINEERING COST ESTIMATE.

a. General. The engineering cost estimate shall be analyzed to assure the best cost versus benefit ratio for the agency.

b. Agency Owned Property: A comparison of modernization costs versus facility replacement cost shall be made to establish modernization or relocation action. Divide the modernization cost by the facility replacement cost to

Chap 5 Page 16 Par 99

09/04/85 6480.17

AIR TRAFFIC EVALUATION ANALYSIS WORKSHEET

31

CHAPTER 6 OPERTONAL MPACT PEOPLE IPACT MANNENT IMPACT 8ECTION TOTAL8 PERTAGE PERCTIN ION

FACILITY SCORE SECTION 1 TOTAL POSSIBLE 1 23

FACILITY SCORE SECTION" 2 TOTAL POSSIBLE FACILITY SCORE SECTION 3 TOTAL POSSIBLE FACILITY 8CORE SECTION 4 TOTAL POSSIBLE FACILITY IMPACT TOTALS SCORE TOTAL 5 POSSIBLE

PERCENTAGE PER IMPACT 6

CHAPTER TOTALS

CHAPTER TOTAL FACILITY SCORE

CHAPTER TOTAL POSSIBLE SCORE PERCENTAGE THIS CHAPTER 778

Chap 5 Par 101 Page 17

32

6480.17 09/04/85

establish the percentage value. If modernization costs are 65 percent or greater of the facility replacement cost, relocation should be considered.

c. Agency Leased Property. Property which is occupied by the agency on a leased basis is subject to śtrict limitations under the Economy Act of 1932. If modernization costs exceed the last entry on FAA Form 4450-9, relocation should be considered. (See chapter 4, paragraph 87.)

102. SUMMARY REPORT.

a. General. The summary report shall be completed and sent to Washington headquarters, APM/ATR, with any request to initiate modernization or relocation projects.

b. Cover Sheet. The facility evaluation summary report (see appendix 2) shall be completed as follows:

(1) Complete the "General" information section including facility name and location, date of field survey, names of facility staff representing Air Traffic and Airway Facilities personnel, and names of all members of the evaluation team with the Coordinator listed first.

(2) Complete the "Cost Estimating" section by:

(a) Entering the total cost of modernization and,

(b) Entering either the facility replacement cost or, in the case of leased property, the maximum amount allowable.

(3) Circle the recommended action, either to modernize or relocate.

(4) Remarks should be as brief as possible but include any pertinent data which should be considered in tne decision to initiate a project.' If relocation is the recommended action, include specific comments addressing why expansion and/or modernization of the existing facility is not feasible.

c. Evaluation Worksheets. The body of the summary report is composed of the evaluation worksheets organized in the order below:

(1) Evaluation Analysis Worksheets.

(2) Air Traffic Evaluation Worksheet - Part 1.

Chap.5 Page 18 Par 101

33

09/04/85 6480.17

(3) Air Traffic Evaluation Worksheet - Part 2. (4) Airway Facilities Evaluation Worksheets. (5) Engineering Cost Estimate. 103. thru 112. RESERVED.

Chap 5 Par 102 Page 19 (and 20)

09/04/85 6480.17

CHAPTER 6. TOWER STRUCTURES, CONTROL CAB, AND TRACON REQUIREMENTS

35

NOTE: This chapter provides information to support in depth evaluation of air traffic control functions and areas from an operational point of view. Each paragraph is numbered to coincide with the same numbered item on the Air Traffic Evaluation Worksheet, Part 1. The paragraphs are designed to provide a frame of reference against which an evaluation can reliably and fully judge an Air Traffic Control Facility relative to the need for major modernization or relocation. The entries in this chapter shall be evaluated by Air Traffic personnel; however, Airway Facilities shall evaluate the same areas from a construction, maintenance, and Occupational Health and Safety (OSHA) viewpoint. Airway Facilities shall complete the cost estimate to correct all deficiencies noted, both Air Traffic and Airway Facilit ies.

SECTION 1 - TOWER STRUCTURES

NOTE: A great variety of space configurations will be encountered. In order to standardize the evaluation approach, the facility being evaluated should be considered in relation to the size/type of standard FÃA base building/tower which would be built if the facility were replaced (see appendix 4). This decision must consider the faciǐity level, existing and planned equipment and specific requirements for offices based on the facilities authorized position chart in combination with FAA Order 1l00.126E. The replacement facility selection should also consider any planned or programmed future growth. Once the appropriate standard design has been selected, it will serve as the standard for comparison against which the location is evaluated. Typical density levels are presented in the following chart:

Par (NOTE:) Chap 6 Page 21

36

TERMINAL TYPES

TERMINAL APPROACH NON- NON-RADAR LIMITED RADAR LEVEL VFRTOWER APPROACH APPROACH

I 0 - 34.9 0 - 24.9

II 35 - 89.9 25 - 79.9 0 - 24.9

III 90 OR MORE 80 OR MORE 25 - 59.9

IV 60 OR MORE

V

TRAFFIC AIRPORT AIRPORT INSTR. OPS DATA OPERATIONS OPS. AND USED: INSTR. OPS

09/04/85

RADAR APPROACH

0 - 19.9

20 - 59.9

60 - 99.9

100 OR MORE

INSTR.OPS

Hourly Traffic Density Factor (Sum of'daily traffic for

CRITERIA:

the busiest 183 days; divided by 183 days; divided by 16 hours or actual hours of operation if a facility is open less than 16 hours). Traffic data to be used is

determined by facility type.

Chap_6 CHART

37

09/04/85 6480.17

113. LOCATION. Strategic location of an ATCT is required to minimize excessive viewing distances from the control tower to outer aircraft landing and movement areas. The best location for the ATCT will vary depending on the unique runway, taxiway and building configurations found at each location. This is an overall evaluation factor which seeks to consider the ATCT's general location in regard to operational requirements.

114. HEIGHT. While height and depth perception are related, the height factor goes beyond simply being able to distinguish between two aircraft. Adequate height enables the controller to achieve more of an aerial view of the airport. This allows the controller to make judgments on sequence of taxiing aircraft or the position of one aircraft relative to another for control decisions. Major airports are normally subject to greater deficiencies than smaller airports due to size and complexity.

115. ORIENTATION. The tower cab should be oriented to face north or alternately east, south, or west, normally in that order of preference for towers in the northern hemisphere. (In areas where snow accumulates on the ground surface, a southern orientation should be avoided.) Orientation should not be such that the view of a primary runway approach is in line with a rising or setting sun.

NOTE: Operational requirements should be the final determining factor when scoring orientation.

116. RUNWAY/HELIPAD VISIBILITY. A clear, unobstructed view of the approach to the end of the primary instrument runway and all active runways/helipads must be available to the local/helicopter control position. While not mandatory, all operating positions should have this view.

117. TRAFFIC PATTERN VISIBILITY. A clear, unobstructed view of traffic patterns to all active runways/helipads must be available to the local/helicopter controller.

118. TAXIWAY VISIBILITY. A clear, unobstructed and direct view of taxiways and runways must be available to the ground control position. While not mandatory, all operating positions should have this view.

119. OTHER MOVEMENT AREA VISIBILITY. A clear, unobstructed view of helicopter pads (on airport), terminal gates and other movement areas is desired for the ground controller, but not considered mandatory.

120. DEPTH PERCEPTION.

a. General. The ability to differentiate the number and type of grouped aircraft and/or ground vehicles and to observe their movement and position relative to the airport surface area should be available from the control cab.

Chap 6 Par 113 Page 23

38

6480.17 09/04/85

b. Criteria. To meet the depth perception requirements outlined in "a." above, cab eye level must intersect the grade of all aircraft air traffic control service movement areas at an angie of 35 minutes or greater. As a rule of thumb, multiply the controllers eye level above grade (in feet) times 100. The product is approximately the maximum distance (in feet) which meets this angle requirement.

NOTE: The next two evaluation paragraphs deal with important conditions which vary widely between locations. If conditions at the facility/ location being evaluated are not adequately covered by the factors as written, describe them in detail along with your evaluation grade. These two items are repeated in sections 1, 3, and 4 of the evaluation worksheet; however, do not grade parking or accessibility in more than one section unless required to adequately describe conditions at the facility being evaluated.

121. PARKING. This paragraph considers the factors encountered from the time the employee enters the parking lot until the initial entry to the building complex housing the facility. Conditions may range from parking adjacent to the facility to parking which is located in remote lots requiring either long walks, riding a bus, or some other means of mechanical conveyor. Any unusual restrictions that are encountered in getting to the parking area, such as those associated with military bases or major airports should be considered under this item. The physical condition of the parking area will be evaluated by Airway Facilities and is not to be considered in this score.

122. ACCESSIBILITY. This paragraph is a continuation of parking, paragraph 121. Considered here are those factors involved with the physical access to the administrative and/or operations area after an employee has made the initial entry into the building. Conditions may range from going up a private elevator/stair, passage through areas with locked gates, doors, security check points under another authorities jurisdiction, or crossing the roof of a terminal building. Access to the employee's work area should not cause excessive time to be wasted.

123. PHYSICAL CONDITION/APPEARANCE. Visually inspect for material deterioration, defects, internal or external appearance, leaks or other deficiencies which affect and are not conducive to a professional work environment.

124. FIRE PROTECTION. Inspect areas for existence of smoke alarms and similar devices strategically located. (NOTE: Airway Facilities will evaluate the facility for fire code requirements.)

Chap.6 Page 24 Par 120

39

09/04/85 6480.17

125. AIR QUALITY. The work environment should be free of noxious odors. Ventilation shouTd be adequate to remove any odor introduced into the work environment and ventilation supply air should not be contaminated by external odor sources. Heating and cooling should be adequate to accommodate changing requirements throughout the day. The use of supplemental fans or space heaters indicates the heating/cooling is inadequate.

126. CATWALKS. A catwalk shall be provided around all control tower cabs, to facilitate washing of windows. (Towers with an operating window washing system are exempt from this requirement.) Airway Facilities will evaluate the catwalks against OSHA standards; however, Air Traffic should evaluate conditions which appear to adversely impact Air Traffic personnel.

127. STAIRS. Tower and cab stairs serve as required means of ingress/egress. Stairs shall be in good state of repair, void of slippery areas and well lighted. Headroom must be of sufficient height to allow unrestricted passage. Stairways must be enclosed to avoid the unsafe conditions brought about by exposure to extreme weather conditions.

128. ELEVATORS. ATCTs where the cab floor is 50 feet or more above the ground should be equipped with an elevator. The elevator should be reliable and in good repair free from dents, scratches, or other damage. The elevator cab must be equipped with emergency communications and should be power ventilated to maintain a comfortable environment.

129. TOILET ROOM. One toilet room is acceptable for ATCT personnel. The room should be located within one floor of the cab level and shall be equipped with a toilet and lavatory with hot and cold running water. The door shall be capable of being locked from the inside without a key. Heating and cooling must be adequate to maintain a comfortable environment and the room must be equipped with an exhaust fan.

130. SECURITY. Adequate locks and communication/surveillance systems shall be provided as required to ensure security.

131. thru 140. RESERVED.

SECTION 2 - CONTROL CAB

141. CAB SIZE. The cab size must be adequate to permit the conduct of all required work functions with maximum staffing levels. Included in this requirement is space to perform on-the-job training without interfering with normal operat ional procedures.

142. CAB SHAPE. The shape of the cab should not restrict an efficient configuration of operating positions. A cab with many sides and angles may restrict the space available for equipment or controllers view of the airport.

Chap 6 Par 125 Page 25

40

6480.17 09/04/85

143. LIGHTING - GENERAL. Overhead and floor lighting should be controlled separately by dimmer switches with an off position. Floor lighting should provide adequate illumination to allow for safe controller movement at night.

144. LIGHTING - TASK. Task lighting should adequately illuminate each specific position of operation. This lighting must be controlled from the operating position by a dimmer switch and shouǐd originate from ceiling height. Lighting must be shielded to prevent reflections in the cab glass.

145. CEILING - HEIGHT. The cab height should be sufficient to permit proper positioning of the BRITE displays and observation of traffic patterns. Ceilings should be high enough to provide an adequate acoustical environment.

146. CEILING - COLOR. The ceiling should be a dark colored acoustical material to prevent reflections in the cab windows.

147. ACOUSTICS. Acoustics within the cab should allow performance of work at any position of operation without distractions under normal operating conditions.

148. VISIBILITY OBSTRUCTIONS - INTERNAL. The controllers view of movement areas should not be blocked by large pieces of equipment. If pieces of equipment have been placed on console tops or window sills creating obstructions to controller vision, evaluate whether modifications could be made to accommodate this equipment in an appropriate layout.

149. NOISE - EXTERNAL. Question cab personnel concerning interfering external sources. The cab should provide a sufficient acoustical separation so that external noise does not interfere with normal work operations. Examples are runup areas, helicopter landing pads, jet engine test cells, etc.

150. PHYSICAL CONDITION/APPEARANCE. Visually inspect for material deterioration, defects, internal or external appearance, leaks or other deficiencies which affect and are not conducive to a professional work environment.

151. AIR QUALITY. The work environment should be free of noxious odors. Ventilation should be adequate to remove any odor introduced into the cab and ventilation supply air should not be contaminated by external odor sources. Heating and cooling should be adequate to accommodate changing requirements throughout the day. Use of portable supplemental fans or space heaters indicates the heating/cooling is inadequate.

152. GLARE. Question cab personnel concerning existing glare problems. These problems include, but are not limited to, reflections from buildings or hanger roofs or reflections between cab glass at corners.

Chap.6 Page 26 Par 143

41

09/04/85 6480.17

153. STRAY ILLUMINATION. Night operations are subject to special glare problems which diminish the controllers ability to see aircraft. The problem may be the result of poorly shielded ground lights adjacent to the tower or looking over or into a lighted area such as a parking lot.

154. PROXIMITY TO TRACON ROOM. The cab and TRACON should be in reasonable proximity to facilitate personnel rotation and supervision and to accommodate the use of common equipment such as radio control equipment.

155. PROXIMITY TO TRAINING ROOM. The cab and training room should be in reasonable proximity to facilitate the recall of personnel.

156. PROXIMITY TO BREAK ROOM/LOCKER ROOM. The cab and break room/1ocker room should be in reasonable proximity to facilitate the recall of personnel.

157. PROXIMITY TO ADMINISTRATIVE AREA. The administrative area provides support to operations personnel. This area should be reasonably accessible to operational personnel and in reasonable proximity to the cab to facilitate access as required by the facility manager and staff.

158. CONSOLE- HEIGHT/DEPTH. The dimensions of the cab consoles should be appropriate for the installation. Consoles which are too large can obstruct the view of controllers especially if the taxiways are close to the tower and consoles which are too small lack the space for writing and equipment installation.

159. DROP TUBES. Drop tubes, where required, shall be capable of being instalTed between the cab and TRACON room. Excessively long horizontal"runs may not provide an acceptable routing path. Existing installations should provide reliable service.

160. POSITION EQUIPMENT LAYOUT. Addition of equipment. usually occurs in space that is available rather than in a logical position from an operations point of view. Equipment should be arranged in a logical order to facilitate efficient work operations.

161. INTERPOSITION WORKFLOW. Changing operational and procedural requirements may have adversely impacted the original operational position logic. Evaluate the current workflow patterns to determine if data can be transferred in an efficient manner.

162. POSITION RECONFIGURATION/RELOCATION CAPABILITY. Sufficient space should be available to facilitate relocation of existing positions when required.

163. EQUIPMENT REPLACEMENT CAPABILITY. Consoles shal1 be in good condition and capable of accepting the electronic equipment required by the current accepted level of technology for the facility activity classification.

Par 153 Chap 6 Page 27

42

6480.17 09/04/85

164. POSITION EXPANSION CAPABILITY. Sufficient space should be available to accommodate additional new pieces of equipment which had not previously appeared in the console.

165. SUPERVISOR'S WORK AREA. The cab and the TRACON require an area which has access to facility communications and space for supervisory work area. Specific requirements for this area will vary from facility to facility. This area is housed in the operations space to permit close supervision of the operation.

166. CONVENIENCE AREA. This area should be equipped with a sink (with hot/cold water and a drinking fountain), refrigerator, and storage for smali utensils, supplies such as coffee, cups, sugar, etc., and controller's lunches. This area must be capable of providing reasonable support for single controllers during periods of low activity.

167. STORAGE. A reasonable amount of space must be provided for storage of forms and other supplies that must be readily available in the operations area. This area should provide for organized storage of material conducive to a professional working environment.

168. CENTRAL VACUUM SYSTEM. These systems are required to support the cleaning of operational areas. The blower unit should be installed in a remote location and use of the system should not produce annoying noise levels.

169. FLO0RING. Floor coverings shall be securely attached to the floor, free of rips, tears, missing sections, and other similar defects. The material should have characteristics which permits thorough and efficient cleaning.

170. EXHAUST FANS. These fans remove excessive unwanted smoke/fumes from the operations area. The capacity of this system should allow operations to continue even during periods of poor air quality.

171. EQUIPMENT MAINTENANCE ACCESSIBILITY. To ensure a high degree of reliability, operational equipment must be accessible to Airway Facilities technicians. The controller should not be forced to vacate a position in order for routine maintenance to be performed.

172. HEADSET STORAGE. A "pigeonhole"-type storage area should be provided for temporary storage of operations personnel headsets.

173. thru 181. RESERVED.

Chap_6 Page 28 Par 164

43

09/04/85 6480.17

SECTION 3 - TRACON

182. SIZE. TRACON size is determined by the number and types of consoles/ positions required for the present operation plus additional positions required for future expansion. Included in the requirements for present operations

should be adequate space to support on-the-job training (0JT) for all posit ions.

183. SHAPE. The shape of the TRACON should not restrict the efficient configuration of operational positions.

184. PHYSICAL CONDITION. Visually inspect for material deterioration, defects, internal or external appearance, leaks or other deficiencies which affect and are not conducive to a professional work environment.

185. LIGHTING - GENERAL. Overhead and floor lighting should be controlled separately by dimmer switches with an off position. Floor lighting should provide adequate illumination to allow for safe controller movement.

186. LIGHTING - TASK. Task lighting should adequately illuminate each specific position of operation. This lighting must be controlled from the operating position by a dimmer switch and should not interfere with other positions.

187. CEILING - HEIGHT. Ceiling height should be a minimum of 8 feet.

188. CEILING - COLOR. The ceiling shall be acoustical material with low light reflectance to achieve a darkened room environment.

189. ACOUSTICS. Acoustics within the TRACON should allow performance of work conditions. at any position of operation without distractions under normal operating

190. NOISE - INTERNAL. Question TRACON personnel about any interfering or unusual internal noise problems such as blowers, fans or other equipment noise.

191. NOISE - EXTERNAL. Question TRACON personnel about any interfering or

helicopter landing pads. unusual external noise problems such as engine generators, runup areas, or

192. STRAY ILLUMINATION/LIGHT REFLECTIONS. Question facility personnel concerning any unshielded or interfering Tight sources.

193. AIR QUALITY. The work environment should be free of noxious odors. Ventilation should be adequate to remove any odor introduced into the TRACON and ventilation supply air should not be contaminated by external odor sources. Heating and cooling should be adequate to accommodate changing requirements throughout the day. Use of supplemental fans or space heaters indicates the heating/cooling is inadequate.

Chap 6 Par 182 Page 29

44

6480.17 09/04/85

NOTE: The next two evaluation paragraphs deal with important conditions which vary widely between locations. If conditions at the facility/location being evaluated are not adequately covered by the factors as written, describe them in detail along with your evaluation grade. These two paragraphs are repeated in sections 1, 3, and 4 of the evaluation worksheet; however, do not grade parking or accessibility in more than one section unless required to adequately describe conditions at the facility being evaluated.

194. PARKING. This paragraph considers the factors encountered from the time the employee enters the parking lot until the initial entry to the building complex housing the facility. Conditions may range from parking adjacent to the facility to parking which is located in remote lots requiring either long walks, riding a bus, or some other means of mechanical conveyor. Any unusual restrictions that are encountered in getting to the parking area, such as those associated with military bases or major airports should be considered under this paragraph. The physical condition of the parking area will be evaluated by Airway Facilities and is not to be considered in this score.

195. ACCESSIBILITY. This paragraph is a continuation of parking, paragraph 194. Considered here are those factors involved with the physical access to the administrative and/or operations area after an employee has made the initial entry into the building. Conditions may range from going up a private elevator/stair, passage through areas with locked gates, doors, security check points under another authorities jurisdiction, or crossing the roof of a terminal building. Access to the employee's work area should not cause excessive time to be wasted.

196. PROXIMITY TO CAB. The cab and TRACON should be in reasonable proximity to facilitate personnel rotation and supervision and to accommodate the use of common equipment such as radio control equipment.

197. PROXIMITY TO TRAINING ROOM. The TRACON and training room should be in reasonable proximity to facilitate the recall of personnel.

198. PROXIMITY TO TOILETS. Toilets should be located within a reasonable distance of the TRAcoN to minimize the amount of time operational personnel are away from the operating position.

199. PROXIMITY TO BREAK ROOM/LOCKER ROOM. The TRACON and break room/locker room should be in reasonable proximity to facilitate the recall of personnel.

200. PROXIMITY TO ADMINISTRATIVE AREA. The administrative area provides support to operations personnel. This area should be reasonably accessible to operational personnel and in reasonable proximity to the TRACoN to facilitate access as required by the facility manager and staff.

Chap.6 Page 30 Par 193

45

09/04/85 6480.17

201. CONSOLES. Consoles shal1 be in good condition. The size and design should be adequate to support the functions being performed at each position.

202. POSITION EQUIPMENT LAYOUT. Addition of equipment usually occurs in space that is available rather than in a logical position from an operations point of view. Equipment should be arranged in a logical order to facilitate efficient work operations.

203. INTERPOSITION WORKFLOW. Changing operational and procedural requirements may have adversely impacted the original operational position logic. Evaluate the current work flow patterns to determine if data can be transferred in an efficient manner.

204. POSITION RECONFIGURATION/RELOCATION CAPABILITY. Sufficient space should be available to facilitate relocation of existing positions as required.

205. EQUIPMENT REPLACEMENT CAPABILITY. Consoles shall be in good condition and capable of accepting the electronic equipment required by the current accepted level of technology for the facility activity classification.

206. POSITION EXPANSION CAPABILITY. Sufficient space should be available to accommodate additional new pieces of equipment which had not previously appeared in the console.

207. SUPERVISOR'S WORK AREA. The cab and the TRACON require an area which has access to facility communications and space for supervisory work area. Specific requirements for this area will vary from facility to facility. This area is housed in the operations space to permit close supervision of the operation.

208. DRINKING FOUNTAIN. A drinking fountain should be located in the TRACON room in an area that does not interfere with the operation.

209. STORAGE. A reasonable amount of space must be provided for storage of forms and other supplies that must be readily available in the operations area. This area should provide for organized storage of material conducive to a professional working environment.

210. CENTRAL VACUUM SYSTEM. These systems are required to support the cleaning of operational areas. The blower unit should be installed in a remote location and use of the system should not produce annoying noise levels.

211. FL00RING. Floor coverings shall be securely attached to the floor, free of rips, tears, missing sections, and other similar defects. The material should have characteristics which permits thorough and efficient cleaning.

Chap 6 Par 201 Page 31

46

6480.17 09/04/85

212. EXHAUST FANS. These fans remove excessive unwanted smoke/fumes from the operations area. The capacity of this system should allow operations to continue even during periods of poor air quality.

213. SECURITY. Adequate locks and communication/surveillance systems shall be provided as required to ensure security.

214. EQUIPMENT CONTROL PANEL. The equipment control panel should be in a location that is convenient to both the supervisor's area and the control pos it ions.

215. DISPLAY BOARDS. Sufficient convenient space should be available for position display boards and status boards as required.

216. EQUIPMENT MAINTENANCE ACCESSIBILITY. To ensure a high degree of reliability, operational equipment must be accessible to Airway Facilities technicians. The controller should not be forced to vacate a position in order for routine maintenance to be performed.

217. FIRE PROTECTION. Inspect areas for existence of smoke alarms and similar devices strategically located (NOTE: Airway Facilities will evaluate the facility for fire code requirements).

218. HEADSET STORAGE. A "pigeonhole"-type storage area should be provided for temporary storage of operations personnel headsets.

219. thru 224. RESERVED.

SECTION 4 - ADMINISTRATIVE SPACE

NOTE: Administrative space includes areas such as offices, lobbies, open bay areas, etc., not specifically included in sections 1, 2, and 3. The many variables associated with existing space configurations, available equipment, monitoring limitations, etc. make rigid standards impossible to establish; however, for evaluation purposes the facility should' be graded against the appropriate level/type standard design drawings of the agency (see appendix 4). Only those spaces included in the facilities authorized staffing shall apply.

225. AIR TRAFFIC MANAGER (ATM). Private office required.

226. ASSISTANT AIR TRAFFIC MANAGER (AATM). Private office required.

227. TRAFFIC MANAGEMENT COORDINATOR (TMC). Shared office space adequate.

228. ASSISTANT MANAGER FOR PLANS AND PROCEDURES (AMP). Private office required.

Chap 6 Page 32 Par 212

47

09/04/85 6480.17

229. ASSISTANT MANAGER FOR TRAINING (AMT). Private office required. 230. ASSISTANT MANAGER FOR AUTOMATION (AMA). Private office required. 231. AREA MANAGER (AM). Private office required. 232. AREA SUPERVISOR (AS). Private office required. 233. TRAINING SPECIALIST (TS). Shared office adequate. 234. PLANS AND PROCEDURES SPECIALIST (PPS). Shared office adequate. 235. AUTOMATION SPECIALIST (AUS). Shared office adequate. 236. QUALITY ASSURANCE SPECIALIST (QAS). Private office required. 237. QUALITY ASSURANCE AND TRAINING SPECIALIST (QATS). Private office required. 238. PROGRAM SPECIALIST (PS). Shared office adequate. 239. ADMINISTRATIVE OFFICER. Shared office adequate. 240. EDUCATION SPECIALIST (EDS). Shared office adequate. 241. RECEPTION AREA. Adequate space required with waiting area. 242. SECRETARIAL AREA. Adequate space required for work stations authorized. 243. TRAINING CLASSROOM. Enclosed room required. This room may also serve as the conference room for the facility. 244. CONFERENCE ROOM. Enclosed room required. This room may also serve as a training classroom for the facility.

In the case, grade paragraph 243 only. 245. BREAKROOM/LOCKER ROOM. An enclosed area is required. The breakroom should be equipped with a counter, sink, cabinets, two-burner stove, a rapid heat oven, and a refrigerator. The locker room should be equipped to provide one section of a double (15 by 72 inch) locker with separate coat compartments and upper small compartments for all facility personnei. 246. TOILET ROOMS. Toilet rooms should be in reasonable proximity to the TRACON and in either the junction or subjunction levels of the tower. 247. TAPE PLAYBACK ROOM. An enclosed room located in a quiet, secure area of the building is required. The room should also be soundproofed to the extent possible.

Chap 6 Par 229 Page 33

48

6480.17 09/04/85

248. STORAGE. An enclosed, secure room is required. The space should contain storage racks, shelves and cabinets. Heating and ventilation. is desirable.

249. COMPUTER BASED INSTRUCTION (CBI) LABORATORY. Where this space is provided or planned, adequate space should be available to house this equipment. The size and layout of this space should facilitate learning which is normally conducted in individual study cubicles. Lighting and acoustics should be conducive to the learning task. The CBI area should be readily available to personnel from the training department.

250. JANITORS CLOSET. This area is used for the storage of maintenance equipment and supplies for the building and grounds. Space should be provided for storage racks, shelves, cabinets, mop rack, and slop sink. Convenience outlets, heating and ventiiation should be provided for this space.

251. FUNCTIONAL ARRANGEMENT OF ADMINISTRATIVE SPACE. The relationship of individual work areas and support space should conform to and complement the facilities work flow requirements. In general, work should progress with the minimum amount of handling, travel and delays possible.

252. EXPANSION.

a. General. Future expansion refers to the ability of a facility to expand by incremental future additions. If future operational and technical requirements can be accommodated by internal flexibility, this paragraph does not apply.

b. Operational/Technical/Administrative Expansion. Obtain the budgeted and planned expansion program for the facility. Based on these projected future requirements, the facility must be able to accommodate incremented expansion in those areas most likely to experience growth. If a future expansion program has not been formulated for the facility, a ten percent expansion'factor should be applied.

c. Support Services. The site must be capable of accepting the building addition and any increase in area required for support buildings, parking lots, access roads, etc.

253. AIR QUALITY. The work environment should be free of noxious odors. Ventilation shouTd be adequate to remove any odor introduced into the work environment and ventilation supply air should not be contaminated by external odor sources. Heating and cooling should be adequate to accommodate changing requirements throughout the day. The use of supplemental fans or space heaters indicates the heating/cooling is inadequate.

254. LIGHTING. Lighting should be of sufficient brightness and distribution to allow work functions to be performed from any location in any given work area. For spec ific requirements, see paragraph 543.

Chap.6 Page 34 Par 248

49

09/04/85 6480.17

255. PHYSICAL CONDITION. Visually inspect for material deterioration, defects, internal or external appearance, leaks or other deficiencies which affect and are not conducive to a professional work environment.

256. ACOUSTICS. Acoustic material should be sufficient to maintain noise levels which are not distracting to the work function under normal conditions.

257. SECURITY. Adequate locks and communications/surveillance systems shall be provided as required to ensure security.

258. DRINKING FOUNTAINS. Drinking fountains should be located in or in reasonable proximity of the work area and in good operating condition.

259. NOISE - INTERNAL. Question personnel about any interfering or unusual internal noise problems such as blowers, fans or other equipment noise.

260. NOISE - EXTERNAL. Question personnel about any interfering or unusual internal noise problems such as engine generators, run up areas, or helicopter 1anding pads.

NOTE: The next two evaluation paragraphs deal with important conditions which vary widely between locations. If conditions at the facility/ location being evaluated are not adequately covered by the factors as written, describe them in detail along with your evaluation grade. These two paragraphs are repeated in sections 1, 3, and 4 of the evaluation worksheet however, do not grade parking or accessibility in more than one section unless required to adequately describe conditions at the facility being evaluated.

261. PARKING. This paragraph considers the factors encountered from the time the employee enters the parking lot until the initial entry to the building complex housing the facility. Conditions may range from parking adjacent to the facility to parking which is located in remote lots requiring either long walks, riding a bus, or some other means of mechanical conveyor. Any unusual restrictions that are encountered in getting to the parking area, such as those associated with military bases or major airports should be considered under this paragraph. The physical condition of the parking area will be evaluated by Airway Facilities and is not to be considered in this score.

262. ACCESSIBILITY. This paragraph is a continuation of parking, paragraph 261. Considered here are those factors involved with the physical access to the administrative and/or operations area after an employee has made the initial entry into the building. Conditions may range from going up a private elevator/stair, passage through areas with locked gates, doors, security check points under another authorities jurisdiction, or crossing the roof of a terminal building. Access to the employee's work area should not cause excessive time to be wasted.

Par 255 Chap 6 Page 35

50

6480.17 09/04/85

263. COPY MACHINE SPACE. Adequate space should be available to accommodate copy machine equipment and supplies.

264. WORD PROCESSOR SPACE. Adequate space should be available to accommodate word processing equipment and supplies.

265. thru 274. RESERVED.

Chap 6 Page 36 Par 263

51

09/04/85 6480.17

CHAPTER 7. AIRWAY FACILITIES BUILDING REQUIREMENTS

NOTE: The following paragraphs apply to general areas of the facility. A great variety of requirements and configurations of the spaces will be encountered and, therefore, the paragraphs listed address general descriptions rather than specific criteria. Additional guidance will be provided by comparing the existing space with the appropriate standard design. (See appendix 4 for a listing of standard designs.) A11 paragraphs in this chapter shall be evaluated by Airway Facilities personnel.

SECTION 1 - SPACE REQUIREMENTS

275. ADMINISTRATIVE SPACE.

a. General. Administrative space shall include areas such as offices, lobbies, waiting rooms, etc. Some or all Airway Facilities administrative space may be located in rental space separate from the facility being evaluated.' In such case, this item applies only' to those areas located in the facility being evaluated.

b. Work Flow. The relationship of individuals and support spaces should conform to and compliment work flow requirements. In general, work should progress with the minimum amount of handling, travel, and delays possible.

c. Space Standards. The many variables associated with existing space configuration, available equipment, monetary limitations, etc., make rigid standards impossible to establish. The diagrams contained in the appendix 4 are to be used for general guidance to assure provision of adequate space for spec ific needs.

d. Safety. Exits, corridors, and stairways shall not contain equipment which will obstruct their use in an emergency.

276. LOCKER SPACE.

a. General. Every facility should have locker space to provide an area for facility personnel to store personal belongings while on or off duty.

b. Size and Location.

(1) The size of the locker rooms provided will be dependent on the number of personnel assigned to the facility. The amount of space required should be calculated as follows:

Chap 7 Par 275 Page 37

52

6480.17 6480.17

Airway Facilities Personnel - 5 Square Feet/Person

(2) Airway Facilities lockers may be located in mechanical rooms or equipment rooms as appropriate to the job assignment of these personnel.

c. Locker Quantity. Airway Facilities personnel are normally assigned one full size (12-inch by 60-inch) locker.

277. TOILET ROOMS.

a. General. Toilet facilities shall be evaluated in accordance with the table below. A single toilet is acceptable for occupancies of less than 15 persons.

Total Min imum Number Number of Employees/Shift of Toilets Requiredt 15 1 16 - 35 2 36 - 55 3 56 - 80 4 81 - 110 5 111 - 150 6 Over 150 1 for each additional 40 employees

† Separate men's and women's toilet rooms must be provided except for rooms serving occupancies of less than 15.

b. Equipment and Accessories. Toilet rooms shall be equipped with toilet partitions and accessories including, but not limited to; mirrors, soap dispensers, towel dispensers, waste receptacles, coat hooks, toilet paper holder, grab bars (handicapped toilets), and sanitary napkin and tampon dispenser (women's toilets).

278. COMMUNICATIONS EQUIPMENT ROOM.

a. General. Every facility shall have a secure area to house electronic equipment necessary for radio communications. A locking rack enclosure shall be acceptable in lieu of a separate secure room in low activity level control towers (Level I, Level II).

b. Location. This room may be located in the tower shaft; however, when the facility contains a TRACON, it should be located adjacent to above or below this room. The radar equipment room may be collocated in this area.

Chap_7 Page 38 Par 276

53

09/04/85 6480.17

c. Size and Shape. The size of the room is determined by the amount of equipment required plus additional expansion space. The ceiling should provide a minimum of 1 foot clear above all equipment for mechanical and electrical installations.

d. Finishes. Exposed ceilings painted white are preferred; however, suspended ceilings are acceptable. Floor surface should be in good condition.

279. RADAR EQUIPMENT ROOM.

a. General. Every facility shall have a secure area to house equipment necessary for radar surveillance of air traffic and/or automated radar terminal system (ARTS) control.

b. Location. This room may be located in the tower shaft; however, when the facility contains a TRACON, it should be located adjacent to above or below this room. The communications equipment room may be collocated in this area.

c. Size and Shape. The size of this room is determined by the number and type of components required for the activity level of the facility and space for future expansion. The ceiling should provide a minimum of 1 foot clear above all equipment for mechanical and electrical installations.

d. Finishes. Exposed ceilings painted white are preferred; however, suspended ceilings are acceptable. Floor surface should be in good condition.

280. TELEPHONE EQUIPMENT ROOM.

a. General. This room contains telephone equipment which is associated with air traffic control operations.

b. Location. This room should be located adjacent to or in proximity to the communications equipment room and the radar equipment room.

c. Size and Shape. The size of this room will be determined by the total number of equipment racks projected to be required for the facility.

d. Exposed ceilings painted white are preferred; however, suspended ceilings are acceptable. Floor surface should be in good condition.

e. Special Requirements. If batteries are used, this space must be adequately ventilated. This room must be a secure area.

f. Special Note. At locations having a planned integrated communication switching system (ICSS), the requirements for this equipment must be evaluated in lieu of the telco room. Basic requirements outlined above for the telco room will apply; however, the size requirements shall be significantly reduced.

Chap 7 Par 278 Page 39

54

6480.17 09/04/85

281. ENGINE GENERATOR ROOM.

a. General. This room contains the engine generator used to supply emergency power to all equipment on the emergency power circuit.

b. Size and Shape. The room should be sized to provide adequate space for all necessary equipment including a minimum of 2 feet clear space on all sides of equipment for maintenance. See chapter 10, section 3 for clearance requirements around electrical equipment.

c. Acoustics. With engines operating at peak capacity, the noise levels should not exceed NC45. Question the facility staff concerning the amount of vibration which is transferred to adjacent areas.

d. Security. Due to the critical nature of the function served by the engine generators, this area of the building must be secure. All openings into this room greater than 96 square inches should be protected by burglarproof construction such as iron bars spaced not more than 5 inches apart or steel grilles of minimum No. 9 gauge, 2-inch square mesh material. (See FAA Order 1600.6 Protection of Agency Property.)

e. Access. Exterior doors should be large enough to accommodate maintenance and replacement of equipment.

f. Fire Protection. The engine generator room shall be isolated from other areas of the building by construction of not less than 2 hour fireresistive construction. A fire detector and fire alarm should be provided in this room.

282. MECHANICAL EQUIPMENT ROOM.

a. General. This area houses operating elements of mechanical equipment not located elsewhere such as exterior or on the roof.

b. Size and Shape. The room should be sized to provide adequate space for all necessary equipment including space required for maintenance. Refer to the chapter 9 for ease of maintenance requirements.

c. Acoustics. With equipment operating at peak capacity, the noise levels should not exceed NC45 in the cab, TRACON operations room and office areas, and NC50 in all other areas. Question the facility personnel concerning the amount of vibration and noise interference which is transferred to adjacent areas.

d. Fire Protection. Mechanical rooms shall be. isolated from other areas of the building by construction of not less than 1 hour fire-resistive construction.

Chapo? Page 40 Par 281

09/04/85 6480.17

283. ELECTRICAL EQUIPMENT ROOM. This room provides space for the facility electrical 'equipment. This area of the building shall be secure and entry to the area controlled to prohibit unauthorized personnel. Refer to chapter 10 for clearance and equipment enclosure requirements.

55

284. PCS/BATTERY ROOM.

a. General. This area provides space for PCS equipment and batteries. This area of the building shall be secure and entry to the area controlled to prohibit unauthorized personnel.

b. Special Requirements. This area should be adequately ventilated to remove excess heat from the PCS and gases from the battery area. The battery area shall have an eye wash and shower in the room or directly adjacent to it.

285. STORAGE ROOMS.

a. General. Storage rooms should provide for the secure and orderly storage of items required for facility operations and maintenance.

b. Size and Shape. Storage rooms may be any size or shape but should be capable of holding the necessary material or equipment for the area they serve.

c. Security. Storage rooms should be provided with a cylinder lockset. The lockset function shall allow entrance by key only (outer knob always fixed and inner knob always free).

286. CABLE CHASES

a. General. Cable chases provide vertical access ways for communications and electrical cabling.

b. Access. Cable chases should have access openings as required to accommodate installation of additional cable runs.

c. Capacity. Cable chases should be large enough to accommodate all planned or programmed requirements or a minimum of 10 percent future growth.

287. INTERNAL FLEXIBILITY.

a. General. Future flexibility is the ability of a facility to accommodate changing requirements by internal reorganization.

b. Spatial Flexibility. Items to be considered when evaluating internal flexibility include possible reorganization of departments, combination of similar functions into one area, and the amount and utilization of storage space at the facility.

Chap 7 Par 283 Page 41

56

6480.17 09/04/85

c. Systems Flexibility. The mechanical and electrical systems in the facility must be capable of adapting to future needs. To accommodate these changes, systems must be easily adaptable and have sufficient capacity to provide for increased requirements.

d. Operational Flexibility. Based on projected future requirements, the facility must be able to accommodate change in those areas most likely to be affected. If no projected growth requirements are available, a 10 percent growth factor should be used.

288. BUILDING EXPANSION.

a. General. Future expansion refers to the ability of a facility to expand by incremental future additions. If future operational and technical requirements can be accommodated by internal flexibility, this paragraph does not apply.

b. Operational/Technical/Administrative Expansion. The coordinator should obtain the budgeted and planned expansion program for the facility. Based on these projected future requirements, the facility must be able to accommodate incremented expansion in those areas most likely to experience growth. If a future expansion program has not been formulated for the fac ility, a 10 percent expansion factor shouīd be applied.

c. Support Services. The site must be capable of accepting not only the building addition but also any increase in area required for support buildings, parking lots, access roads, etc.

289. thru 297. RESERVED.

SECTION 2 - BUILDING CODE

NOTE: The entries in this section are intended to provide general guidance although specific requirements are stated. The evaluator should not downgrade a facility for deminimust dimensional violations.

tDeminimus - A condition which is in violation of any occupational safety or health standard but that has no immediate or direct relationship to safety or health is deminimus; that is, a condition that presents no apparent hazard to employee safety and health, such as minor difference in certain dimensions. While abatement may be desirable, no corrective action is required for deminimus violations.

298. NUMBER OF EXITS

a. General. Every building, structure, or portions thereof shall be provided with exits as outlined in this paragraph.

Chap7 Page 42 Par 287

57

09/04/85 6480.17

b. Number of Exits Required.

(1) Buildings or portions thereof complying with the conditions set forth below shall have a minimum of one required exit from each occupied level.

(a) Base buildings having a total floor area of less than 3,000 square feet on one or more stories aboveground. No floor above the ground level shall exceed 1,500 square feet. (b) Tower shafts, either functional' or non-functional.

(c) Control cabs.

(2) All buildings or portions thereof not complying with the provisions established in (1) above shall have a minimum of 2 required exits from each occupied level.

(3) Any room larger than 3,000 square feet or having an occupancy capacity of 30 or more shalǐ have a minimum 'of 2 exits.

299. EXIT DISTANCE. The maximum distance of travel from any point to an exterior door, horizontal exit, exit passageway, or enclosed fire stair shall not exceed 150 feet.

300. LABELED DOORS.

a. General. The door assembly including the doorway, frame, door, and necessary hardware shall conform to the requirements of this paragraph.

Continue reading ↓ 120 of 425 passages shown