This order provides direction and guidance regarding the testing of drinking water at ATO facilities. The objectives of this order are to standardize drinking water testing procedures, define roles and responsibilities for managing drinking water issues, and provide procedures for responding to drinking water quality issues.

Official source ↗ Open PDF

U.S. DEPARTMENT OF TRANSPORTATION ORDER FEDERAL AVIATION ADMINISTRATION JO 3900.61A

U.S. DEPARTMENT OF TRANSPORTATION ORDER FEDERAL AVIATION ADMINISTRATION JO 3900.61A

Air Traffic Organization Policy Effective Date:

04/09/2019

SUBJ: Drinking Water Testing at Air Traffic Organization Facilities

The Air Traffic Organization (ATO) is committed to providing potable water to its employees in accordance with Environmental Protection Agency (EPA) and Occupational Safety and Health Administration (OSHA) regulations and labor union agreements. This order provides direction and guidance regarding the testing ofdrinking water at ATO facilities. The objectives ofthis policy are to:

• Standardize drinking water testing procedures at A TO facilities; • Define roles and responsibilities for managing drinking water issues; • Provide procedures for responding to drinking water quality issues.

This policy must be implemented immediately for all future drinking water testing events. For facilities that have conducted testing within the previous three years, protocols within this policy must be implemented during the next scheduled sampling event. It is not necessary to retest drinking water that has been sampled within the last three years to comply with this policy.

Chief Operating Officer Air Traffic Organization

Distribution: Electronic Initiated By: AJW-23

1. Purpose of This Order. This order provides direction and guidance regarding the testing of drinking water at ATO facilities. The objectives ofthis order are to standardize drinking water testing procedures, define roles and responsibilities for managing drinking wat~r issues, and provide procedures for responding to drinking water quality issues. ·

2. Audience. All ATO employees and managers who are involved in drinking water testing at ATO facilities.

3. Where Can I Find This Order. You can find an electronic copy ofthis order on the Directives Management System (DMS) website: https://employees.faa.gov/tools resources/orders notices/. Or go to the MyF AA employee website, select "Tools & Resources" and then select "Orders & Notices".

4. What This Order Cancels. FAA Order JO 3900.61, Drinking Water Testing at Air Traffic Organization Facilities, dated September 1, 2010.

5. Explanation of Policy Changes. This revised order expands testing requirements to leased facilities. The order also updates sampling protocols, test methods, and testing parameters.

6. Roles and Responsibilities.

a. Air Traffic Control (ATC) Facilities, Environmental, Occupational Safety and Health (EOSH) Services. The ATC Facilities EOSH Services is responsible for maintaining and updating this drinking water policy, coordinating funding requests for testing, and providing technical assistance to resolve drinking water issues.

b. ATO Project Managers/Project Implementers. ATO Project Managers/Project Implementers are responsible for ensuring the testing ofdrinking water at facilities affected by projects such as newly constructed, renovated and newly plumbed systems at ATO facilities.

c. Facility Managers. Facility Managers, for purposes ofthis order, are the persons who have overall responsibility for ensuring that National Airspace System maintenance activities are performed at an ATO facility. Facility Managers are responsible for requesting appropriate funding to meet the requirements ofthis order, ensuring that required drinking water testing is conducted and results analyzed for facilities they manage, and implementing any necessary corrective actions. Facility Managers will also be responsible for retaining testing results and communicating with employees and union representatives regarding drinking water issues at that facility.

d. Contracting Officer Representatives (COR). CORs are staff designated to facilitate administration ofa lease on behalf ofthe Real Estate Contracting Officer (RECO). CO Rs are responsible for obtaining and disseminating drinking water test results from the lessor to facility management, where the lease specifies that testing drinking water is the lessor's responsibility.

e. ATO EOSH Professionals. ATO EOSH Professionals, including Safety and Environmental Compliance Managers and Service Center Environmental Requirements Specialists, will provide technical and analytical assistance to Facility Managers in implementation ofthis order as requested, including development ofsampling plans and corrective action plans.

f. Employees. Employees are responsible for elevating any drinking water quality issues to their supervisor or Facility Manager.

7. Scope and Applicability.

a. Owned facilities. This policy applies to all A TO owned facilities, except for:

(1) Facilities where all potential drinking water sources have signs posted indicating tha the water is non-potable.

(2) Facilities that meet the definition ofa "public water system" as defined by the Safe Drinking Water Act. Because these facilities must comply with the more comprehensive sampling and testing requirements of 40 CFR Part 141, compliance with those requirements fulfills the drinking water testing requirements ofthis order.

b. Leased facilities. This policy applies to all Federal Aviation Administration (FAA) leased facilities (to include non-ATO leased facilities) where ATO employees have access to drinking water. In the case ofleased facilities, FAA's preferred approach is to require the lesso to conduct drinking water testing in accordance with the requirements ofthis order and provide the results to the FAACOR.

c. Effective Date. Protocols within this policy apply to the next scheduled sampling event. It is not necessary to retest drinking water that has been sampled within the last three years to comply with this policy.

8. Testing Requirements.

a. Testing for Newly Constructed, Renovated or Newly Plumbed AT() Facilities.

(1) Drinking water will be tested for lead, copper, total coliforms at newly constructed, renovated and newly plumbed systems at ATO facilities, prior to use for consumption. The renovation at the facility must be as such that the water piping/delivery system is affected.

Samples for testing ofdrinking water will be taken downstream ofnew plumbing. The testing will be conducted prior to the contractor acceptance inspection (CAI). Any exceedance from th action levels identified in paragraph 9.b discovered during the testing must be mitigated as part ofthe CAI process.

(2) The Safe Drinking Water Act (SDWA) mandates the use oflead-free materials in public water systems and the plumbing offacilities that provide water for consumption. For

t

r

e

construction, renovation, and repair projects, the use of solder and flux containing more than 0.2 percent lead and domestic water pipe or pipe fittings with a weighted average lead content of wetted surfaces ofmore than 0.25 percent is prohibited.

b. Testing of Facilities that obtain Drinking Water from Non-Public Water Systems. Where facilities receive drinking water from non-public water systems ( e.g., well, surface waters) that are not federally regulated by the SOWA, drinking water must be analyzed at least annually for nitrates, total dissolve solids, total coliforms, and any other contaminants that are appropriate based on local conditions such as fluoride, VOCs and radon, or as determined by the state or local requirements or other FAA orders for drinking water quality ( whichever is the most stringent). You should also test your well immediately ifthere are known problems with ground water or drinking water in your area; conditions near your well has changed significantly (i.e. flooding, land disturbances and new construction or industrial activity); you replace or repair any part ofthe your well system; you notice a change in your water quality (i.e. odor, color, taste). A TO EOSH Professionals should be consulted for the development ofan appropriate sampling plan for these facilities.

c. Testing of Facilities that obtain Drinking Water from Public Water Systems. For facilities where water is supplied by a public water system (e.g., municipal water), drinking water will be tested at least once every three years for lead, copper, and total coliforms. Samples may also be tested for other parameters ifthere are other concerns with the facility's drinking water (see Appendix C, Other Possible Tests Based on Visual Observations or Other Factors, for other possible tests). The result ofthese samples should be taken in conjunction with the local Consumer Confidence Report (CCR) ofthe water treatment facility that supplies the water for the facility being tested for a complete understanding ofthe drinking water quality at the site.

d. Testing in Response to Incidents or Emergencies. Ifan action occurs that could impact the facility's drinking water, testing may be needed to confirm the quality ofthe facility's drinking water. Circumstances that may indicate the need for this testing may include, but are not limited to:

(1) Facilities using well water where groundwater contamination has occurred.

(2) Water main breaks prior to water entering the facility.

(3) Replacement ofbuilding water distribution system appurtenances

(4) Public advisories (e.g., boil water advisory) issued from local water suppliers.

(5) Objections to water odor, taste, or color by one or more employee.

(6) Sampling plan conducted in accordance with a previously established corrective action plan to restore the drinking water to potable standards.

Ifthe testing in response to incidents or emergencies meets the sampling requirements of paragraphs (b) and ( c ), the test may serve as a triennial test.

9. Procedures for Sampling and Analysis.

a. Drinking water samples must be obtained using the sampling procedures outlined in Appendix B, Drinking Water Sampling Protocols.

b. Sample analysis must be conducted by a drinking water laboratory certified by EPA or the state for each drinking water parameter being tested. Laboratories supporting public water systems must use EPA-approved analytical methods when analyzing samples. In accordance with 40 CFR 141.23 and 40 CFR 141.21, the test methods and action levels to be used are:

Table 1.

Parameter Test Method Action ;Level Lead (Pb) EPA Test Method Total Inductively Coupled plasma-Mass Spectrometry (ICP-MS) 200.8 or Standard Method (SM) 3113B

0.015 mg/I ·'

Copper (Cu) EPA Test Method Total ICPMS 200.8 or SM3111B

1.3 mg/I

Total Coliforms Presence/ Absence

Microbiological Parameters utilizing

SM9221D

IAny positive coliform test iwill be considered an !indicator ofcontamination

10. Elevated Contaminant Level Response Process. When it has been determined that the water quality inside the facility does not meet current EPA primary drinking water standards or exceeds EPA-established action levels, the Facility Manager will be responsible for ensuring the following actions are conducted:

a. Post signs at all affected fixtures, informing employees not to use the fixtures until further notice. Signage should indicate "Not Potable" or "Do Not Drink".

b. Develop a corrective action plan to document the actions that will be taken to restore water quality. ATO EOSH Professionals should be consulted for development of an appropriate corrective action plan. The corrective action plan must document and address the following aspects:

(1) Employee notification and sanitation procedures;

(2) Actions needed to determine source ofcontamination;

(3) Actions taken to restore water to potable water standards ( e.g., repair/replacement of affected supply system components);

(4) Actions taken to provide employees potable water (Bottled water may only be provided when drinking water at the site has been deemed unsafe for human consumption in accordance with FAA policy in the Acquisition Management System (http://fast.faa.gov)); and

(5) Sampling plan to confirm water meets potable water standards within ten (10) days following correction/abatement.

c. Inform facility supervisors and employees ofthe corrective action plan contents.

11. Recordkeeping. The Facility Manager must retain copies ofthe water quality test results for the previous three years on file. Corrective action plan documentation must be retained for three months after the corrective action and necessary follow-up have been completed.

Appendix A

Appendix A

Appendix A. Administrative Information

1. Distribution. The order will be distributed electronically and can be found at Directives Management System (DMS) website: https://employees.faa.gov/tools resources/orders notices. ATO offices may obtain a hard print copy ofthe order by contacting EOSH Services.

Appendix A. Administrative Information

2. Background. The SDWA of 1974 was established to protect the quality of drinking water in the United States. The Act authorizes EPA to establish minimum standards to protect tap water and requires all owners or operators ofpublic water systems to comply with these primary (health-related) standards. These standards are found in 40 CPR Part 141. In addition, the OSHA regulations require that potable water be provided in all places ofemployment, for drinking, washing, and cooking (29 CPR §19I0.141(b)).

3. Definitions.

a. Coliform. A group ofrelated bacteria whose presence in drinking water may indicate contamination by disease-causing microorganisms.

b. Consumer Confidence Report (CCR). An annual drinking water report circulated to users ofa community water system to provide information on the water's quality.

c. First Draw Sample. A water sample that has stood motionless in the plumbing pipes for at least six hours and is collected without flushing the tap.

d. Flush Sample. A water sample that has not been in contact with the plumbing system for an extended period oftime.

e. Potable Water. Water that meets the standards for human consumption ofthe state and local authority having jurisdiction or water that meets the quality standards prescribed by the EPA's National Interim Primary Drinking Water Regulations, published in 40 CPR Part 141.

f. Public Water System (PWS). An entity that provides water for human consumption through pipes or other constructed conveyances to at least 15 service connections or serves an average ofat least 25 people for at least 60 days a year.

Appendix B

Appendix B

Appendix B: Drinking Water Sampling Protocols,

Preparation for Sampling

1. Contact a certified drinking water testing laboratory or certified environmental laboratory to obtain sample containers and detailed sampling instructions. In the absence ofdetailed instructions from the lab, follow the protocol below.

2. Perform an inventory of all drinking water sources, such as drinking water fountains, break room/cafeteria sinks, icemakers, and any other sink or water source known to be or visibly confirmed to be used for consumption (e.g., coffee maker or cups are nearby). In addition, identify all water sources that are not routinely used for drinking water, but where water could be accidentally ingested (e.g., showers, bathroom sinks). ·

3. Ensure that the water fixtures to be sampled for copper and lead are not used for at least 6 hours before sampling by marking each fixture to be sampled with a sign stating "DO NOT USE". It is permissible to use tape to make the fixture inoperable for the required 6 hours. (Note: Do not use a shut offvalve to shut the water off at the fixture because it is possible to release some quantities of solder and metal deposits in the valve.)

4. Inform facility staff that water is being tested at their facility and request that they observe signs that will be posted on various fixtures in the facility.

General Sampling Instructions

1. To prevent sample contamination, use antiseptic techniques. Wash hands with soap and water or sanitizer and use nitrile or powder-free latex gloves. To collect the sample, hold the sample container in one hand and remove the cap with the other hand. Do not touch the opening or any interior part ofthe sample container or cap. Do not set the cap down.

2. Immediately replace cap and tighten securely. Label bottle with facility name/identification (ID), sample location/ID, name ofperson sampling, date, and time of sample taken. The samples must be immediately placed in a location that is <50°F and kept out ofdirect sunlight. Do not allow the samples to freeze. Bacteriological samples must be received the same day or within 24 hours ofthe samples being taken. Lead and copper samples must be received by the laboratory within 14 days of sampling ifnot acid preserved. Follow the laboratory's shipping instructions.

Sampling for Lead and Copper

1. Test all inventoried drinking water sources for lead and copper, except those that are not routinely used for drinking water, but where water could be accidentally ingested ( e.g., showers, bathroom sinks). Also exclude from sampling any fixtures with devices designed to change the water composition, such as water softeners and reverse osmosis devices.

Appendix B

2. Collect a "first-draw" or "first-flush" sample from each selected fixture. To achieve a first draw, do not run water for at least 6 hours before collecting these samples. Do not remove aeration devices prior to sampling. Turn the cold water on and fill the sample container to the neck ofthe bottle or the fill line with the first flow from the faucet. Do not allow any water to run before collecting the sample.

3. Collect "purged-line" or "flushed" samples in addition to the first draw san;iples for 10 percent or at least two ofthe fixtures being sampled. This provides a sample that has not been in contact with the plumbing system for an extended period oftime. To collect this second sample, allow the tap to run for at least five minutes, then fill to the neck ofthe bottle or the fill line.

4. Ifresults show lower levels oflead or copper in the first-draw sample than the flushed sample for the same fixture, the source ofthe lead or copper contamination is likely the fixture itself. Ifexceedances are happening in multiple fixtures and/or first draw and flushed samples are both high, the lead and copper contamination is most likely coming from components ofthe facility plumbing, such as pipes or fittings, or from a source outside the facility.

Sampling for Total Coliforms

1. Test all inventoried drinking water sources that are routinely used for drinking for total coliforms, except fixtures that are threaded and fixtures that have recently been repaired or replaced. In addition, test 5 percent or at least one ofthe fixture that are not routinely used for drinking, but where water could be accidentally ingested (e.g., showers, bathroom sinks). When sampling for total coliforms, remove any screens or aerators from the fixtures, unless otherwise instructed by the certified laboratory.

2. Clear the line by running cold water only at full force for at least 5 minutes. Reduce cold water flow to a clear stream with no bubbles. Fill the sample container to the neck ofthe bottle or the fill line.

Appendix C

Appendix C: Other Possible Tests Based on Visual Observations or

Appendix C: Other Possible Tests Based on Visual Observations or

Other Factors Table

Table 2.

Symptom Description Recommended Tests Stained plumbing fixtures cooking utensils and/or laundry

Red or brown Iron

Reddish-brown slime Iron bacteria Black Manganese Green or blue Coooer Chalkv white Hardness Off-color water Cloudy Turbidity, suspended solids

Black Hydrogen sulfide, manganese Brown or yellow Iron, tannic acid Unusual taste and odor Rotten egg Hydrogen sulfide

Metallic Ph, corrosion index, iron, zinc, copper, lead Salty Total dissolved solids (TDS), chloride, sodium Septic, musty, earthy Total coliform bacteria, methane Alkali, bitter pH, total dissolved solids (TDS) Gasoline or oil Hydrocarbon scan Soapy Surfactants (surface-active agents) Corrosive water Deposits, pitting of plumbing fixtures

Corrosion index, pH, copper, lead

Radon Undetectable by taste, smell, or sight. Potentially present in well water in regions noted for high radon levels

Radon

ATC ATO CCR COR DMS EOSH EPA EPS FAA NPDWR

ATC ATO CCR COR DMS EOSH EPA EPS FAA NPDWR

OSHA PIM ppb ppm PWS SDWA

Appendix D

Appendix D. Acronym List

Air Traffic Control Air Traffic Organization Consumer Confidence Report Contracting Officer Representative Directives Management System Environmental and Occupational Safety and Health Environmental Protection Agency Environmental Protection Specialist Federal Aviation Administration National Primary Drinking Water Regulations Occupational Safety and Health Administration Program Implementation Manager parts per billion parts per million Public Water System Safe Drinking Water Act