Order 3900.16 Safety Alert-Fire Hazard 1.5 Kva 240/32 Volt Transformer

This document is cancelled. It may have been replaced. Check the official source before relying on it.

Official source ↗ Open PDF

DEPARTMENT OF TRANSPORTATION ORDER AVIATION ADMINISTRATION GREAT LAKES REGION

DEPARTMENT OF TRANSPORTATION ORDER AVIATION ADMINISTRATION GREAT LAKES REGION

28 Jul 72

SUBJ: SAFETY ALERT - FIRE HAZARD 1.5 KVAt 240/32 VOLT TRANSFORMER

1. PURPOSE. This order is to alert the field of a possible fire hazard when using 1.5 KVA, 240/32 volt transformer.

2. DISTRIBUTION. This order is distributed to section level in the Airway Facilities Division and all Airway Facilities Sector Offices.

SUBJ: SAFETY ALERT - FIRE HAZARD 1.5 KVAt 240/32 VOLT TRANSFORMER

3. ACTION. At facilities where these transformers are in use, they should be thoroughly inspected at regular intervals for wiring defects and overheating. Corrective action: Redo all splices using mechanical connectors. When in doubt~ remake the connections.

4. BACKGROUND. A VORTAC in the Great Lakes Region was badly damaged recently due to a fire thought to be caused by a bare conductor due to insulation failureD a loose connection, or a poorly taped mechanical connector coming in contact with

the cover of the wiring cabinet causing an arcing condition. Molten metal from the cover plate fell on the indoor-outdoor carpeting which ignited and the ensuing events destroyed the TACAN, part of the VOR, some test equipment 9 acoustical tile. TACAN baffles, etc. The exterior and interior of the building suffered considerable smoke damage.

H.~ Chief. Airway Facilities Division