POLYCHLORINATED BIPHENYLS (PCBs) IN THE NATIONAL AIRSPACE SYSTEM
JUNE 20 1991 JUNE 20, 1991
AEE-20 A W(NS/SM/LG/AS/AP/CS/EE/AM) 3 A W(VN) 2 AEE 20 A-W(NS/SM/LG/AS/AP/CS/EE/AM)-3: A-W(VN)-2;
A-XYZ-2; A-X(AF)-3; A-Y(DE/FA)-3; A-FAF-0(LTD); ZLR-442
FOREWORD
This order provides agency policy, procedures, and responsibilities for implementation and compliance with regulations concerning the use, storage, transport, and disposal of substances that contain polychlorinated biphenyls (PCB) in the National Airspace System.
A-XYZ-2; A-X(AF)-3; A-Y(DE/FA)-3; A-FAF-0(LTD); ZLR-442
James B. Busey Aministrator
Page i (and ii)
6/20/91
TABLE OF CONTENTS
CHAPTER 1. GENERAL
1. Purpose 2. Distribution 3. Cancellation 4. Background 5. Explanation of Changes 6. Definitions 7. Requests for Information 8. Forms and Reports 9. Authority to Change this Order 10. Responsibilities 11. Policy 12. PCB Coordinator 13. Funding and Budget Request Procedures 14.-199. Reserved.
CHAPTER 2. EMERGENCY PROCEDURES
CHAPTER 2. EMERGENCY PROCEDURES
200. General 201. Precautionary Measures 202.-299. Reserved
CHAPTER 3. PROCEDURES
SECTION 1.
1050.14A
Page
1
1 1 1 1 2 2 8 8 8 9 10 10 11 11
13
13 17 17
19
AUTHORIZED USES, INSPECTION REQUIREMENTS, AND SERVICING CONDITIONS FOR PCB EQUIPMENT
300. Responsible Agent 301. PCB Items 302. Dielectric Fluids and Other PCB Fluids 303. Exposure Risk to Food and Feed Products 304. Transformers 305. Capacitors 306. Electromagnets, Switches, and Voltage Regulators . 307. Circuit Breakers, Fuses, Filters, Reclosers, and Cable 308. Heat Transfer Systems 309. Hydraulic Systems 310.-314. Reserved
AUTHORIZED USES, INSPECTION REQUIREMENTS, AND SERVICING CONDITIONS FOR PCB EQUIPMENT
19 19 19 19 20 20 26
28
29 30 30 30
Page iii
1050.14A
SECTION 2. TESTING 315. Testing Requirements 316.-319. Reserved
SECTION 3. MARKING 320. Marking Requirements
6/20/91
Page
30 30 31
31 31 33
g Requirements
Figure 3-1. TSCA PCB Marking 321. Labeling Design Figure 3-2. Large PCB Mark Figure 3-3.s Smail PCB Mark Figure 3-4. PCB-Contaminated Mark Figure 3-5. Certified Mark 322. Marking Unidentified Items 323.-329. Reserved
SECTION 3. MARKING 320. Marking Requirements
SECTION 4. RECORDS AND REPORTS 330. General Recordkeeping Figure 3-6. PCB Inventory Record 331. Records for Sale of PCB Items 332. PCB Waste Disposal Records and Reports 333. PCB Management Checklist 334.-339. Reserved
SECTION 5. STORAGE 340. Approved Storage 341. Long Term Storage 342. Long Term Storage Facilities 343. Short Term Storage 344. Storage Marking 345. Storage Handling Equipment 346. Storage Containers 347.-349. Reserved
SECTION 6. DECONTAMINATION 350. PCB Containers 351. Mobile Equipment 352.-359.Reserved
SECTION 6. DECONTAMINATION 350. PCB Containers 351. Mobile Equipment 352.-359.Reserved
SECTION 7. DISPOSAL 360. General
34 35 35 35 35 34 34
34 34 37 38 39 40 40
40 40 40 41 41 42 42 43 43
43 43 44 44
44 44 45
Spills, Leaks, and Other Uncontrolled Discharges
361. 362. PCB Cleanup Requirements Figure 3-7. PCB Cleanup Requirements 363.-369. Reserved
SECTION 7. DISPOSAL 360. General
Page iv
47 49-50 44
6/20/91
SECTION 8. TRANSPORT 370. Vehicle Marking 371. Liquid PCB's Packaging 372. Non-liquid PCB's Packaging 373. Marking 374. Manifests 375.-399. Reserved
SECTION 9. SALE OF PCB ITEMS 400. Requirements 401. Unmarked Items 402. Prohibited Sales 403. Bill of Sale Figure 4-1. Bill of Sale for PCB 1
1050.14A
Page
51 51 51 51 51 51 51
51 51 51 51 52
Equipment
APPENDIX 1.
53
EPA Rules For Controlling Polychlorinated Biphenyls Under The Toxic Substances Control Act (40 CFR 76i); Approved Disposal Companies; and Regional
Contacts on PCB (45 pages)
APPENDIX 2. Fluids Containing PCB's (1 page)
APPENDIX 2. Fluids Containing PCB's (1 page)
APPENDIX 3.
EPA
Fluids That Do Not Contain PCB's (1 page)
APPENDIX 4. PCB Management Checklist (7 pages)
Page v (and vi)
CHAPTER 1. GENERAL
1. PURPOSE. This order updates agency policy, procedures, and responsibilities for implementation and compliance with the Environmental Protection Agency (EPA) Final Rule, 40 CFR Part 761, Polychlorinated Biphenyls (PCB's) Manufacturing, Processing, Distribution in Commerce, and Use Prohibitions (see Appendix 1).
CHAPTER 1. GENERAL
2. DISTRIBUTION. This order is distributed to the branch level in the NAs Transition and Implementation Service, Systems Maintenance Service, Logistics Service, Office of Airport Safety and Standards, Office of Airport Planning and Programming, Office of Civil Aviation Security, Office of Environment and Energy, and Office of Aviation Medicine, and to the division level in the Regions with a branch level distribution in the Airway Facilities Division; to the division level at the FAA Technical Center; to the division level at the Aeronautical Center with a branch level distribution in the Facility Support Division and the FAA Depot at the Aeronautical Center; to the division level in the Aviation Standards National Field Office and in the Office of Advanced Design and Management Control; and a limited distribution to the Airway Facilities Field Offices.
3. CANCELLATION. Order 1050.14, Agency Compliance with Regulations Concerning Uses of Polychlorinated Biphenyls (PCB's) in the National Airspace System, dated May 18, 1983, is canceled.
4. BACKGROUND.
a. The Toxic Substances Control Act (TSCA), P.L. 94-469, designated PCB's as hazardous chemical substances. PCB's, such as askarel products, are commonly found as fluids or mixtures in such items as capacitors, transformers, fluorescent light ballasts, electric motor'coolants, hydraulic machinery, and heat transfer systems. PCB's are also found in voltage regulators, switches, circuit breakers, reclosers, and cables. 40 CFR Part 761, issued by EPA, outlines procedures for use, storage, and disposal of PCB and pCB items when they are removed from service. The rule does not require removal and disposal of many of these PCB items before their service lives have ended. (Chapter 3, Section 1, discusses use authorizations of various types of PCB Items.) 40 CFR Part 761 also establishes requirements for inspection, recordkeeping, marking, and transporting of PCB's. Unless otherwise specified, the terms "pCB", "pCBis", and "PCB items" used in this order refer to chemical substances and combinations of substances that contain at least 50 ppm of PCB's (on a dry weight basis).
Chap,1 Page 1 Par 1
b. It should be noted that Section 15 of the TSCA states that failure to comply with the EPA PCB regulations is unlawful. Section 16 imposes liability for civil penalties upon any person who violates these regulations, and the EPA Administrator has established by regulation (40 CFR Part 702) a procedure for citizens to file suit to remedy these violations. Section 16 also subjects a person to criminal prosecution for a violation which is knowing or willful. In addition, Section 17 authorizes Federal district courts to enjoin activities prohibited by these EPA regulations, and to compel the taking of actions required by these EPA regulations.
5. EXPLANATION OF CHANGES. This revision:
a. Contains additional restrictions on the use of PCB Items.
b. Provides guidance on the sale and transfer of PCB equipment and requires a bill of sale to be completed for all such transactions.
c. Explains the "cradle-to-grave" tracking system that uses an EPA shipping manifest when PCB items are transported off-site.
d. Contains a cleanup policy for PCB spills. It establishes numerical cleanup standards, reporting requirements, and recordkeeping requirements.
e. Requires a PCB Coordinator for each region and center.
6. DEFINITIONS. This list of definitions pertain to this order and is abstracted from 40 CFR Part 761. The more complete list of definitions in Part 761 may be a useful, but not an essential adjunot to thie order.
a. Capacitor means a device for accumulating and holding a charge of electricity and consisting of conducting surfaces separated by a dielectric.
b. Small capacitor means a capacitor which contains less than 1.36 ky (3 lbs) of dielectric fluid. The followiny assumptions may be used if the actual weight of the dielectric fluid is unknown. A capacitor whose totai volume is less than 1,639 cubic centimeters (100 cubic inches) may be considered to contain less than 1.36 kg (3 lbs) of dielectric fluid and a capacitor whose total volume is more than 3,278 cubic centimeters (200 cubic inches) must be considered to contain more than 1.36 kg (3 lbs) of dielectric fluid. A capacitor whose volume is
Chap1 Page 2 Par 4
between 1,639 and 3,278 cubic centimeters may be considered to contain less than 1.36 kg (3 lbs) of dielectric fluid if the total weight of the capacitor is less than 4.08 kg (9 lbs).
c. Large high voltage capacitor means a capacitor which contains 1.36 kg (3 lbs) or more of dielectric fluid and which operates at 20o0 volts or above (a.c. or d.c.).
d. Large low voltage capacitor means a capacitor which contains 1.36 kg (3 lbs) or more of dielectric fluid and which operates below 2000 volts (a.c. or d.c.).
e. Disposal means to discard, throw away, or otherwise complete or terminate the useful life of PCB items, or PCB contaminated materials, whether such action is intentional or accidental.
f. Double wash/rinse means a minimum requirement to cleanse solid surfaces (both impervious and nonimpervious) two times with an appropriate solvent or other material in which PCB's are at least 5 percent soluble (by weight). The procedure for conducting this type of cleanup is contained in 40 CFR 761.
g. Facility means any building, installation, structure, equipment, aircraft, vehicle, and property owned, leased, operated, or maintained for use by the FAA.
h. High-contact industrial surface means a surface in an industrial setting which is repeatedly touched, often for relatively long periods of time. Manned machinery and control panels are examples of high-contact industrial surfaces. High-contact industrial surfaces are generally of impervious solid material. In contrast, low-contact industrial surfaces include ceilings, walls, floors, roofs, roadways and sidewalks in the industrial area, unmanned machinery, concrete pads beneath electrical equipment, curbing exterior structural building components, indoor vaults, and pipes.
i. Impervious solid surfaces means solid surfaces which are nonporous and thus unlikely to absorb spilled PCB's within the short period of time required for cleanup of spills under this policy. Impervious solid surfaces include, but are not limited to metals, glass, aluminum siding, and enameled or laminated surfaces.
j. Incinerator means an engineered device, approved by the Regional Administrator of the EPA, which uses controlled flamc combustion to thermally degrade PCB's and PCB Items. Examples of
Chap 1 Par 6 Page 3
1050.14A 6/20/91
such devices are rotary kilns, liquid injection incinerators, cement kilns, and high temperature boilers.
k. In or near commercial buildings means within the interior of, on the roof of, attached to the exterior wall of, in the parking area serving, or within 100 feet of a non-industrial non-substation building. Commercial buildings are typically accessible to both members of the general public and employees, and include:
(1) Public assembly properties, (2) Educational properties, (3) Institutional properties, (4) Residential properties, (5) Stores, (6) Office buildings, and (7) Transportation centers (e.g., airport terminal buildings).
l. Leak or leaking means any instance in which a PCB article, PCB container or PCB equipment has any PCB's on any portion of its external surface.
m. Manned control center means an electrical power distribution control room where the operating conditions of a PCB transformer are continuously monitored during the normal hours of operation (of the facility) and where the duty engineers, electricians, or other trained personnel have the capability to generics a PCB transformer completely within 1 minute of the receipt of a signal indicating abnormal operating conditions such as an overtemperature condition or overpressure condition in a PCB transformer.
n. Mark means the descriptive name, instructions, cautions, or other information applied to PCB's and PCB items, or other objects subject to EPA regulations.
o. Municipal solid waste means garbage, refuse, sludge, wastes, and other discarded materials resuiting from residential and non-industrial operations and activities, such as household activities, office functions, and commercial housekeeping wastes.
p. Network transformer means a transformer suitable for use in a vault to feed a variable capacity system of interconnected secondaries. These are typically used in substation applications to provide primary power to an installation or several installations. The secondary distribution of this power is accomplished with the use of a radial distribution system.
Chap 1 Page 4 Par 6
q. Nonimpervious solid surfaces means solid surfaces which are porous and are more likely to absorb spilled PCB's prior to completion of the cleanup requirements prescribed in this policy. Nonimpervious solid surfaces include wood, concrete, asphalt, and plasterboard.
r. Nonrestricted access areas means any area other than outdoor electrical substations and other restricted access locations. In addition to residential/commercial areas, these areas include unrestricted access rural areas (areas of low density development and population where access is uncontrolled by either man-made barriers or naturally occurring barriers, such as rough terrain, mountains, or cliffs).
s. On site means within the boundaries of a contiguous property unit.
t. Outdoor electrical substations means outdoor, fenced-off, and restricted access areas used in the transmission and/or distribution of electrical power. outdoor electrical substations restrict public access by being fenced or walled off as defined under 40 CFR 761.30(1)(1)(ii). For purposes of this TSCA policy, outdoor electrical substations are defined as being located at least 0.1 km from a residential or commercial area. Outdoor fenced-off and restricted access areas used in the transmissions and/or distribution of electrical power which are located less than 0.1 km from a residential/commercial area are considered to be residential/commercial areas.
u. PCB and PCB's means any chemical substance that is limited to the biphenyl molecule that has been chlorinated to varying degrees or any combination of substances which contains such substance.
v. PCB article means any manufactured article other than a PCB container that contains PCB's and whose surface(s) has been in direct contact with PCB's. PCB articles include capacitors, transformers, electric motors, pumps, pipes, and any other manufactured item:
(1) Which is formed to specific shape or design during manufacture,
(2) Which has end use function(s) dependent in whole or in part upon its shape or design during end use, and
Chap 1 Par 6 Page 5
(3) Which has cither no change of chemical composition during its end use or only those changes of composition which have no commercial purpose separate from that of the PCB article.
w. PCB article container means any package, can, bottle, bag, barrel, drum, tank, or other device used to contain PCB articles or PCB equipment, and whose surface(s) has not been in direct contact with PCB's.
x. PCB container means any package, can, bottle, bag, barrel, drum, tank, or other device that contains PCB's or PCB articles and whose surface(s) has been in direct contact with PCB'S.
y. PCB equipment means any manufactured item other than a PCB container or a PCB article container, which contains a PCB article or other PCB article container. This includes microwave ovens, electronic equipment, fluorescent light ,ballasts, and fluorescent fixtures.
z. PCB item means any PCB article, PCB container, PCB article container, or PCB equipment that deliberately or unintentionally contains or has as a part of it any PCB or PCB's at a concentration of 50 parts per million (ppm) or greater.
aa. PCB transformer means any transformer that contains PCB's at a concentration of 500 parts per million (ppm) or greater.
bb. PCB-contaminated electrical equipment means any electrical equipment, including, but not limited to, transformers, capacitors, circuit breakers, reclosers, voltage regulators, switches (including sectionalizers and motor starters), electromagnets, and cable that contain 50-499 ppm of PCB's. (States may have established more stringent levels than Federal levels.) Oil-filled electrical equipment other than circuit breakers, reclosers, and cable whose PCB concentration is unknown must be assumed to be PCB-contaminated electrical equipment. (See paragraphs 304a(4)(a) and 306a(3)(d) for provisions permitting reclassification of electrical equipment containing 500 ppm or grcater PCB's to PCB-contaminated electrical equipment.)
cc. Posing an exposure risk to food or feed means being in any location where human food or animal feed products could be exposed to PCB's released from a PCB item. A PCB item poses an exposure risk to food or feed if pCB's released in any way from the PCB item have a potential pathway to human food or animal
Chap _1 Page 6 Par6
feed. EPA considers human food and animal feed to include items regulated by the U.S. Department of Agriculture or the Food and Drug Administration as human food or animal feed; this includes direct additives. Food or feed is excluded from this definition if it is used or stored in private homes.
dd. Radial transformer means a unit substation which has a single stepdown transformer and which has an outgoing section for the connection of one or more outgoing radial (stub end) feeders.
ee. Rupture of a PCB transformer or PCB capacitor means a violent or non-violent break in the integrity of a PCB Transformer caused by an overtemperature and/or overpressure condition that results in the release of PCB's.
ff. Significant exposure means any exposure of human beings or the environment to PCB's as measured or detected by any scientifically acceptable analytical method.
gg: Soil means all vegetation, soils, and other ground media, including sand, grass, gravel, and oyster shells. It does not include concrete and asphait.
hh. Spill means both intentional and unintentional spills, leaks and other uncontrolled discharges where the release results in any quantity of PCB's running off or about to run off the external surface of the equipment or other PCB source, as well as the contamination resulting from those releases. This policy applies to spills of 50 ppm or greater PCB's. The concentration of PCB's spilled is determined by the PCB concentration of the material spilled as opposed to the concentration of PCB's in the material onto which the PCB's were spilled. Where a spill of untested mineral oil occurs, the oil is presumed to contain greater than 50 ppm, but less than 500 ppm PCB's and is subject to the relevant requirements of this policy.
ii. Spill area means the area of soil on which visible traces of the soil can be observed plus a buffer zone of 1 foot beyond the visible traces. Any surface or object within the visible trace area or on which visible traces of the spilled material are observed is included in the spill area. This area represents the minimum area assumed to be contaminated by PCB's in the absence of precleanup sampling data and is thus the minimum area which must be cleaned up.
jj. Spill boundaries means the actual area of contamination as determined by postcleanup verification sampling or by prcclcanup sampiing to detcrminc actual spill boundarics. EPA
Par 6 Chap 1 Page 7
can require additional cleanup when necessary to decontaminate all areas within the spill boundaries to the levels required in this policy (e.g., additional cleanup will be required if postcleanup sampling indicates that the area decontaminated by the responsible party, such as the spill area as defined in this section, did not encompass the actual boundaries of PCB concentration).
kk. Standard wipe test means, for spills of high-concentration PCB (500 ppm or greater) on solid surfaces, a cleanup to numerical surface standards and sampling by a standard wipe test to verify that the numerical standards have been met. This definition constitutes the minimum requirements for an appropriate wipe testing protocol. The procedure for conducting this test is contained in the EPA regulations (40 CFR 761).
ll. Totally enclosed manner means any manner that will ensure that any exposure of human beings or the environment to any concentration of PCB's will be insignificant; that is, not measurable or detectable by any scientifically acceptable analytical method.
mm. Waste oil means any used products primarily derived from petroleum, which include, but are not limited to, fuel oils, motor oils, gear oils, cutting oils, and transmission fluids.
7. REQUESTS FOR INFORMATION. Questions regarding compliance with 40 CFR Part 761 that are not answered by this order can be addressed to Office of Environment and Energy or the Regional EPA Offices (See Appendix 1 for EPA addresses and telephone numbers). In addition, answers can be provided by calling the EPA Industry Assistance Office on the nationwide toll free number, 800-424-9065 (persons in the Washington, D.C., area can reach this office by dialing 554-1404).
8. FORMS AND REPORTS. An annual report (PCB Record Inventory, RIS 1050-5) is required. See paragraph 332a.
9. AUTHORITY TO CHANGE THIS ORDER.
a. The Administrator reserves the authority to approve changes which establish policy, delegate authority, or assign responsibility.
b. The Director of Environment and Energy may issue changes to this order for compliance with the latest EPA policy related to polychlorinated biphenyls. Changes in 40 CFR Part 761 that take effect after the issuance of this order shall take
Chap 1 Page 8 Par 6
precedence over any part of this order with which it corrcsponds or conflicts. The Office of Environment and Energy will advise the responsible FAA components, listed in paragraph 9, of such changes in 40 CFR Part 761 as soon as these changes are known.
c. Changes proposed by an organizational element within FAA must be submitted to AEE. AEE will oversee the coordination of the change. After proper coordination, AEE will forward the change to the appropriate approval authority and ensure final processing authority.
10. RESPONSIBILITIES. Compliance with the policies and procedures of this order is the responsibility of the offices, services, regions, and centers.
a. Regions and FAA centers are responsible for development of implementation procedures not otherwise detailed in this order, plus assignment of personnel and other,resources necessary to carry out the provisions of this order within their respective areas of responsibility.
b. The System Maintenance Service and the Regional Airway Facilities Divisions are responsible for developing implementation procedures with the assistance of the FAA Depot and the Logistics Service and/or Regional Logistics Division covering inventorying, marking, storing, disposing, and transporting PCB's and PCB items. The Regional Airway Facilities Divisions and Sector offices are also responsible for submitting a fiscal year budget item for maintenance and disposal of hazardous substances.
c. The Office of Environment and Energy (AEE) is responsible for the overall review of FAA compliance with the provisions of 40 CFR Part 761, development of policies for implementing 40 CFR Part 761, provision of assistance to offices, services, regions, and centers in development of guidelines and procedures for their program areas, interpret policies established in this order in consultation with the responsible officials in the EPA, provide advice to responsible officials in FAA concerning changes in EPA policies relative to PCB's and PCB items in the National Airspace System (NAs), and other responsibilities as defined elsewhere. Copies of implementing instructions to be provided by FAA organizational elements wiil be reviewed for consistency with agency policy.
d. The Logistics Service (ALG) and its counterparts in the regions and centers are responsible for necessary logistic support to the NAs Transition and Implementation service and the
Chap 1 Par 9 Page 9
Systems Maintenance Service, Centers, other Regional Divisions, and the FAA Depot for marking, storing, disposing, and transporting of PCB's and PCB items. They are also responsible for reviewing all procurement and disposal documents to ensure that no PCB's or PCB articles are imported or exported without a special EPA exemption.
e. The Occupational Health Division of the Office of Aviation Medicine (AAM-7o0) and Regional Aviation Medical Divisions, in their respective areas, are responsible for: reviewing reports received from the Regional/Center Occupational Safety and Health Managers on PCB handling; providing medical guidance in the development of criteria for the safe handling of PCB's and PCB items; establishing a program (including budget requirements) for periodic physical examinations of those persons who may or have had personal contact with PCB's; and performing medical monitoring in accordance with MGL #B-5-0060 (January 13, 1986). AAM-700 is also responsible for developing the FAA Respiratory Protection Program.
f. Regional/Center Occupational Safety and Health Managers are responsible for: reviewing field reports received from Sector/facility Occupational Safety and Health officers for evidence of unsafe or unhealthy PCB handling procedures; reporting those types of inadequate PCB handling procedures to their Regional Flight Surgeon; providing copies of instructions to FAA employees so that approved procedures can be followed; notifying the Federal'Air Surgeon (AAM-1) within 72 hours of significant PCB exposures.
g. The Office of Budget should use this order as the basis for developing the annual call for estimates related to costs associated with compliance with 40 CFR Part 761.
11. POLICY. FAA will comply with all EPA procedures and policies of 40 CFR Part 761 and related orders, statutes, and regulations as well as state regulations. The FAA has been required to comply with regulations regarding the use, handling, storage, disposal, and transportation of PCB's and PCB items since 1978.State standards, which are often more stringent than Federal standards, must be complied with. Although the EPA allows the majority of PCB contaminated equipment to be used throughout its service life, it is advisable to reduce the number of PCB-tainted components wherever possible in order to avoid potential hazards and liabilities associated with its use.
12. PCB COORDINATOR. Each region and center and the Aviation Standards National Field Office shall designate an individual as
Chap 1 Page 10 Par 10
a PCB Coordinator, and shall always make the designee known to the Office of Environment and Energy (AEE-20). It will be the responsibility of the coordinator to maintain required records for inspection, testing, accidental spills/cleanup, storage, disposai, transportation, and sale of PCB Items, submit budget projections for the funding of PCB compliance measures, and to act as thc point of contact for pcB-related questions/problems.
13. FUNDING AND BUDGET REQUEST PROCEDURES. Regional AirwaY Facilities Divisions and Sector offices shall submit a fiscal year budget item for the management and disposal of hazardous substances. The estimate shall cover yearly costs for testing, disposal (transportation, storage, and incineration), and replacement components. Normal operations and faciiities and equipment budget procedures for current and future budget needs shali be followed. It is the responsibility of each region and center to submit a ycarly budget to the Airways Facilities Program and Planning Branch on the costs associated with compliance with PCB regulations (40 CFR Part 761), as required in the Annual Call for Estimates portion of Order 2500.24Y.
a. Operations Budget Requirements. The requirements which shall be considered under the operations budget are:
(1) Marking, (2) Reporting, (3) Disposing, (4) Transporting of PCB's and PCB Items, and (5) Minor cleanup
NOTE: These are recurring costs associated with the continuance of compliance with PCB regulations.
b. Facilities and Equipment (F&E) Requirements. Include within the scope of any routine modernization or relocation projects the replacement of equipment containing PCB's and any environmental cleanup measures.
c. A-106 Budget Requests. The Federal EPA requires a semiannual reporting of pollution abatement projects. Each region and center shall report all PCB-related budget projections on EPA Form 3500-7, Federal Agency Pollution Abatement Plan. All forms shall be submitted semiannually to AEE-1 as is currently required. The A-106 will be used as a tracking mechanism to ensure adequate funds are requested to implement the required PCB compliance measures.
14.-199.RESERVED.
Chav 1 Par 12 Page 11 (and 12)
CHAPTER 2. EMERGENCY PROCEDURES
CHAPTER 2. EMERGENCY PROCEDURES
200. GENERAL. This chapter describes actions that can be taken to reduce the effects of leaks, spills, or the burning of materials containing PCB's. It also provides first aid procedures (paragraph 200g below) in the event of accidental contact with pCB's. Cleanup requirements for pCB spills is contained in paragraph 362.
a. Personal contact with PCB's, regardless of its concentration, shall be reported immediately to the designated PCB Coordinator and the Regional Flight Surgeon, the Manager, Occupational Health Division, AAM-700, or the Safety/Health Official and/or the Industrial Hygienist for the local facility, through established emergency phone numbers.
b. In joint use facilities, a timely notification of the possibility of evacuating any part of the facility shall be made to, and then coordinated with, the Air Traffic Manager or his/her representative.
c. The affected areas must be restricted during emergency situations, such as a PCB equipment rupture or fire where vaporization of PCB's could expose any person. The access restriction must be strictly enforced until decontamination is complete and air monitoring results indicate levels are below the establishcd occupational limits for airborne PCB's as described in paragraph 201c.
d. FAA employees shall not participate in cleanup operations involving spills or pCB equipment fires, as discussed in paragraphs 200d and 200e. However, FAA employees may participate in the cleanup of a PCB leak if such cleanup can be accomplished without skin or eye contact with the PCB's. Commercial firms are available on a contract basis to clean up spills. If maintenance is required on the equipment in the area, personnel entering the area must wear protective clothing and respirators, as described in 20of(3)(a) and (b), to prevent skin and eye contact as well as inhalation of toxic vapors.
e. A PCB leak should be corrected as follows:
(1) Contain the liquid to prevent loss to sewer systems, navigable waterways, and streams. The liquid can be contained by prompt use of absorbent material such as sawdust, vermiculite, dry sand, clay, dirt, etc. It can also be trapped or removed by use of drip pans or trays.
Chap 2 Par 200 Page 13
(2) Notify FAA Regional PCB Coordinator.
(3) Ensure proper cleanup and removal of the PCB's in accordance with paragraph 362.
(4) Repair or replace the defective device.
f. In the event of a PCB spill or rupture:
(1) All personnel not directly involved in the cleanup or site assessment should leave the spill area.
(2) To prevent the accumulation of vapors, the spill area must be adequately ventilated (i.e., open doors, windows, operate fans, etc.).
(3) Only trained personnel wearing appropriate protective equipment shall enter the spill area:The Safety/Health Officer or the Industrial Hygienist for the facility shall be contacted to select the proper protective equipment for each situation.
(a) Clothing shall be disposable and shall prevent skin contact with the PcB's. clothing that becomes saturated with PCB's shall be removed promptly and any contaminated skin areas shall be washed with soap and water.
(b) Respiratory protection, as described in 29 CFR 1920.134, is required following a PCB leak, spill/rupture or fire/visible smoke, and during decontamination procedures. The Occupational Safety and Health Administration (OSHA) is responsible for establishing workplace exposure standards or permissible exposure limits (PEL's) for FAA employees. The 8-hour time-weighted overall PEL for airborne PCB containing 54 percent chlorine is 0.5 milligrams per cubic meter of air. For PCB containing 42 percent chlorine, the standard is 1.0 milligrams per cubic meter of air. The limits of both PEL's can be exceeded during any 8-hour work shift, provided the 8-hour time-weighted average level is not exceeded. Respiratory protection is required until airborne levels of PCB can be determined and exposure monitoring indicates that the OSHA permissible exposure limits have not been exceeded. When specifically dictated by the facility's Safety/Health Officer or Industrial Hygienist, eye and respiratory protection (as defined in 29 CFR 19i0.134, Respiratory Protection) shall be provided with respirators approved under 30 CFR 11 by the National Institute of Occupational Safety and Health or the Mine Safety and Health Administration (MSHA). Such respirators include:
Page 14 Par 200 Chap 2
1 A self-contained breathing apparatus with full facepiece operated in pressure demand or other positive pressure mode, and
2 A combination type C supplied air respirator with full facepiece operated in pressure demand or other positive pressure mode,"with an auxiliary self-contained breathing apparatus operated in pressure demand or other positive pressure mode.
(4) The spill shall be contained as stated in 200d(1). Additional measures such as blocking floor drains, containing water runoff, and controlling and treating any water or other liquids used during cleanup shall be taken as soon as possible to prevent contamination of sewer systems or streams.
(5) Contact the FAA Regional PCB Coordinator.
(6) Ensure that further spread of PCB contamination will not occur.
(7) Residues contaminated with PCB's (wiping cloths, absorbent material, used disposable protective clothing, etc.) shall be collected, placed in proper DOT-approved containers, marked as to contents, and provided proper storage prior to disposal.
(8) Contact state and regional EPA offices. If the spill is about to enter a nearby stream and/or navigable waterway (or has the potential to), inform the National Response Center (jointly operated by the U.S. Coast Guard and EPA) by telephone on (800) 424-8802.
(9) Ensure proper cleanup, removal, and disposal of PCB contaminated material in accordance with EPA or State requirements. Paragraph 362 contains Federal EPA cleanup levels for PCB spills. State standards may more stringent. FAA personnel are not to conduct cleanup actions; commercial firms are available on a contract basis to cleanup spills.
g. Fire/Visible Smoke. Fires involving PCB electrical equipment (transformers, etc.) can be responsible for the release of PCB's. PCB's released from PCB equipment in fire situations can become volatilized and converted into substances which are much more toxic than PCB. Extreme caution should be used in this situation to prevent exposure to these substances.
Chap 2 Par 200 Page 15
(1) All personnel should vacate the fire/smoke area.
(2) The area shall not be ventilated. Shut down related air handling equipment.
(3) Call the fire department and the designated Safety/Heaith Officer or Industrial Hygienist for the local facility.
(4) The fire department and/or the Safety/Health Officer shali assess the need for facility evacuation. (In joint use facilities, the Air Traffic Manager shall be consulted.)
(5) Contact FAA Regional PCB Coordinator.
(6) Contact the EPA/Coast Guard's National Response Center by telephone at (800) 424-8802.
(7) Contact State or regional EPA.
(8) Ensure that proper cleanup, removal, and disposal of contaminated material is conducted according to State or regional EPA requirements. Material may be contaminated by other than PCB and should be handled accordingly. FAA personnel are not to conduct cleanup measures. Commercial firms are available to conduct cleanup operations.
h. First-Aid Procedures.
(1) Ingestion. Consult a physician. Do not induce vomiting or give oily laxatives. If a large amount of PCB's was ingested, gastric lavage (i.e., getting one's stomach "pumped") is suggested.
(2) Skin. If PCB is splashed or spilled on the skin, remove contaminated clothing and wash skin thoroughly with soap and water. Hot PCB may cause thermal burns.
(3) Eyes: If eyes have come in contact with PCB, they shall be irrigated immediately with copious quantities of water for at least 15 minutes. A petroleum based ophthalmic ointment may be applied to the eye to relieve the irritating effects of PCB. Consult a physician immediately.
(4) Inhalation. Remove to fresh air. If respiratory irritation persists, consult a physician. (When electrical
Chap 2 Page 16 Par 200
equipment arcs over, PCB's or other chlorinated hydrocarbon dielectric fluids decompose to produce hydrochloric acid, a respiratory irritant.)
201. PRECAUTIONARY MEASURES. The storage, disposal and handling of PCB's and PCB items must be undertaken with extreme caution so that exposure to pcB's is minimized. Even at very low levels, PCB's have been determined to be hazardous to health. PCB's can enter the body through the lungs, mucous membranes, and skin. While PCB's have been identified as carcinogens, their safe handling is possible with the proper precautions.
a. Protective clothing and equipment. The worker's protective clothing and equipment shall be selected to prevent skin and eye contact with PCB's, and to control respiratory exposure to PCB vapors. The degree of protection required is dictated by the circumstances involved in a potential incident, including amount of fluid that could be spilled,"duration of the spill, and location of the PCB equipment and spill. In any operation where workers may come into contact with PcB's, protective clothing impervious to PCB's shall be worn. Gloves, heavy overalls, boots, and bib-type aprons that cover boot tops shall be worn when handling PCB's to provide skin protection. A full suit of non-porous cloth may be more appropriate for spill cleanup activities.
b. Eye protection. Chemical safety goggles, face shields with goggles, or safety glasses with shieids shall be worn during any operation in which worker's eyes may be exposed to PCB's.
c. Respiratory protection. In normal situations involving the operation and maintenance of PCB equipment (including PCB leaks), the PCB's in dielectric fluid will not vaporize in sufficient quantities to exceed the permissible exposure limit. However, each new type of work situation should be evaluated by the Safety/Health Officer or Industrial Hygienist to determine if the limit may be exceeded, so that respiratory protection as described in paragraph 200f(3) (b) will be used.
202.-299.RESERVED
Chap 2 Par 200 Page 17 (And 18)
CHAPTER 3. PROCEDURES
CHAPTER 3. PROCEDURES
SECTION 1. AUTHORIZED USES, INSPECTION REQUIREMENTS, AND SERVICING CONDITIONS FOR PCB EOUIPMENT
300. RESPONSIBLE AGENT. 40 CFR Part 761 places certain responsibilities for compliance on the user/owner of the PCB item. For purposes of this order, it is not necessary to consider whether the FAA is the user or the owner but only to define who is "responsible." Responsibility is determined by consideration of the following four categories:
SECTION 1. AUTHORIZED USES, INSPECTION REQUIREMENTS, AND SERVICING CONDITIONS FOR PCB EOUIPMENT
a. The FAA is responsible if it is or was previously the owner/operator of the PCB item at a FAA facility or originally purchased the PCB Item.
b. If a tenant at an FAA facility has a PCB item which they had purchased or obtained from a non-FAA source, the tenant is the responsible agent.
c. If non-FAA PCB items (such as power company transformers) are at an FAA facility, the owner of the item is the responsible agent.
d. If the FAA is operating a private facility, the FAA is responsible only if the item is FAA-owned or if the terms under which the FAA assumed operation of the facility gave the FAA maintenance responsibilities.
301. PCB ITEMS. PCB items (as defined in paragraph 7w) are in many FAA facilities. Most PCB's in the facilities are in dielectric fluids, either those that are categorized as PCB dielectric fluids or in non-PCB mineral oil dielectric fluids that have become contaminated in manufacturing or servicing operations. This section will discuss these PCB items, including any use restrictions, inspection requirements, and servicing conditions.
302. DIELECTRIC FLUIDS AND OTHER PCB FLUIDS.
a. Dilution of pCB fluids is prohibited. Dielectric fluids containing any pCB concentration less than 500 ppm that are mixed with fluids that contain 500 ppm PCB or greater must not be used as dielectric fluid in any electrical equipment. The entire such mixture must then be considered greater than 500 ppm PCB. [40 CFR 761.30(a)(2)(iv)].
Chap 3 Par 300 Page 19
b. The trade names of various PCB dielectric fluids are listed in Appendix 2, Fluids Containing PCB's. Representative dielectric fluids which do not contain PCB's are identified under the trade names listed in Appendix 3, Dielectric Fluids That Do Not Contain PCB's. These appendices are useful in determining transformer category and may limit the need for testing. (Testing is described in section 2 of this chapter.)
303. EXPOSURE RISK TO FOOD OR FEED PRODUCTS. "POsing an exposure risk to food or feed" means being in any location where human food or animal feed products could be exposed to PcB's released from a PCB item. A PCB item poses an exposure risk to food or feed if PCB's released in any way from the PCB item have a potential pathway to human food or animal feed. FPA considers human food and animal feed to include items regulated by the U.s. Department of Agriculture or the Food and Drug Administration as human food or animal feed; this includes direct additives. As such, 40 CFR 761 dictates that PCB's or PCB-contaminated items (transformers, capacitors, etc.) shall not be used or stored in any location where it may pose an exposure risk to food or feed.
304. TRANSFORMERS. Transformers in FAA facilities may be classified into one of three categories: PCB transformers (500 ppm PCB's or greater), PCB-contaminated transformers (50 - 499 ppm PCB's), and non-PCB transformers (less than 50 ppm PCB's).
a. PCB Transformers.
(1) Definition. PCB transformer means "any transformer that contains PCB at a concentration of 500 parts per million (ppm) or greater." Since mandatory inspections are oniy required for PCB transformers, there may be an incentive to convert PCB transformers to another category. A transformer must be assumed to be a PCB transformer if any of the following conditions exist:
(a) The nameplate or manufacturer's documentation indicates that it contains PCB dielectric fluid and there is no test data to indicate that the concentration of PCB's is less than 500 ppm.
(b) There is reason to believe that the transformer contains PCB dielectric fluid and there is no test data.
(c) The transformer dielectric fluid has been tested and found to contain 500 ppm PCB's or greater.
Chap 3 Page 20 Par 302
(d) The transformer does not have a nameplate or manufacture's documentation, there is no information available to indicate the type of dielectric fluid in it, and the transformer has not been tested to ascertain that it contains less than 500 ppm.
(2) Use conditions.
(a) The use and storage for reuse of PCB transformers that pose an exposure risk to food or feed (as defined in paragraph 7z.) is strictly prohibited.
(b) All PCB transformers (500 ppm and greater) shall be registered with the local fire department having primary jurisdiction over the facility. Information concerning the location of PCB transformers, the principle constituent of the dielectric fluid in the transformers (e.g. PCB's, mineral oil, or silicone oil), and the name and phone number of the FAA Regional and/or Sector coordinator shall be provided to the fire personnel.
(c) All combustible materials (e.g., paints, solvents, paper, etc.) stored within a PCB transformer enclosure or within i6 feet of an unenclosed PCB transformer shall be removed except when PCB transformers and stored combustibles are separated by a wall which would act to reduce the risk of starting or feeding a fire.
(d) Any PCB transformer fire-related incident shall be immediately reported to the EPA/Coast Guard's National Response Center by calling 1-800-424-8802.
(e) The following actions apply ONLY to those PCB transformers located "in or near commercial buildings" (non-industrial non-substation buildings); i.e., in or within 100 feet of an airport terminal building:
1 The installation of PCB transformers (which have been placed in storage for reuse or which have been removed from another location) is prohibited.
2 Higher voltage network PCB transformers. Effective October 1, 1990, the use of higher secondary voltage network PCB transformers (480 volts and above, including 480/277 volt systems) was prohibited. These transformers shall be removed and disposed of.
Chap 3 Par 304 Page 21
3 Lower voltage network PcB Transformers and lower voltage radial PCB Transformers. Effective October 1, 1990, all lower secondary voltage network PCB transformers (480 volts and below, including 480/277 volt systems) and lower secondary voltage radial PCB transformers shall be equipped with electrical protection to avoid transformer failures caused by high current faults. Type of protection: Current-limiting fuses or other equivalent technology shall be used to detect sustained high current faults and provide complete deenergization of the transformer within several tenths of a second, before transformer failure occurs. Accepted engineering practices shall be used.
4 Higher voltage radial PCB transformers. As of October 1, 1990, all higher voltage radial PCB Transformers (480 volts and above, including 480/277 volt systems) shall be equipped with electrical protection to avoid transformer failures caused by low current faults. Type of protection: These transformers shall use pressure and temperature sensors and disconnect equipment which would either automatically deenergize the transformer within 1 minute of receipt of the signal indicating an abnormal condition (e.g., over pressure or overtemperature in the transformer) or manually deenergize the transformer from a manned on-site control center. The manually deenergized method must also deenergize the transformer within 1 minute of receipt of an audio or visual signal indicating an abnormal condition. If the automatic operation is selected, and a circuit breaker is used for disconnection, it shall have the capability to be manually opened if needed.
(3) Inspection.
(a) Visual inspections of PCB transformers for leaks should be only as complete as safely possible. The inspection must include investigation for any leak of dielectric fluid on or around a transformer. The extent of the inspection will vary, depending on the physical constraints of each transformer installation. No visual inspection should require an electrical shutdown of the transformer being inspected. Transformers that require electrical isolation (shutdown) to be inspected thoroughly (due to safety precautions, enclosures, etc.) may be inspected as completely as possible without disconnecting the transformer. Future inspections should then be coordinated, when possible, with equipment outages from the power system so that more thorough inspections can be completed.
(b) Frequency of inspection. Each PCB transformer in use, or stored for re-use, shall be visually
Chap 3 Page 22 Par 304
inspected at least once every three months, unless the transformer meets criteria, described in (c) below, for reduced frequency of inspection. The quarterly inspections may take place any time during the three-month periods (January-March, April-June, July-September, and October-December) as long as there is a minimum of thirty days between inspections. (Refer to the chart below).
(c) Reduced frequency of inspection. The frequency of inspections can be reduced from at least once every three months to at least once every twelve months for PCB transformers that utilize either of the risk reduction measurements described below:
1 A PCB transformer which has impervious, undrained secondary containment capacity of at least 100 percent of the total dielectric fluid volume of all transformcrs so contained, or
2 A PCB transformer which has been tested and found to contain less than 60,000 ppm PCB's (after three months of in service use if the transformer has been serviced for purposes of reducing the PCB concentration).
(d) These inspections may take place any time during each calendar year as long as there is a minimum of 180 days between inspections.
Transformer Inspection Schedule:
PCB Concentration Inspection Required Frequency
50 - 499 ppm No N/A
500 - 60,000 ppm Yes every 12 months
Crcatcr than 60,000 ppm Yes cvery 3 months
500 ppm and greater plus Yes every 12 months secondary containment of the transformer.
(e) The inspection program is designed to detect leaks and prevent PcB's from entering the environment. Follow-up maintenance activities to repair a leak are required only if corrective action is necessary to stop the leak. EPA recognizes that some small leaks of dielectric fluid are unavoidable in the operation of a transformer and repairs are not always required to
Chap 3 Par 304 Page 23
stop a leak. A leak of dielectric fluid which has run off or is about to run off the external surface of a PCB transformer clearly needs repair to the transformer to prevent further leaking or replacement of the transformer. A leak of dielectric fluid which does not form a run or drip, i.e., sweat or a weep, and does not require repair to prevent further leaking, only requires proper cleanup.
(f) All leaks must be cleaned up within 48 hours of discovery and the PCB contaminated materials properly disposed of in a timely manner in accordance with the disposal requirements in section 7. Leaks must be cleaned up in accordance with the PCB cleanup requirements in paragraph 362. If dielectric fluid is actively leaking, the leak must be contained to prevent the PCB's from entering the environment or exposing humans to the PCB's. Until appropriate action is completed, the PCB transformer must be inspected daily to verify containment of the leak. Trenches, dikes, buckets, and pans are examples of proper containment measures (see paragraph 20of(4)).
(g) Records of inspection and maintenance history shall be maintained by those facilities having recordkeeping responsibilities (see section 4) for at least 3 years after disposal of the equipment and shall be made available for inspection upon EPA request (OMB Control Number 2070-0003). Such records shali contain the following information for each PCB transformer:
1 Its location.
2 Thc datc of each visual inspection and the date that a leak was discovered, if different from the inspection date.
3 The person performing the inspection.
4 The location of any leak(s).
5 An estimate of the amount of dielectric fluid released from any leak.
6 The date of any cleanup, containment, repair, or replacement.
7 A description of any cleanup, containment, or repair performed.
Chap 3 Page 24 Par 304
8 The results of any containment and daily inspection required for uncorrected active leaks.
(4) Servicinq. The servicing of any PCB transformer is prohibited unless the transformer is being converted to a transformer that is classified as PCB-contaminated electrical equipment or to a non-PCB transformer.
(a) Converting a PCB transformer to PCB-contaminated electrical equipment or to a non-PCB transformer: A PCB transformer may be converted to PCB-contaminated electrical equipment or to a non-PCB transformer by draining, refilling, and/or otherwise servicing the transformer. In order to be reclassified, the transformer's dielectric fluid must contain less than 500 ppm PCB's (for conversion to PCB-contaminated electrical equipment), or less than 50 ppm PCB's (for conversion to a non-PCB transformer), after a minimum of threc months of in-service use subsequent to the last servicing conducted for the purpose of reducing the PCB concentration in the transformer."In-service use" means that the transformer is used electrically under loaded conditions that raise the temperature of the dielectric fluid to at least 50 degrees centigrade.
NOTE: The EPA Assistant Administrator for Pesticides and Toxic Substances may grant approval for the use of alternative methods that simulate the loaded conditions of in-service use. Reguests for using alternative conditions must demonstrate that these conditions result in equivalent or greater release of PCB's from internal components of the equipment into the dielectric fluid as would occur three months of in-service use.
(b) All electrical fluids, regardless of pCB concentration, removed during the reclassification of a PCB transformer must be captured and disposed of in accordancc with the requirements of section 7. Under no circumstances shall PCB fluids be reused.
b. PCB-contaminated transformers and electrical equipment (50-499 ppm PCB's).
(1) Definition. PCB-contaminated electrical equipment means any electrical equipment, including but not limited to, transformers, capacitors, circuit breakers, reclosers, voltage regulators, switches, electromagnets, and cable that contain 50-499 ppm PCB's. Oil-filled electrical equipment other than circuit breakers, reclosers, and cable whose
Chap 3 Par 304 Page 25
PCB concentration is unknown must be assumed to be PCB-contaminated electrical equipment.
(2) Use Conditions. There are no time restrictions for use, or storage for use, of transformers that are PCB-contaminated electrical equipment.
(3) Inspection. There are no EPA-imposed nandatory inspection requirements, but a periodic visual inspection for leaks should be conducted as an adjunct to normal inspection and maintenance of equipment at FAA facilities.
(4) Servicing Conditions.
(a) Transformers classified as PCB-contaminated electrical equipment may only be serviced (including rebuilding) with dielectric fluid containing no PCB's.
(b) Converting a transformer from PCB-contaminated electrical equipment to a non-PcB transformer. A transformer that is classified as PCB-contaminated electrical equipment may be reclassified to a non-PCB transformer in the same manner used to convert a PCB transformer to a non-PCB cransformer described in paragraph 304a(4)(a).
(c) PCB fluid concentrations of 50 ppm or greater which are removed during any servicing activity must be captured and disposed of in accordance with section 7.
305.CAPACITORS.
a. Definitions.
(1) "Large high voltage capacitors" means a capacitor which contains more than 1.36 kg (3 lbs) of dielectric fluid and which operates at 2000 volts (a.c. or d.c.) or above;
(2) "Large low voltage capacitors" means a capacitor which contains 1.36 kg (3 lbs) or more of dielectric fluid and which operates BELOW 2000 volts (a.c. or d.c.).
(3) "Small capacitor" means a capacitor which contains less than 1.36 kg (3 lbs) of dielectric fluid.
b. General.
(1) It should be noted that virtually all capacitors nanufactured prior to 1978 were filled with PCB fluid at a
Page 26 Chap 3 Pagc 304
concentration near 100 percent, and that capacitors manufactured after 1978 did not use PCB fluid. Therefore, it is easy to categorize which capacitors contain PCB's and to estimate the PCB concentration without testing. The EPA prohibits the use of large PCB capacitors (500 ppm or greater PCB) in areas posing an exposure risk to food or feed, and in areas other than "restricted-access" areas. See 40 CFR 761.30(1)(1)(i) and (ii).
(2) A contained and restricted-access indoor facility is any installation that has a roof, walls, and floors that will contain any release of PCB's within the indoor location. This type of installation prevents precipitation from reaching the large PCB capacitors and has controlled access to these PCB capacitors. A building which prevents PCB releases from escaping, including escape through drains or expansion joints, would be acceptable. This type of contained and restricted-access installation allows proper cleanup of PCB's with very little exposure to humans or the environment.
(3) A restricted-access outdoor facility is any outdoor fenced or walled-in facility that restricts public access to the enclosed equipment.
c. PCB Large High Voltage Capacitors and PCB Large Low Voltage Capacitors.
(1) Use Conditions.
(a) These capacitors are prohibited from use or storage for reuse, after October 1, 1988, unless the capacitor is used, or intended for reuse, within a restricted access-outdoor facility or in a contained and restricted-access indoor facility as defined in 305b(2) above.
(b) Non-PCB capacitors shall be used whenever a capacitor is serviced or replaced.
(2) Inspection. Though there are no EPA-imposed mandatory inspection requirements, periodic visual inspections for leaks should be conducted as an adjunct to normal inspection and maintenance of equipment at FAA facilities.
(3) Servicing Conditions. There are no servicing restrictions since these capacitors are not designed for draining and refilling.
Chap 3 Par 305 Page 27
d. Small Capacitors.
(1) Use Conditions. PCB's are rarely released from small capacitors (as defined above) and EPA does not recommend that any risk reduction measures be taken with regard to small capacitors.
(2) Inspcction. Though therc arc no EPA-imposed mandatory inspection requirements, periodic visual inspections for leaks should be conducted as an adjunct to normal inspection and maintenance of equipment at FAA facilities.
(3) Servicing Conditions. There are no servicing restrictions since these capacitors are not designed for draining and refilling.
306. ELECTROMAGNETS, SWITCHES, AND VOLTAGE REGULATORS.
a. General. Electromagnets are not commonly used in FAA facilities, but voltage regulators and switches (including sectionalizers and motor starters) are frequently used to control, transmit, and distribute electric power efficiently. Though most oil-filled electromagnets, switches, and voltage reguiators were not designed to contain PCB's and most contain less than 50 ppm PcB's, these components must be considered to be PCB-contaminated electrical equipment unless the actual PCB concentration of the oil is known.
(1) Use conditions.
(a) Any concentration of PCB's may be used in oil filled switches, voltage regulators, and electromagnets, but there are servicing restrictions described in paragraph 306a(3), if the responsible agent knows the concentration and cannot consider the equipment to be PcB-contaminated electrical equipment.
(b) There are no restrictions on the use, or storage for reuse, of any oil filled switches or voltage regulators during the service life of such equipment.
(c) There are no restrictions on the use, or storage for reuse, of electromagnets that are classified as PCB-contaminated electrical equipment.
(2) Inspection. Although there are no EPA-imposed mandatory requirements, periodic visual inspections for leaks from oil-filied switches, voltage regulators, and other
Chap 3 Page 28 Par 305
oil-filled electromagnets should be conducted as an adjunct to normal inspection and maintenance of equipment at FAA facilities.
(3) Servicing Conditions.
(a) Servicing (including rebuilding) of any electromagnet, switch, or voitage regulator with PCB fluid is prohibited.
(b) Electromagnets, switches, and voltage regulators classified as PCB-contaminated electrical equipment may be serviced (including rebuilding) only with dielectric fluid containing no PCB's.
(c) PCB's removed during any servicing activity must be captured and disposed of in accordance with the requirements of section 7.
(d) Converting electromagnets, switches, and voltage regulators. An clcctromagnet, switch, or voltage regulator with a PCB concentration of at least 500 ppm may be converted to PCB-contaminated electrical equipment or to a non-PCB classification, and PCB-contaminated electrical equipment may be reclassified to a non-PCB classification by using the same methods described in paragraph 304b [see also 40 CFR 76i.30 (h)(2)(v)]. In general, converting to PCB-contaminated or non-PCB status is not recommended due to expense and difficulty involved.
307. CIRCUIT BREAKERS, FUSES, FILTERS, RECLOSERS, AND CABLE. These items are types of oil-filled electrical equipment that, generally, are not designed to contain PCB's. Available data indicate that a small percentage of such equipment contains some PCB's as a consequence of past servicing and manufacturing practices. All such equipment may be assumed to contain liess than 50 ppm PCB's, to have no use or disposal restrictions, and to be subject to a servicing restriction that limits servicing to use of dielectric fluid containing no PCB's. If any such equipment is known to contain at least 50 ppm PCB's, there are no use restrictions, but it is subject to the same servicing conditions and disposal requirements that apply to PCB-contaminated electrical equipment, such as, electromagnets, switches, and voltage regulators(paragraph 306a(3)). Inspection procedures are limited to periodic visual inspection during normal inspection and maintenance of other equipment.
Chap 3 Par 306 Page 29
308. HEAT TRANSFER SYSTEMS. The use of heat transfer systems that have contained PCB's is prohibited.
309. HYDRAULIC SYSTEMS. The use of hydraulic systems that have contained PCB's is prohibited.
310.-314. RESERVED
SECTION 2. TESTING
315. TESTING REQUIREMENTS. Testing is required to ensure proper storage and disposal of PCB items. Testing can reduce the need for, or frequency of, EPA-mandated inspections and can eliminate unnecessary fire department coordination and emergency procedures. Tested items shall be labeled in accordance with section 3. Testing shall be conducted in the following manner:
SECTION 2. TESTING
a. Transformers and other electric equipment containing oil-type dielectric (voltage regulators, switches, reclosers, circuit breakers). EPA does not require that transformers be tested to determine the PCB concentration of the fluid. In the absence of a test, EPA requires that certain assumptions be made about the transformer. If the nameplate indicates that the transformer contains PCB dielectric fluid, or if there is any reason to believe that the transformer contains PCB dielectric, then the transformer must be assumed to be a PCB transformer. A transformer designed to use mineral oil dielectric fluids must be assumed to be contaminated with 50 to 499 ppm PCB until tests prove otherwise.
b. Hydraulic equipment and heat transfer equipment. EPA regulations [40 CFR 761.30 (d) and (e)] require that all hydraulic equipment and oil-filled heat transfer equipment be tested to determine if it contains greater than 50 ppm PCB.
Capacitors. Capacitors are normally sealed and not easily tested. If a capacitor was manufactured after 1978, it will state on the nameplate that it does not contain PCB's. All other capacitors should be assumed to contain PCB's unless verified by the manufacturer as non-PCB.
d. Records of the test results shall be kept at the nearest responsibly manned FAA facility: Recordkeeping requirements for test results are contained in section 4.
Chap 3 Page 30 Par 308
e. Testing to measure the concentration of PCB's shall be performed by a laboratory qualified to test PCB's. Contact regional EPA office for assistance in finding local laboratories and proper sampling methods.
316.-319. RESERVED.
SECTION 3. MARKING
SECTION 3. MARKING
32O. MARKING REOUTREMENTS.
a. Marking shall be used to ensure proper inspection, storage, disposal, and sale of PCB items. Ail items containing, or suspected of containing, PCB's shall be tested as described in paragraph 315 and then marked in accordance with this section. (The labels to be used are pictured in figures 3-2 through 3-5.)
(1) The following marking procedure shall be used:
(a) Items containing more than 499 ppm of PCB's shall be labeled "Caution Contains PCB's". (b) Items containing 50 - 499 ppm of PCB's shall be labeled "pCB-Contaminated"; and (C) Items containing less than 50 ppm of PCB's shall be labeled "Certified".
(2) Figure 3-1 details the PCB marking requirements.
b. All PCB transformer (500 ppm or greater) locations shall be labeled with the "Caution Contains PcB's" mark as illustrated in Figure 3.2 (e.g., doors, hallways, fences, and other means of access to PCB transformers).
c. Equipment housing PCB capacitors containing more than 3 lbs. of dielectric fluid shall be labeled "Caution Contains PCB's" on an exterior side panel. No label is required on each of the small capacitors containing less than 3 lbs. of dielectric fluid.
d. Each storage area used to store PCB's and PCB items for disposal shall be labeled with the "Caution Contains PCB's" mark.
Chap 3 Par 315 Page 31
e. Transport vehicles shall be labeled on each end and side if they are loaded with PCB cntainers that contain more than 45 kg (99.4 lbs) of liquid PCB's or with one or more PCB transformers. In addition, one label is required for transport vehicles that contain PCB items and PCB containers with more than 45 kg (99.4 lbs) of liquid pCB's in concentrations of 50 to 499 ppm.
f. Where one or more large PCB high voltage capacitors are installed in a protected location (i.e., on a power pole, in a structure, or within a fence) the pole, structure, or fence shall be labeled and a record identifying the pCB capacitors shall be maintained. If these procedures are followed, the individual capacitors do not have to be marked until they are removed from service.
g. Where the label illustrated in figure 3-2 is specified but the PCB article or PCB equipment is too small to accommodate the smallest permissible size, the label illustrated in figure 3-3 may be used instead.
Chap 3 Page 32 Par 320
FIGURE 3-1. TSCA PCB MARKING REQUIREMENTS* (40 CFR 761.40)
FIGURE 3-1. TSCA PCB MARKING REQUIREMENTS* (40 CFR 761.40)
Item Marking Requirements
Transformers Mark all PCB** transformers which are in service or in storage. NOTE: Marking of PCB-contaminated transformers is recommended but not required
Transformer Enclosures Owners must mark the outside of all PCB** (for equipment transformer enclosures (vault or machinery room with 500 ppm or doors, fences or other means of access (except greater PCB) for grates and manhole covers) with the PCB mark ML (40 CFR 761.45). The mark must be placed so it is easily read by firmen responding to a fire.
Capacitors - Large Mark al1 PCB** large high voltage (LHV) capacitors High Voltage which are in service or in storage. If one or more PCB LHV Capacitors are installed in a protected location such as a pole or behind a fence, then the pole or fencé shall be marked and a record identifying the PCB LHV capacitor shall be maintained at the protected location.
Capacitors - Large Mark all PCB large low voltage (LLV) capacitors Low Voltage removed from service and in storage for disposal
Capacitors - Small After 1 JUL 1978, manufacturers must mark "NO PCBs"
Electric motors, other For each of these items, mark if coolant or fluid Heat transfer system has a PCB concentration of 50 ppm or greater & Hydraulic systems
Equipment containing a Mark all such equipment which is in service or in PCB** Transformer OR storage. PCB** LHV Capacitors
PCB Containers Mark containers which fall into categories listed above, which contain cleanup debris (soil, rags, etc.), or which contain liquid with a PCB concentration of 50 ppm or greater.
Storage Areas Mark all storage areas containing PCBs or PCB items
Transport Vehicles Mark vehicle on all four sides if loaded with more than 45 kg (99.4 1bs) of fluid containing 50 ppm or greater PCBs OR one or more PCB** transformers.
All other items No marking requirements
Additional marking required prior to transportation ** Containing 500 ppm or greater PCBs.
Chap 3 Par 320 Page 33
h. All labels required by this section must be placed in a position on the exterior of the PCB items or transport vehicle so that the labels can be easily read by persons inspecting or servicing the marked PCB items or transport vehicle.
32l. LABELING DESIGN. Labels shall meet the following designs outlined below. All labels shall be sufficiently durable to equal or exceed the life of the PCB item (including time in storage for disposal).
a. The "Caution Contains PCB's" mark, in figure 3-2, shall have letters and striping on a white or yellow background. The mark shall be at least 15.25 cm. (6 inches) on each side. Where the mark is too large to be accommodated on the equipment, a smaller mark, in figure 3-3, may be used which is 2 inches on each side.
b. The "pCB-contaminated" mark, figure 3-4, shall have letters and striping on yellow background. The mark shall be at least 15.25 cm. (6 inches) on each side.
c. The "Certified" mark, figure 3-5, shall have letters and striping on a blue background. The mark shall be at least 15.25 cm. (6 inches) on each side.
d. Labels may be obtained from sources recommended by local EPA regional offices or from commercial label suppliers.
322. MARKING UNIDENTTFIED TTEMS. If an item does not have a name plate, or other information from which one would know or could infer the PCB concentration to determine whether or not it requires marking, one should use the assumptions on pCB concentration discussed in paragraph 320 to determine marking requirements.
323.-329.RESERVED.
SECTION 4. RECORDS AND REPORTS
SECTION 4. RECORDS AND REPORTS
330. GENERAL RECORDKEEPING. Records shall be kept at each facility for the inspection, storage, disposal, and sale of PCB items. Inspections and records shali be performed by the field organization which performs regular maintenance on this equipment. The requirements concerning EPA inspection and maintenance records only apply to pCB transformers.
a. Annual Report. By February 15 of each year, an annual report shall be submitted to AEE-l which shall contain
Chap 3 Page 34 Par 320
6/20/91
1050.14A
FIGURE 3-2. THRU 3-5. PCB LABELS
FIGURE 3-2. THRU 3-5. PCB LABELS
FIGURE 3-2. CAUTION CONTAINS PCBS (Greater than 499 ppm)
CAUTION
CONTAINS
PCBs
(Polychiorinated Biphenyts)
A toxic environmental comtaminsmt requiring specisl handling and disposal in accordancs with U.S. Environmental Protection Agency Regulstions 40 CFR 761-For Disposal Informartion contact the nesrest U.S. E.P.A. Office.
in case of accidem or spil, call toll free the U.S. Coast Guard National Response Center: 80024t8802 Also Contact Td. No.
FIGURE 3-4. PCB CONTAMINATED (50-499 ppm)
PCB CONTAMINATED THE DIELECTRIC FLUID IN THIS TRANSFORMER HAS BEEN TESTED TO DETERMINE THE AMOUNT OF POLYCHLORINATED BIPHENYL(S) OPCB CONTENT. WE CERTIFY THAT, BASED ON THE TEST SAMPLE, THE FLUID CONTAINED BETWEEN 60 AND 400 PPM OF PCS AND IS THEREFORE CLASSIFIED AS A PCB-CONTAMINATED TRANSFORMER AS DEFIMED IN THE MAY 31, 197& VOL 44. NO. 106 OF THE FEDERAL BEGISTER
Bank spaoe for witien
Chap 3 Par 320
FIGURE 3-3. CAUTION CONTAINS PCBS (Greater than 499 ppm)
CAUTION CONTAUNS PCBS [Polychtorinaned Biphenyte) FOR PROPER DISPOSAL SUPORMATION CONTACT U.S SNVIRONMENTAL PROTECTION ADSNCY
FIGURE 3-5. CERTIFIED (Less than 50 ppm)
CERTIFIEDL
THE DIELECTTOC FLUID IN THIS UNIT HAS BEEN TESTED TO DETERMINE THE AMOUNT OF POLYCHLQRINATED BIPHENYL(S) (PCB CONTENT). WE CERTIFY THAT, BASED ON THE TEST SAMPLE, THE FLUID CONTAINED LESS THAN SO PPM PCB AND IS THEREFORE CLASSIFIED A NON PCB AS DEFINED IN THE MAY 31, 197D, VOL. 44, NO. 106 OF THE FEDERAL REGISTER
CERTIFIED.
1050.14A 6/20/91
information on the disposition of PCB items maintained by each facility during the previous year that has on hand PCB containers containing at least 45 kilograms (99.4 pounds) of PCB fluid, or one or more PCB transformers, or at least 50 PCB large high voltage capacitors and/or large low voltage capacitors. Records shall be maintained on all PCB disposal activity, however, an annual report for AEE-1 is not required if disposal activity totals less than 45 kilograms in 1 year.
Figure 3-6 contains an example of the type of PCB inventory record that would satisfy the requirement. Reports shall contain the reports identification symbol (RIs) number reflected in the subject line of this order. The PċB inventory record shall contain the following information:
(1) The dates when the PCB Items are,removed from service, placed in storage for disposal, placed into transport for disposal, or sold. The quantities of the PCB's and PCB Items shall be identified using the following breakdown:
(a) Total weight in kilograms of PCB's and of PCB items, including the identification of the contents, such as liquids and capacitors. Note that any requirements for weights in kilogram of PCB's may be calculated values, if the internal volumes of containers and transformers is known and is included in the reports together with any assumptions on the density (i.e., the "specific gravity") of the fluid contained in the containers or transformers.
(b) Total number of PCB transformers and total weight in kilograms of PCB's contained in the transformers.
(c) Total number of PCB large nigh and large low voltage capacitors.
Chap 3 Page 36 Par 330
Par 330 Chap 3 Installed PCB RECORD OFINVENTORY Storage Transferred1
Total Total Total Nomenciature PCB Item Quantity Woight Liquid Facility Location Date Weight Liquid Storage Trans Date Weight Liquid Transter Company. Namme, Address Date
Date: As of Disoosal 6/20/91
Total Date Wight Liquid Dispbéal Facility Name, Adatess
Received
NSN No. Each PCBs Type, Number Stord PCBs Location ferred PCBs Driver Name (Kgs) (Kgsl (Kgs)
1/: Traneler of PCBs or PCB liens requwre a Bal of Lading accnmpanying the shpment wrth sufficient copes t6 pert Mandlest) so that Page Lal Each transler driver sugns the Bill of Ladeng and keeps one copy (b) Parson receving PCB shepment at storage or drsposal lacity sugne ali copees of tho Bil of Laoing: drstritrutes one cupy to drive, one copy to
3 originatar ol shapment; reawns one copy
Figure 3-6 PCB INVENTORY RECORD
Disposed PCBs (Kgs)
1050.14A
(2) For PCB's and PCB items removed from service, the location of the storage facility and the name of the owner or operator of the facility.
(3) The total quantities of PCB's and PCB items remaining in service at the calendar year, using the same breakdown as 332a(1),(b), and (c) above.
c. Records and documents shall be maintained in the Sector, Center or airport office where the facility is located if the office is normally occupied at least 8 hours a day, and at the next higher echelon if not occupied at least 8 hours a day: Copies of this inventory shall be forwarded to the appropriate Regional or Center that has the responsibility for the administration of this program.
d. Records shall be maintained for at least five years after the facility ceases to use or to store PCB's or PCB items in the prescribed quantities.
e. These records and documents shall be available for inspection by authorized representatives of the EPA. If records and documents are not kept at the facility where PCB's or PCB items are used or stored, the facility should know the identity of the office that is maintaining records.
f. In addition to the following information required in this section, all documents, correspondence, and data concerning PCB's that are received by the FAA facility from any state or local government agency shall be kept and maintained at the office that has that assigned responsibility.
331. RECORDS FOR SALE OF PCB ITEMS.
a. If a Region chooses to sell excess PCB equipment, a bill of sale shall be completed for any transaction involving the sale of a PCB item. The same recordkeeping requirements contained in paragraph 332 shall be followed for the sale of pCB items. The guidance in this section and in Section 9, Sale of PCB Equipment, is to provide measures to ensure safe and responsible handling of PCB Equipment. However, pCB liability ultimately cannot be sold, transferred, or given away.
b. The bill of sale shall contain the following information:
(1) Buyer name, company name, address, and telephone number;
Chap 3 Page 38 Par 330
(2) Description of the FCB Item(s) sold; (3) Number of PCB Items sold; (4) Identification number of each PCB Item; and (5) Signatures of the buyer and FAA representative involved in the sale.
c. Figure 4-1 in section 9 contains an example of a bill of sale that would satisfy the above requirements.
332. PCB WASTE DISPOSAL RECORDS AND REPORTS. For PCB WaSte disposal, the EPA also requires a tracking system, described in 40 CFR 761-Subpart K, which is similar to the "cradle-to-grave" tracking system for hazardous wastes required by EPA's regulations under the Resource Conservation and Recovery Act (RCRA). There are four parts to the system:
a. Notification. (40 CFR 761.205) Those PCB waste handlers that generate (and also have an on-site, long-term PCB storage facility), dispose, commercially store, or transport pCB wastes are required to notify the EPA of such activities.
b. Manifesting. (40 CFR 761.207) Before transporting or allowing transport of PCB wastes (50 ppm PCB or greater) off-site, all generators must manifest their waste using EPA Form 8700-22, the Uniform Hazardous Waste Manifest.
(1) On the manifest, the generator designates the EPA-permitted storage or disposal facility that wiil receive the waste.
(2) If the State in which the receiving facility is located also has its own version of the manifest, then that version is to be used instead of the EPA form.
(3) At least four copies of the manifest are required for each shipment:
(a) The generator's original (b) A copy for each transporter in the chain (c) A copy for the receiving facility and (d) A copy for the receiving facility to sign and return to the generator.
NoTE: Some States also require a copy for the Statc receiving the wastes and a copy for the state in which the shipment originated.
Chap 3 Par 331 Page 39
(4) To obtain copies of the Uniform Manifest (EPA Form 8700-22), contact your PCB or hazardous waste transporter, State environmental agency, or EPA regional office (see Appendix 1).
c. EPA Identification Number. (40 CFR 761.202) Generators are to include their EPA Identification Number on the Uniform Manifest. Each Federal generator is to use the two-character State abbreviation designated by the U.S. Postal Service, followed by that facility's 10-digit General Service Administration Real Property Number.
d. Recordkeeping. (40 CFR 761.208-218) Manifest reports are to be retained for three years. Also, refer to EPA regulations concerning: exception reporting, Certificates of Disposal, unmanifested waste reports, and annual documents and reports.
333. PCB MANAGEMENT CHECKLIST. Appendix 4 Contains a "PCB Management Checklist" to be used as a self-audit of compliance with 40 CFR 761. This checklist shall be completed concurrently with the annual report required by paragraph 332(a) and then kept with other PCB records at the facility.
334-339.RESERVED
SECTION 5. STORAGE
SECTION 5. STORAGE
34O. APPROVED STORAGE.
a. Storage of PCB items shall be avoided whenever possible. FAA facilities are not required to establish or construct storage areas. Whenever possible, alternative storage areas shall be used. Approved storage may be provided through inquiry to the following:
(1) Existing military installations (2) Local utility companies (3) Local manufacturers (General Electric, Westinghouse, etc.) (4) State, county, and local government agencies (5) Approved commercial facilities (See Appendix 1 for list of EPA-approved storage/disposal facilities)
b. If pCB items must be stored on site, the proceeding requirements shall be followed:
341. LONG TERM STORAGE. Long-term storage means the storage of pCB items for over 30 days but not exceeding one year. PCB items
Chap 3 Page 40 Par 332
that are not disposed of within the 1-year deadline will be subject to penalty fees imposed by the EPA. Sufficient lead-time is necessary in order to process disposal documents so that such liabilities can be avoided. Storage of PCB items shall meet the requirements listed in this paragraph. Storage facilities shall meet the specifications contained in paragraph 342.
a. All PCB items must be inspected for leaks every 30 days.
b. Records must be kept on the identity of each PCB item received at the storage facility. Each container must bear a notation indicating the contents of the container.
c. An inspection log shall be kept in each storage facility which indicates the date each PCB item was placed into storage and when disposal occurred.
342. LONG TERM STORAGE FACILITIES.
a. Long term storage facilities must meet the following requirements:
(1) The storage facility shall have adequate roof and walls to prevent precipitation from reaching the stored PCB items. It shall have an adequate floor which has continuous curbing with a minimum six-inch high curb. The floor and curbing shall be constructed of continuous smooth and impervious materials such as Portland cement concrete or steel which will prevent or minimize penetration of PCB's. No drain valves, floor drains, expansion joints, sewer lines, or other openings which would permit the flow out of the curbed area are allowed.
(2) The floor and curb must provide a containment volume equal'to at least twice the internal volume of the largest PCB article or PCB container stored therein, or 25 percent of the total internal volume of all PCB articles or PCB containers stored therein, whichever is greater.
(3) The storage area must be located at a site which is at or above the 10o-year flood water elevation.
b. Any PCB item stored for disposal shall be removed from storage and disposed of within one year from the date when it was first placed instorage and the fluid and case incinerated.
343. SHORT-TERM STORAGE. Short term storage means the temporary storage of certain PCB items for up to a period of 30 days. Temporary storage of PCB's (500 ppm or above) is prohibited.
Chap 3 Par 341 Page 41
a. Temporary 30-day storage at an indoor facility which does not meet the criteria in paragraph 342 above may be used for certain PCB items provided a notation is attached to the PCB item or PCB container which indicates the date the PCB item was removed from service. The following PCB items are authorized to be placed in temporary storage:
(1) Non-leaking PCB articles and PCB equipment.
(2) Leaking PCB articles and PCB equipment if the PCB items are placed in a DOT-approved container that has sufficient throbbing material, such as sawdust, to absorb any liquid PCB's remaining in the PCB item.
(3) PCB containers with non-liquid PCB's, such as contaminated soil, rags, and debris.
(4) PCB containers with liquid PCB concentrations of 50 to 499 ppm. Each of the containers must bear a notation that indicates that the liquid in the drum does not exceed 500 ppm PCB'S.
b. Non-leaking and structurally undamaged PCB large high voltage capacitors and PCB contaminated electrical equipment that have not been drained of free flowing dielectric fluid may be stored on pallets next to a storage facility that meets the requirements set forth in paragraph 342. (PcB Contaminated electrical equipment which have been drained of free-flowing dielectric fluid are not subject to the requirements of section 5.)
c. Short-term storage (under the provisions of paragraph 343)will be permitted only when the adjacent storage facility has immediately available unfilled storage space equal to 10 percent of the volume of capacitors and equipment transformers stored outside the facility. The capacitors and equipment shall be checked for leaks at least once a week.
344. STORAGE MARKING. All storage areas subject to the requirements of paragraphs 342 or 343 shall be marked in accordance with section 3.
345. STORAGE HANDLING EQUIPMENT. No item of movable equipment that is used for handling PCB's and PCB items in storage facilities and that comes in direct contact with PCB's shall be removed from the storage facility area unless it is decontaminated in accordance with the procedures described in paragraph 351.
Chap 3 Page 42 Par 343
346. STORAGE CONTAINERS. Packaging for PCB storage shall be in accordance with the following provisions of Department of Transportation(DOT) regulations (49 CFR Part 178) shipping container specifications.
a. Liquid PCB's shall be stored in containers that comply with one of the following:
(1) Specification 5, paragraph 178.80
(2) Specification 5B, paragraph 178.82
(3) Specification 6D, paragraph 178.102
(4) Specification 25L, paragraph 178.35a
(5) Specification 17E, paragraph 178.116
b. Non-liquid PCB's shall be stored in containers that comply with one of the following:
(1) Specifications 5, paragraph 178.80
(2) Specifications 5B, paragraph 178.82
(3) Specification 17C, paragraph 178.115, or
(4) Containers larger than those specified above, if they are designed to provide as much protection against leaking and exposure to the environment as those specified above. In addition, they must be of the same relative strength and durability.
347.-349. RESERVED
347.-349. RESERVED
SECTION 6. DECONTAMINATION
350. PCB CONTAINERS. Decontamination of any PCB item shall be achieved by flushing the material surfaces of the item three times with a solvent (such as kerosene, xylcne, and toluene) containing less than 50 ppm PCB's. Where possible, detergents (less volatile) should be used instead of solvents. The solubility of pcB's in the solvent must be at least five percent or more by weight. Each rinse shall use a volume of the normal diluent equal to approximately ten percent of the PCB Item's capacity. The solvent may be reused for decontamination until it reaches a concentration of 50 ppm PCB's. Disposal of the solvent
SECTION 6. DECONTAMINATION
Chap 3 Par 346 Page 43
or non-liquid PCB's resulting from decontamination procedures shall be performed in accordance with the pertinent provisions of section 7. Precautionary measures are covered in paragraph 201.
351. MOBILE EQUIPMENT. Movable equipment used in the storage areas shall be decontaminated by swabbing surfaces with a solvent meeting the criteria in paragraph 350.
352.-359.RESERVED.
SECTION 7. DISPOSAL
SECTION 7. DISPOSAL
360. GENERAL.
a. Regions shall comply with local, State, and Federal regulations. A directory shall be established which contains a local, State, and Federai listing of contacts by name, telephone number, and location. A file of applicable local, State, and Federal regulations shall be maintained.
b. In general, 40 CFR Part 761 does not require PCB's and PCB items to be removed from service for disposal until the items no longer serve their intended purpose. Exceptions to the above are transformers containing PCB's which are discussed in paragraphs 304a, b, and c.
c. EPA and some states require an EPA ID number when disposing of PCB's. An ID number can be obtained by completing EPA Form 8700-12, Notification of Hazardous Waste Activity. See paragraphs 332a and c.
d. Transporters and Disposal Sites. In addition to licensing by Federal agencies, carriers and disposal sites require licensing by State EPA and DOT. Lists of approved contractors may be obtained from the responsible State agency. Regions with multi-State responsibility should subscribe to a commercial directory of Hazardous Waste Services. A directory should provide updating services at least semiannually. Listings shall be maintained by regional coordinators. A list of EPA-approved disposal companies is contained in Appendix 1.
NOTE: Materials shipped for disposal must be documented by supplying the FAA with a copy of the Uniform Hazardous Waste Manifest--EPA Form 8700-22, which indicates that the PCB materials were shipped for final disposition. See paragraph 332b.
Chap 3 Page 44 Par 350
e. Method of Disposal:
(1) All materials contaminated with PCB's (50 ppm or more, including rags, gloves, etc.) requiring disposai, shall be disposed of in an EPA-approved incinerator except those items listed below which may be disposed as municipal waste (Note: Regions are to follow State and local regulations regarding disposal of items less than 50 ppm):
(a) Small PCB capacitors (containing less than 3 pounds of dielectric fluid), unless there are 10 or more capacitors present. (Check local regulations for quantity of capacitors);
(b) Hydraulic equipment that has been drained of its dielectric fluid. (Machines whose liquid contains 1000 ppm PCB's or greater, must be flushed with solvent containing less than 50 ppm PCB's. The drained fluid and rinse fluid must be disposed of in an EPA-approved incinerator).
(c) Empty PCB containers which stored items containing 500 ppm or less of PCB's.
(d). PCB-contaminated transformers (50-499 ppm) that have been drained of its dielectric fluid.
(2) If incineration is not possible, PCB materials may be disposed in a chemical waste landfiil, in a high efficiency boiler, or in an EPA-approved alternative method of disposal which would destroy PCB's as effectively as an incinerator or high efficiency boilcr. Specific requirements for these types of disposal methods are contained in 40 cFR part 761.70 and 76i.75.
(3) Waste oil that contains a quantifiable level of PCB's (2 ppm or greater) is not to be burned in oilburning spaceheaters. Transformer oil must be assumed to contain 2 ppm PCB's or greater unless chemical analysis proves otherwise. The EPA regulations that govern the burning of waste oil are 40 CFR 266.41"(if containing hazardous waste) and 40 CFR 761.20(e).
361. SPILLS. LEAKS. AND OTHER UNCONTROLLED DISCHARCES. Spi1lS, leaks, and other uncontrolled discharges of PcB's constitute disposal of PCB's.
a. PCB Mishap Reporting:
(1) PCB mishaps (leaks, spills, rupture, fire, personnel exposure, etc.) shall be recorded in the Safety
Chap 3 Par 360 Page 45
Management Information System (SMIS). FAA Form 3900-6, FAA Mishap Report, shall be filled out and forwarded to the Regional Safety and Health Manager within 24 hours after the incident. To ensure retrieval of oniy the PCB mishaps, the narrative of the incident shall begin with: PCB mishaps. It must be entered that way for.all cases to ensure retrieval of all PCB mishaps. While completions of the form is self-explanatory, instructions are contained in Chapter 14, Order 3900.19A, Occupational Safety and Health.
(2) PCB spills that meet the criteria in subparagraph b. below shall be reported to the EPA Regional Office (Pesticides and Toxic Substances Branch) within 24 hours, to the Office of Aviation Medicine, Occupational Health and Division, AAM-700, Oklahoma City, OK, FTS 747-3711 or (405) 680-3711, and to the EPA/Coast Guard's National Response Center (at 800-424-8802, or at 426-2675 calling from Washington, DC).
b. Spills are to be reported when:
(1) the PCB concentration of the spill is 50 ppm or greater and involves more than 10 pounds of PCB-containing fluid (generally 1 gallon or more of PCB dielectric fluid);
(2) people come into direct and uncontrolled contact with PCB's, or if the extent of the spill is large enough to expose significant numbers of animals;
(3) the extent or volume of the spill is unknown, such as spills that enter drainage systems; or
(4) the spill directly contaminates surface waters, sewers, drinking water supplies, or grazing lands.
c. Spills involving less than 10 pounds of PCB's by weight do not require EPA notification; however, the spill must be cleaned up in accordance with the requirements contained in paragraph 362.
d. As a general rule, spills involving a single capacitor do not have to be reported unless PCB's threaten or enter a watercourse. Generally, transformer spills should be reported unless it is only a minor leak that is not running onto the ground. All leaks that require repair to prevent further leaking should be reported and repaired within 48 hours.
Page 46 Chap 3 Par 361
e. The FAA is required to take measures to contain a spill, but shall not clean up a spill. Qualified professionals shail conduct cleanups.
f. Spill Containment Measures: A spill shall be contained by damming or diking, plugging the leaks, and soaking up the liquid with an absorbent material such as dirt, rags, or a commercial product. (See paragraph 200d(4). Once a spill is contained, cleanup measures can begin.
362. PCB CLEANUP REOUIREMENTS. The PCB spill cleanup policy applies to spills/releases that contain 50 ppm PCB's or more. (Individual States may have more stringent threshold levels.) Spills which have occurred before May 4, 1987, are excluded from the scope of this policy.
a. The following cleanup actions must be taken after the discovery and containment of a PCB spill (Note: Cleanup measures are to be conducted by qualified professionals):
(1) Delineate and restrict the spill area 3 feet beyond any visible traces of the spill and post warning signs at the site.
(2) Notify the FAA Regional PCB Coordinator.
(3) Notify the regional EPA office.
(4) Document the area of visible contamination, noting the extent of the visible traces and the center of the visible trace area. If there are no visible traces, this should be noted and the EPA should be contacted for guidance on conducting a statistical sampling of the spill area to establish spill boundaries.
(5) Initiate cleanup of all visible traces on hard surfaces and'soil within 24 hours of discovery of a spill. Spills directly into surface waters, drinking water supplies, sewers, or grazing lands shall be reported to the EPA Regional Office (Pesticides and Toxic Substances Branch) where guidance shall be obtained on the appropriate cleanup measures.
(6) Cleanup actions must be completed within 48 hours for low concentration spills (less than 500 ppm PCB's) involving less than 1 pound of pCB's by weight. Time limits for high concentration spills (500 ppm or greater) involving 1 pound or more of PCB's by weight, wiil be determined by EPA regional offices on a case-by-case basis; EPA should be contacted as soon
Chap 3 Par 361 Page 47
as possible to negotiate time limits for completing cleanup actions for high concentration spills.
b. The level of cleanup required will vary depending upon the concentration of PCB's spilled, the type of material contaminated, and whether the spili occurred in a restricted or non-restricted area. FAA facilities are generally considered to be restricted access areas. If there is a situation where a PCB spill occurs in a non-restricted access area, cleanup requirements contained in 40 CFR Part 761.125 shall be followed. Figure 3-7 provides the cleanup requirements for PCB spills.
c. When there is any doubt about the level of cleanup required, consult with the appropriate EPA Regional Federal Facility Coordinator to obtain information on sampling methods and analytical procedures to determine whether the contaminated area has been cleaned up to the appropriate level.
d. After the completion of a cleanup, records shall be kept to certify that an area has been decontaminated. Records shall be kept for a period of 5 years. The records shall contain the following information:
(1) Source of the spill (e.g., type of equipment) (2) Date and time spill occurred (3) Date and time cleanup was completed (4) Location of spill (5) Pre-cleanup sampling data used to establish the spill boundaries (which is required when there is insufficient visible traces of liquid PCB's after a suspected leak or spill). (6) Amount and depth of soil excavated (7) Statement signed by the facility manager certifying that the cleanup requirements have been met. (8) Post-cleanup sampling data to verify the level of cleanup for high concentration spilis (500 ppm and greater) involving 1 pound or more of PCB's by weight. A brief description of the sampling methodology and analytical technique used is required. For guidance on selecting an appropriate sampling method, refer to 40 CFR Part 761.130 or contact the Regionai EPA Office (Pesticides and Toxic Substances Branch).
e. PCB shall be placed in containers as described in paragraph 346a and disposed of in accordance with paragraph 360.
f. PCB items in the form of contaminated soil, rags, cloth, etc., shall be placed in containers as described in paragraph 346b'and disposed of in accordance with paragraph 360.
363.-369.RESERVED.
Page 48 Par 361 Chap 3
FIGURE 3-7. PCB CLEANUP REQUIREMENTS
CONCENTRATION & LOCATION & TYPE OF REQUIRED CLEANUP QUANTITY OF PCB SPILL MATERIAL CONTAMINATED LEVEL & METHOD
FIGURE 3-7. PCB CLEANUP REQUIREMENTS
1. Low Concentration spil1 (1ess than 500 ppm) involving less than 1 lb. of PCB's (i.e., less than 270 gallons of untested mineral oil)
A. Indoor Commercial 10 micro-grams/ Areas, Solid Surface 100 cm2 using "standard wipe test"
B. Soil excavate "spill area" & backfill with clean soil
C. Solid Surfaces in all "double wash/ Other Locations rinse" surfaces
II. High Concentration spills (500 ppm or more) involving 1 lb or more PCB's (i.e., 270 gallons or more of untested mineral oil)
A. Outdoor Electrical Substations
1. Solid Surfaces 100 micrograms/ 100 cm2
1. Solid Surfaces 100 micrograms/ 100 cm2
2. Soil 25 ppm or
50 ppm plus posting a notice of contamination at the site
Chap 3 Par 361 Page 49
1050.14A
6/20/91
FIGURE 3-7 (CONT.) PCB CLEANUP REQUIREMENTS:
CONCENTRATION & LOCATION & TYPE OF QUANTITY OF PCB SPILL MATERIAL CONTAMINATED
CONCENTRATION & LOCATION & TYPE OF QUANTITY OF PCB SPILL MATERIAL CONTAMINATED
B. Restricted-access Areas
1. "High-contact solid"
2. "Low-contact" indoor impervious solid surfaces
3. "Low-contact outdoor" surfaces (both impervious and nonimpervious)
4. Soil
REQUIRED CLEANUP LEVEL & METHOD
10 micrograms/ 100 cm2 surfaces as measured by a "standard wipe test"
REQUIRED CLEANUP LEVEL & METHOD
10 micrograms/ 100 cm2
100 micrograms/ 100 cm2
25 ppm
Chap 3 Par 361
SECTION 8. TRANSPORT
370. VEHICLE MARKING. Each vehicle used for transportation of PCB's and PCB items shall be marked in accordance with the provisions of paragraph 320 if it is loaded with one or more PCB transformers or with PCB containers that contain more than 45 kg (99.4 lbs) of PCB's in the liquid phase in concentrations greater than 50 ppm.
SECTION 8. TRANSPORT
371. LIQUID PCB PACKAGING. PCB shall be transported in containers that comply with the Shipping Containers Specifications of the Department of Transportation listed in paragraph 346a. Containers holding liquid wastes shall be packed with sufficient absorbent material (such as sawdust or soil) to absorb the liquid.
372. NON-LIQUID PCB PACKAGING. Containers used for transporting waste PCB Items that comply with one of the DOT Shipping Container Specifications listed in paragraph 346b.
373. MARKING. All shipping containers shall bear the large PCB mark (figure 3-2), except that containers holding items that contain fluid or material with a concentration of less than 50 ppm PCB shall have the "ORM-E sticker" (i.e., Other Regulated Material) required under DOT regulations (Title 49 CFR) for transportation of hazardous materials.
374. MANIFESTS. A manifest which documents the transportation of PCB and PCB Items shall be supplied to the FAA. See paragraph 332b.
375-399.RESERVED.
SECTION 9. SALE OF PCB ITEMS
SECTION 9. SALE OF PCB ITEMS
400. REQUIREMENTS. All PCB items (as defined in paragraph 7w) that are sold shall be totally enclosed and marked with the appropriate PCB label.
401. UNMARKED ITEMS. As a condition for any sale, any unmarked item containing dielectric fluid shall be tested for pcB's and marked accordingly, i.e., "Caution Contains PCB's," or "PCB-Contaminated."
402. PROHIBITED SALES. The sale of any hydraulic system or heat transfer system that contains or had contained PCB's is strictly prohibited.
Par 370 Chap 3 Page 51
403. BILL OF SALE.
a. A bill of sale shall be completed for all transactions and kept on file. It should be noted that PCB liability cannot be sold, transferred, or given away. The intent of the bill of sale is to clarify that the buyer is responsible for the proper use and disposal of PCB items and must comply with EPA regulations. The bill of sale shall contain the following information:
(1) Buyer name, company name, address, and telephone number; (2) Description of the PCB item(s) sold; (3) Quantity of PCB items sold; (4) Identification number of each PCB item sold; and (5) Signature of the buyer and FAA representative involved in the sale.
b. Figure 4-1 contains an example of a bill of sale that meets the requirements of this section.
Chap3 Page 52 Par 403
FIGURE 4-1.
BILL OF SALE FOR PCB EOUIPMENT
BILL OF SALE FOR PCB EOUIPMENT
The FAA hereby sells the following items for the price of _to the undersigned buyer (Each item to be listed individually.)
ITEM NO. ITEM IDENTIFICATION NO. QUANTITY
(e.g., Capacitor, (Serial, Spec. or Part No. Transformer) as it appears on item) 1 Each
Continue reading ↓ 120 of 490 passages shown