CAR 514 Regulations Of The Administrator Draft Release No. 62-30 Technical Standard Order C76 Fuel Drain Valves
This document is historical. It may have been replaced. Check the official source before relying on it.
FEDERAL AVIATION AGENCY FLIGHT STANDARDS SERVICE
FEDERAL AVIATION AGENCY FLIGHT STANDARDS SERVICE
Washington 25, D. C.
June 19, 1962
REGULATIONS OF THE ADMINISTRATOR DRAFT RELEASE NO. 62-30
SUBJECT: Technical Standard Order C76 "Fuel Drain Valves"
The Flight Standards Service of the Federal Aviation Agency has under consideration an amendment to Part 514 of the Regulations of the Administrator to add a new Technical Standard Order TSO-C76 "Fuel Drain Valves". The reaSons therefor are set forth in the explanatory statement of the attached proposal which is being published in the Federal Register as a notice of proposed rule making.
REGULATIONS OF THE ADMINISTRATOR DRAFT RELEASE NO. 62-30
The Flight Standards Service desires that all persons who will be affected by the requirements of this proposal be fully informed as to its effect upon them and is therefore circulating copies in order to afford interested persons ample opportunity to submit comments as they may desire.
Because of the large number of comments which we anticipate receiving in response to this draft release, we will be unable to acknowledge receipt of each reply. However, you may be assured that all comment will be given careful consideration.
It should be noted that comments should be submitted, preferably in duplicate, to the Docket Section of the Federal Aviation Agency, and in order
to insure consideration must be received on or before August 13, 1962.
Di rector Flight Standards Service
FEDERAL AVIATION AGENCY
FEDERAL AVIATION AGENCY
FLIGHT STANDARDS SERVICE
£Regulatory Docket No. 1260; Draft Release No. 62-307
TECHNICAL STANDARD ORDERS FOR AIRCRAFT MATERIALS
PARTS, PROCESSES AND APPLIANCES
NOTICE OF PROPOSED RULE MAKING
Pursuant to the authority delegated to me by the Administrator
NOTICE OF PROPOSED RULE MAKING
(14 CFR Part 405) notice is hereby given that the Federal Aviation Agency
has under consideration a proposal to amend Part 514 of the Regulations
of the Administrator by adopting a new Technical Standard Order. This
Technical Standard Order establishes minimum performance standards for
fuel drain valves to be used on civil aircraft of the United States. The
design and testing requirements in this order are needed to provide an
adequate and uniform basis for their approval as important components of
a fuel system.
- 1 -
Interested persons may participate in the making of the proposed rule
by submitting such ,vrltten data, vie"s or arguments as they may desire.
Communications should be submitted in duplicate to the Docket Section of
the Federal Aviation Agency, Room C-226, 1711 New York Avenue, N. W.,
Washington 25, D. C. All communications received on or before August 13 ,
1962, will be considered by the Administrator before taking action on the
proposed rule. The proposals contained in this notice may be changed in
light of comments received. All comments submitted ,nIl be available in
the Docket Section for examination by interested persons at any time.
This amendment is proposed under the authority of Sectiom3l3(a) and
601 of the Federal Aviation Act of 1958 (72 Stat. 752, 775; 49 U.S.C. l354(a),
1421) •
In consideration of the foregoing it is proposed to amend Part 514 as
follows:
By adding the follmnng section 514.82:
J 514.82 Fuel drain valves - TSO-C76--(a) Applicability--(l) Minimum
performance standards. ~linimum performance standards are hereby
established for fuel drain valves for use in civil aircraft of the
United States. New models of fuel drain valves manufactured on or after
the effective date of this section shall meet
Federal Aviation Agency Standard, "Fuel Drain
the standards specified in Ire
Valves", dated May 1, 1962.
11 Copies may be obtained upon request addressed to PubliShing and Graphics Branch, Inquiry Section, MS-158, Federal Aviation Agency, Hashington 25, D.C.
- 2 -
(b) Marking. In lieu of the weight specified in J 514.3 (d)(3), the
size shall be shown.
(c) Data requirements. The manufacturer shall furnish to the Chief,
Engineering and Manufacturing Branch, Flight Standards Division, Federal
Aviation Agency, in the region in which the manufacturer is located,
together with the statement of conformance, the following:
(1) Six copies of an instruction manual describing the product and
supplying information on maintenance, overhaul, and installaion.
(2) One copy of the manufacturer's test report.
/!-'::~o; cY
Flight Standards Service
Issued in Washington, D • .c., on ____ J".un".,"'e … 12.-, 1962.
- 3 -
May 1, 1962
FAA STANDARD - FUEL DRAIN VALVES
FAA STANDARD - FUEL DRAIN VALVES
1. PURPOSE: To specify ~unum requirements for fuel drain valves that are intended to drain fuel or water from low points in aircraft fuel systems. Fluid discharge from the valve is intended to be drained to a container for inspection.
2. SCOPE: This standard covers the requirements for acceptance of fuel drain valves used as a quick means of draining fuel or water from aircraft fuel systems. These valves replace pipe plugs used in fuel tank sumps, strainers and gascolators.
3. GENERAL REQUIREMENTS,
3.1 ~~terials. Materials shall be of a high quality which experience
and/or tests have demonstrated to be suitable for use with aviation
fuels having an aromatic content from 0 to 30 percent. Synthetic rubber parts shall be age dated in accordance with ANA Bulletin No. 438.
3.2 Design and Construction.
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
Fuel Spillage. The drain valve shall be designed to permit operation without spillage or leakage of fuel on operating personnel.
Position Indication. Indication shall be provided for the open and closed position of valves. The valve shall utilize detents or other suitable means to retain the valve in the full-open or full-closed position. When manually released from the open position, the valve shall automatically return to the closed position.
Self-locking. The valve shall be provided with a means to prevent accidental opening or opening due to vibration or air loads.
Seals. The valve shall be designed so that the actuating shaft will not be subjected to valve inlet pressure when in the off position. The inlet pressure shall not tend to unseat the main seal.
Loss of Parts. Fuel drain valves shall be designed to preClude the loss of parts. Design consideration shall be given so that the main seal will remain in place and prevent fuel leakage in the event of possible damage to or loss of the valve stem from operational loads to be anticipated in service. If threaded
fittings are employed to support the valve, positive design provisions shall be included to prevent operational loads from
rotating the valve body out of its boss.
4. TEST CONDITIONS:
4.1 Atmospheric Conditions. Unless otherwise specified, all tests required by this standard shall be conducted at an atmospheric pressure of approximately 29.92 inches of mercury and at an ambient temperature of approximately 25 0 C.
4.2 Fluids. Unless otherwise specified, commercial grade aviation fuels shall be used for all tests.
5. TEST METHODS AND PERFORMANCE REQUIREMENTS:
5.1 Functional, This test shall demonstrate the ability of the valve to meet the design requirements specified in Sections 3.2.1, 3.2.2, 3.2.3, 3.2.4, and 3.2.5.
5.2
5.3
5.3.1
5.3.2
Flow Test. The drain valve shall be connected to a suitable container and the time required to pass a ~ gallon quantity of
fuel shall be determined when conducted with a maximum head of six inches of fuel. The time to flow ~ gallon shall not take longer than 30 seconds.
Leakage Tests.
Fuel Leakage. The fuel leakage test shall be conducted at pressures of four inches of fuel~ one Posoio~ 20 posoio, and 60 p.soio The pressure shall be applied to the drain valve inlet with the valve
in the closed position; there shall be no leakage.
Air Leakage. The air leakage test shall be conducted with the valve installed in a suitable test setup so that the valve inlet port is covered by fuel. Air pressure varying from 0 to five p.s.i.
shall be applied to the valve outlet port with the valve in the closed position. There shall be no air leakage evident.
-3- • 5.4 Fuel Resistance and ~treme Temperature. The fuel resistance and extreme temperature tests shall be conducted in accordance with the following table:
Test
Period 1/ Component
configuration
Test Fluid
Period duration Ambient and
test fluid temperature.
Fuel Resistance and Extreme Temperature
Test Schedule
Fuel Resistance Phase I Phase I Soak Dry y Drained and blown dry, normal condition as would be expected under
service conditions, Iports open. MIL-S-3U6, None tvoe III 96 hours 24 hours (4 days) 1580 ±2° F. or Circulating air at 1580 the normal ~2° Fo or the normal operating temper- operating temperature ature of the of the system in which system in which the component is used,
Low Temperature
Mounted as would
be expected under normal service
conditions 1/
MIL-S-3136.
tvoe I 18 hours - Lower the fluid
temperature to -670 +20 F., then maintain the fluid
temperature at -670
...
the component is whichever is higher. ±2° F. fer a minimum used, whichever of 18 hours. is higher. Operation or Actuate component None None tests during at least 4 cycles period. per day in a normal manner. Operation or Conduct leakage (a) Actuate components With temperature not tests immediately test, using for 5 cycles. (b) Conhigher than -650 F., after period. MIL-S-3136, duct functional and conduct functional type III fluid. leakage tests, using and leakage tests, MIL-S-3l36, type I using MIL-S-3l36, 1.1 fluid. type I fluid. 1.1 1.1
Each period shall follow immediately after the preceding one in the order noted o
4
The component shall be maintained in such a manner as to insure complete contact
of all nonmetallic parts with the test fluid as would be expected under normal service conditions.
3/ No leakage is allowed at any time during the test except for the first 15 minutes of the leakage test of the dry cycle.
5.5
5.5.1
5.5.2
Vibration.
Resonance. The valve shall be subjected to a resonant frequency survey of the range specified in the following table in order to determine if there exists any resonant frequencies of the parts. If resonance is encountered, the valve shall be successively vibrated along the three axes for four hours at the critical frequency.
Cvc1ing. The valve, in the closed position, shall be mounted on a vibration device, fluid pressure shall be applied to the inlet port. The valve shall be subjected to the three vibration scanning cycle tests contained in the following table:
Vibration Test
~canning cycle
test 1 2 3 Axis of vibration X Y Z Fluid pressure 60 R.s.i .• 60 p.s •. i. 60 _'Q.s..i. Scanning cycle
time 15 mino 15 mino 15 min. Number of scanning
cycles per 'test 2 2 2
The vibration test shall be conducted on the valve along three mutually perpendicular axes herein referred to as the X, Y, and Z-axes; the X axis being defined as lying along
center lines of the valve. The Procedure frequency shall be uniformly increased with respect to time through a frequency range from 10 to 500 c.p.s. with an applied double amplitude of 0.036 inch up to 75 c.p.s. and from there an applied vibration acceleration not less than ±10g. The frequency shall be similarly decreased such that the complete cycle is accomplished in the specified cycle time.
The test shall also be conducted at pressures of ~ p.s.i. and
five p.s.i. There shall be no fluid leakage during the test.
The test shall also be conducted with air pressure varying from 0-5 p.s.i. gage at the outlet port. Air leakage shall not exceed 10 cc. per minute of free air during the five p.s.i. air suction test.
There shall be no evidence of damage to the valve or loosening of parts as a result of the test.
5.6 Proof Pressure. The valve shall be in the closed position and shall be subjected to a fuel pressure of 100 +2 p.s.i. for a period of one minute at the inlet port. with the outlet port open to atmospheric pressure. There shall be no evidence of permanent distortion or other damage to the valve. There shall be no external leakage when the pressure is reduced to 60 p.s.i.
5.7 Reliability Tests. (Cycling Operations)
5.7.1 ~. The valve shall be dried in an oven at 1580 ±2° F. for
four hours and then. in the dry condition. be subjected to 2.000 complete cycles of operation.
5.7.2 Wet. The valve shall be moistened with fuel. supplied with a six inch head of fuel and then be subjected to 6.000 complete cycles of operation.
5.7.3 Post Rftiabilitv Test. Upon completion of the cycling operations. the valve shall be subjected to the Leakage Test. There shall be no leakage from any portion of the valve as the result of
the Reliability Test.