UNITED STATES OF AMERICA CIVIL AERONAUTICS BOARD WASHINGTON, D.C.

Civil.Air Regulations Amendment 04-1 (of Part 04 as promulgated on November 9, 1945) Effective: November 1, 1946

FIRE PREVENTION IN AIR CARRIER AIRCRAFT

A study of air carrier aircraft accidents in which fires have been one of the causes shows that there is a need for a change in the airworthiness requirements with respect to transport category airplanes. The investigation shows that the changes needed are not confined to any particular component of the airplane but extend to all parts of the airplane which may create. a fire hazard. The requirements hereinafter set forth are intended. to aid in preventing any fire from starting. to detect at the outset any fire which has started, to prevent the spread of any fire, and to extinguish any fire.

FIRE PREVENTION IN AIR CARRIER AIRCRAFT

It appearing to the Board that fire prevention regulations have been under consideration for several months; that proposed regulations were circulated in February and April of this year to the manufacturers of aircraft and to the sir carrier operators: that many detailed discussions have been held with the representatives of the aircraft manufacturers and the air carrier operators; that in view of the"foregoing sufficient public pro/ cedure has been afforded with regard to such rules and further notice cr public procedure woulà serve no usefül purpose; aná that any further proceedings would serve only to delay the regulations which it is in the public interest to adopt at this time;

The Civil Aeronautiçs Board finds thet the notice and public procedure provided, for in section 4(a) of the Administrative Procedure Act is unnecessary with respect to the Civil Air Regulations hereinafter set forth.

Now, therefore, effective November 1, 1946, Part 04 of the Civil Air .Regulations is amended as follows:

1. By adding the following to S 04.00:.

All aircraft certificated under the transport category, the manufacture of which is completed after September 30, 1947, shall comply with the following sections of this Part: §s 04.075, 04.38210. 04.3823C, 04.3824, 04.38251, .04.38252, 04.4113,04.4211, 04.4231(c), 04.425 through 04.4251, 04.4320, 04.4321, 04433, 04.434, 04.441 and subsections, 04.470 through 04.472, 04.49. through 04.4902, 04.491(a) and (c), and 04.4910 through 04.493.

2. By adding a. new S 04.075 to read as follows:

04.075 Susceptibility of materials to fire.

Where necessary for the purpose of determining compliance with any of the following definitions, the Administrator shall prescribe the heat conditions and testing procedures which any specific material or individual part must meet.

(a) Fireproof. "Fireproof" material means a material which will withstand heat equally well or better than steel in dimensions appropriate for the purpose for which it is to be used. When applied to material and parts used to confine fires in designated fire zones "fireproof" means that the material or part will perform this function under the most severe conditions of fire and duration likely to occur in such zones.

(b) Fire-resistant. When applied to sheet or structural members, "fire-resistant" material shall mean a material which will withstand heat equally well or better than aluminum alloy in dimensions appropriate for the purpose for which it is to be used. When applied to fluid-carrying lines, this term refers to a line and fitting assembly vhich will perform its intended protective functions under the heat and other conditions likely to occur at the particular location.

(c) Flame-resistant. "Flamc-resistant" material means material ill not support combustion to the point of propagating, beyond safe li. a flame after removal of the ignition source.

\ (d) Flash-resistant. "Flash-resistant" material means material which wilì not burn violently when ignited.

(e) Inflammable. "Inflammable" fluids or gases mean those which will ignite readily or explode.

3.·By adding a new § 04.38210 to read as follows:

04.38210 Internal doors. Where internal doors are equipped with louvres or other vontilating means, provision convonient to the crew shall be made for.closing tho flow of air through the door when such action is found necessary.

4. By adding to § 04.38230-the following:

Whore partitions betwoen compartments are equipped with louvres or other moens allowing air to floy betvcen such compartments, provision convenient to the crov shall be made 'for closing the flow of air, through the louvres or othor means when such action is found necessary.

5. By deleting §s 04.3824, 04.38240, and 04.3825, and inserting in lieu thereof the following:

04.3824 Cabin interiors. A11 compartments occupied or used by the crew or passengcrs shall comply with the following provisions:

(a) Materials shall in no case be less than flash-resistant.

(b) The wall and ceiling linings, the covering of all upholstering, floors, and furnishings shall be flame-resistant.

(c) Compartments where smoking is to be permitted shall be equipped with ash trays of the self-contained type vhich are completely removable. All other compartments shall be plecarded against smoking.

(a) All receptacles for used towels, papers, and waste shall be of fire-resistant material, and shall incorporatc covers or other provisions for containing possible firos started in the receptacles.

04.3825 Cargo and baggego compartments.

04.38250 General. Each cargo and baggoge compertment shall be designed for tho placarded maximum veight of contents and criticel load distributions at the eppropriate maximm load factors corresponding to all specified flight and ground load conditions, excluding the emergoncy landing conditions of S 04.26. Provisions shall be made to prevent the contents of such compartments from becoming a hazard by shifting under these loads. The provisions also shall be adequate to protect the passengers and crew from injury by the contont's of any compartment when the ultimate inortia force acting forward is 6 g.

04.38251 Fire precautions. Each compertment shall be designed so that, when used for the purpose of storing cargo or baggago, it shall comply with all the requiroments proscribed. for cargo or baggage compartments. It shall include no controls, wiring, lines, equipmont, or accessories, the damage or failure of which would affect the safe oporation of the cirplane, unless such item is adequately shielded, isolated, or othervise protcctod so.thet it cannot be damoged by movemont of cergo in the compartment, ond so that any breakage or failure of such item would not creato a. fire hazcrd in the compartment. Provisions shall bo made to prevent corgo or baggego from interfering with the functioning of tho fire-protective featuros of the comportment. All matericls used in the construction of corgo or boggage compartments, including tie-down cquipment, shall be flamo-rosistont or bottor.

In addition, all cargo and baggage compartments shall include provisions for safeguarding agcinst firos according to tho folloving classifications:

(a) Cargo and boggoge compartments shall be classified in the "A" category, if presence of a possible fire therein can be readily discernible

to a membor of the crew while at his station, and if all parts of the compartment aro easily accessible in flight. A hand fire extinguisher shall be available for such compartment.

(b) Cargo end baggage compartments shall be classified in the "B" category, if sufficient cccess is provided while in flight to enablo a momber of the crew to move by hand all contonts and to reach effectively all parts of the compartmont with a hend fire extinguisher. Furthermore, the design of tho compartmont shell be such that, whon the access provisions aro being used, no hazardous quantity of smoke, flames, or oxtinguishing agent will cnter any compartmont occapied by the crew or passcngers. Each compartment in this catogory shall be equipped with a separate system of an approved type smoko detoctor or fire detoctor other thon heat detoctor to give vorning at the pilot or flight engineer station. Hand fire extinguishers shall bo reedily available for use in all compertmonts of this category. Compartmonts in this catogory shall be complotely lincd with fire-resistant material, excopt that additional service lining of flcme-rosistant matorial may be employed.

(c) Cargo and baggage compartmonts shall be classifiod in tho "C" catogory, if thcy do not conform with the roquiroments for the "A" or "B" catogories. Each compartment of the "C" category shall be cquippod with: (1). a soparate systom of en approved type smoko dotector or fire detoctor other than heat detector to give warning at the pilot or flight ongineer station. end (2) an approved built-in fire-extinguishing systom controlled from the pilot or flight engincer station. Means shall bo provided to 'cxcludo hazardous quantities of smoke, flames, or extinguishing agent from entering into any compartment occupied by tho crow or passengers. Ventilation and drafts shall be furthor controlled within each such.cargo or baggage compartmont to tho extent that tho extinguishing agent providod cen control any firo vhich moy,start within tho compartment. All cargo and baggage compartmonts of this catogory shall be completely lined with firo-resistant material, oxcopt that additional service lining of flamo-resistant material may bo employed.

04,38252 Proof of complianco. Complianco with. those provisions of 6 04.38251 which rofor to tho compartment accessibility, the ontry of hazardous quentitics of smoke or oxtinguishing agont into compartments occupicd by the crow or passengors, and tho dissipation of tho extinguishing agont in category "C"" compartments. shall be domonstrated by tests in flight. It shall also be domonstrated during these tosts that no inadvertent oporation of smoke or firc detectors in adjacent or other compartments within the air-. planc vould occur as a result of fire contained in any one compartment, cither during or after extinguishment, unlcss the extinguishing system floods such compartments. simultaneously.

6. By inserting the. folloving paragraph in 04.4113:

If combustible fluid is used for propcllor do-icing, the provisions of SS 04.49 to 04.4902. inclusive, shall be complicd with.

-5

7. By deleting S.04.4231 (c), and inserting in lieu thereof the folloving:

(c) Location of fuel tanks shall comply with the provisions of 8 04.490. In addition, no portion of engine nacolle skin which lies immediately behind a major air egress opening from tho engine compartment shall act as the wall of an integral tank. Fuel tanks shall be isolated from personnel compartments by means of.fume and fuel proof onclosures.

8. By deleting SS 04.4250 and 04.4251, and inserting in lieu thereof the following:

04.4250 Lines and fittings in designated fire zones. Fuel lines and fittings in all designated fire zones (see 8 04.49) shall comply with the provisions of § 04.4901.

04.4251 Fuel valves. In addition to the requirements contained in s 04.4900 for shut-off means, all fuel valves shall be provided with positive stops or suitable index provisions in the "on" and "off" positions and shall be supported in such a manner that loads resulting from their operation or from accolerated flight conditions are not transmitted to the lines connected to the valve.

9. By insorting at the ends of 04.426 and 04.43122 the folloving:

(See also 04.4902.)

10. By deleting S§ 04.4320 and 04.4321, and inserting in lieu thereof the following:

04.4320 Lines and fittings in designated fire zones. Oil lines and fittings in all designated fire zones (see 8 04.49) shall comply with the provisions of 8 04.4901.

04.4321 0il valves. Requirements of S 04.4900 for shut-off means shall be Complied with. Closing of oil shut-off means shall not prevent feathering the propeller, unless equivalent safoty provisions are incorporated.

All oil valves shall be provided with positive stops or suitable index provisions in the "on" and "off" positions, and shall be supported in such a mannor that locds resulting from their operation or from accelerated flight conditions are not transmitted to the lines attached to the valve.

11. By inserting at the ends of Ss 04.433 and 04.434 the following:

(Soo also S 04.4902.)

12. By inserting the following paragraph in S 04.441:

No inflammable coolant shall be uscd.

13. By deleting S 04.441l0, and inserting in liou thereof tho folloving:

04.44110 Fire-rcsistant coolant lincs and fittings. If the coolant used will ienite and burn under the conditions of power-plant fires, all lines and fittings located within dosignated fire zones shall comply with the provisions of S-04.4901.

14. By deleting SS 04.470 and 04.4700, and inserting in lieu thereof the following:

04.470 Fire walls. All engines, auxiliary power units, fuel burning heaters, and other combustion equipmcnt which are intended for operation in flight shall be isolatod from the remainder of the airplane by means of·fire walls or shrouds, or other equivalent means.

04.4700 Fire wall construction. Fire valls and shrouds shall be constructed in such a manner that no hazardous quantity of air, fluids, or-flame can pass from the engine compartmont to other portions of the airplane. All openings in the firo wall or shroud shall bo sealed with closo-fitting fireproof grommcts, bushings, or fire wall fittings.

Fire walls and shrouds shall be constructod of fireproof material and shall be protected egainst corrosion. Tho folloving materials have boen found tocomply with this.requirement:

(a) heat and corrosion resistant steel 0.015 inch thick;

(b) low carbon steel, suitably protected.against corrosion, 0.018 inch thick.

15. By deleting- the second paragraph of' S 04.471, and inserting in lieu thereof the following:

Covling, unless othorvise specified by these regulations, shall be constructed of fire-resistant material. Those portions of the cowling which are subjectod to high temperatures duo to thoir proximity to cxhaust systom parts or exhaust gas impingoment shall be constructed- of firoproof material.

16. By delcting from' § 04,4804, "(Sce § 04.4251 (c).)". and inserting in licu thercof, "(Sec §.04.4251.)"

17. By deleting ss 04.49 and 04.490, and insorting in lieu thereof the following:

04.49 Powor-plant fire protection. Enginc accessory scctions, installations whero no isolation is provided botwoen the engine and accessory compartment, also regions whcrein lic axiliary pover units, fuel burning heaters, and othor combustion oquipment shall be referred to as designated fire zones. Such zones shall be protected from fire by compliance with the folloving requiroments.

04.490 Inflammable fluids. No tanks or roservoirs which aro a part of a system containing inflammable fluids or gases shall be located in designated fire zones, excopt where the fluid containcd, the design of the system, the matorials used in the tank, the shut-off means, all connections, lincs, and controls are such as to provide equivalent safety. Not less than 1/2 inch of clear air space shall bo providod potween any tank or reservoir and a fire vall or shroud isolating a designated fire zone.

04.4900 Shut-off means. Moans for each individual ongine shall be provided for shatting off or othorvise preventing hazardous quantities of fucl, oil, de-icor, and othor inflammoblc fluids from flowing into, within, or through any dosignated firo zone, except that moans neod not bo provided to shut off flow in linos forming an integral port of an enginc. In ordor to facilitate rapid and effectivo control of fires such shut-off moans shall permit an emergency oporating soquonce which is compatiblc with the emergoncy operation of othor equipment, such as foathoring the propellor. Shut-off means shall bo located outside of dosignated firc zonos, unloss cquivalent safety is provided, (soc S 04.490) cnd it shall bo show that no hazardous quantity of such inflamrable fluid pill drain into any dosignotod fire zone after shutting-off has beon accomplishod.

Adcquato provisions shall bo made to guard ageinst inadvertont operation of the shut-off means and to make it possiblo for tho crew to roopen tho shut-off means aftcr it has once been closed.

04.4901 Lincs end fittings. All lincs and fittings for semo located in dosignated firo zonos which carry inflammable fluids or gasos and vhich are under pressuro or which attach directly to the engine or are subject to relativo motion betwoon conpononts, exclusive of those linos and fittings forming an intogral part of tho engine, shall be floxible, fire-resistant linos with firo-resistant factory-fixod detachablo or other approvod fire-resistant onds. Lines and fittings thich are not subject to pressure or to relative motion between components shall bo of firo-rosistont matorials.

04.4902 Vent and drain linos. All vent and drain lines and fittings for same located in dosignated fire zonos and vhich corry inflammable fluids or gases shall comply with the provisions of § 04.490l, if the Administrator finds thet rupturo or breakage of a particular drain or vont line may result in a fire hazerd.

18. By amonding S 04.491 to designate tho prosont paregrophs (a) and (b) as (b) and (c), rospectivoly; by insorting a nov parcgraph (a); and amonding new paragraph (c) to reod es follows:

(a) Unloss it can be demonstrated that oquivalont protoction against destruction of thc airplanc in casc of firc is providod by tho use of fircproof matorials in tho nacelle and othor componcnts which would be subjected to flame, firc extinguishing systoms shali bo provided to sorvo all dosignated firo zonos.

(c): Materials in the fire extinguishing systóm shall not react chemically with the oxtinguishing agont so as to constitute a hazard.

19. By delcting S 04.4913, end insorting in liou thereof the following:

04.4913 Fire oxtinguishing system materiels. All components of fire extinguishing systems located in designated fire zoncs shall be constructed of firoproof matorials, excopt for connections which ere subject to rolative motion butveen components of the airplanc, in which case they shall be of floxiblo firo-rosistant construction so located as to minimize the possibility of failure.

20. By dcloting from the last sentonce of.S 04.4920 the folloving

. in potential firo zones.

21. By deloting S 04.493, and insorting in licu thereof the following:

04.493 Protcction of other airplonc components against firc. All airplane surfaces aft of the nacellos, in.the rogion of one nacelle diamoter on both sidos of the nacelle conter linc, shall be constructed of firo-rosistant material. This provision need not be applied to tail surfaces lying bohind nacelles unloss tho dimonsional configuration of tho, aircraft is such that the teil surfacos could bo affected roadily by heat, flames, or sparks emanating from a designatod fire zone or engino compartment of any necelle.

22. By deleting SS 04.5612 and 04.5613, and inserting in licu thercof the following:

04.5612 Lines. Hydraulic lines and fittings in all designatod fire. zones (soo s.04.49) shall comply with tho provisions of s 04.4901.

04.5613 Rosorvoirs and accumulators. Location of hydraulic resorvoirs and accumulators shall comply with the provisions of s 04.490, oxcept whon they aro an intogral part of tho engine or propeller.

By tho Civil Aoronautics Board:

(Signed) M. C. Mulligan

(SEAL) M. C. Mulligan Secretary